Product catalogue – Marine - NET
Product catalogue – Marine - NET
Product catalogue – Marine - NET
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Product</strong> <strong>catalogue</strong> <strong>–</strong> <strong>Marine</strong><br />
Fire detection and alarm systems
Objective, vision and values<br />
Protection of life and property<br />
We have one overriding principle: Our products offer customised solutions and maximum safety according to<br />
marine rules and regulations. Our fire alarm systems, which are based on standard modules, may be delivered as<br />
stand alone systems or communicate in integrated networks.<br />
World-wide<br />
The brand Eltek Fire Safety is owned by the international company Honeywell (www.honeywell.com), - one of 30<br />
selected Dow Jones Companies. Honeywell Life Safety AS (HLS), a distribution company within the division<br />
Automation and Control Solution in Honeywell, is responsible for the sales to the marine market world wide.<br />
User-friendly technology<br />
In-house developed, leading-edge technology provides users with superior safety and flexibility enabling future<br />
upgrading and expansion. The system philosophy allows communication between different units. The result is<br />
maximum safety, increased user-friendliness and the best total economy.<br />
Sales<br />
Our products are distributed through a worldwide network of dedicated agents and/or distributors offering our global<br />
operating customers local support and technical know how.<br />
Engineering<br />
Our marine engineering department provides tailor-made solutions based on customer inputs, class requirements<br />
and system design. The demand for safety, reliability and user friendliness is always considered. This requires<br />
know-how <strong>–</strong> built up during decades through our engagement in the marine market.<br />
Service<br />
• Service world-wide through our dedicated service partner.<br />
• Service performed by authorised personnel means that quality is maintained year after year.<br />
• Service contracts result in reliable operation and cheaper maintenance.<br />
• Repairs in accordance to manufacturer’s specifications.<br />
• Repairs subject to the same test procedures and guarantees as new equipment.<br />
• Remote monitoring via modem gives security.<br />
TechZone<br />
On our webpage www.eltek-fs.com you will find TechZone which is an internet service for the distribution of<br />
technical publications and other information. As our guest you can download product datasheets and other general<br />
information. As a VIP-member you will get access to publications concerning installation, service guidelines,<br />
operation, trouble- shooting, other technical documents and the opportunity to download software.<br />
2 (34)
Terms and abbreviations<br />
DELTA TECHNOLOGY:<br />
An expression covering Eltek Fire & Safety’s modular theory - EN54 compatible and flexible - that uses the latest,<br />
user friendly logic in networksystems, operational concepts and alarm signal evaluation.<br />
DELTA COMPACT:<br />
Eltek Fire & Safety's complete fire alarm panel, featuring in one cabinet the following modules as standard:<br />
DELTA OP, DELTA DA and batteries.<br />
DELTA OP:<br />
Eltek Fire & Safety’s operating panel used as the main control and display-unit <strong>–</strong> either as a fire-fighter’s or repeater<br />
panel <strong>–</strong> with possibilities for complete control of the fire alarm system. The DELTA OP panel allows for adjustment<br />
of the discovery detectors.<br />
DELTA REPEATER:<br />
Eltek Fire & Safety’s remote control and display unit <strong>–</strong> repeater panel.<br />
DELTA DA:<br />
Eltek Fire & Safety’s analogue, addressable and/or conventional fire Detection and Alarm module. The module has<br />
connections for detector loops, alarm and control circuits and communication ports. The DA module is also<br />
equipped with built-in power supply and charging units.<br />
DELTA <strong>NET</strong>:<br />
Eltek Fire & Safety fire alarm network where DELTA modules communicate via 2 two wire cables, where one is<br />
used as an emergency alarm line and the other as an eBus line.<br />
eBus:<br />
Eltek Fire & Safety’s bus for multi-master network communication between the DELTA familiy of fire alarm units.<br />
The eBus network is based on intelligent control nodes (eNodes) that communicate with each other via eComm.<br />
The nodes also implement the physical interface between the node’s microprocessor and the eBus.<br />
eComm:<br />
Eltek Fire & Safety’s communication protocol for fire alarm units connected to the multi-master and eBus network.<br />
eNode:<br />
Eltek Fire & Safety’s communication unit for the fire alarm modules connected to the multi-master eBus network.<br />
EMERGENCY ALARM LINE:<br />
To avoid loss of alarm signals due to a communication fault in the alarm system network, the DELTA modules have<br />
built-in, galvanic, insulated, electronics for hardware detection of fire alarms (emergency alarm).<br />
3 (34)
Delta system topology<br />
Main work station<br />
FireWin Presentation<br />
Ethernet<br />
modem<br />
Delta network eBus<br />
eNode<br />
Delta<br />
Decentralised<br />
solution<br />
Delta system configuration<br />
160 units in the system<br />
255 loops in the system<br />
126 detectors/loop<br />
Back-up work station/s<br />
FireWin Presentation<br />
Ethernet<br />
modem<br />
ModBus protocol<br />
IAS work station<br />
Vessel Management<br />
eNode<br />
4 (34)<br />
Ethernet<br />
modem<br />
Delta<br />
Compact<br />
solution<br />
VDR<br />
SMS<br />
Delta<br />
Em. light<br />
Delta<br />
Terminal<br />
Ethernet<br />
modem<br />
eNode<br />
<strong>Marine</strong> approved by major class societies such as<br />
ABS, BV, DNV, GL, LRS…<br />
By choosing a DELTA fire detection and alarm solution from Eltek Fire & Safety by Honeywell you obtain a system<br />
with increased safety focus, reduced installation cost, easy maintenance, less spare parts and a solution which is<br />
in compliance with the various requirements for marine applications.<br />
From the same basic modules, we configure and supply customised system solutions to suit your needs.<br />
The embedded DELTA Technology has the unique features you would find in all the system from Eltek Fire &<br />
Safety. This includes DELTA Logic+, which with artificial intelligence prevents false alarms, allows for flexible use<br />
of space and reports pre-alarms or fire alarms in the event of fire hazard.<br />
The functionality of DELTA Logic+ is implemented in every DELTA OP panel, DELTA DA module and every fire<br />
detector. DELTA Logic+ evaluates a fire hazard based on several criteria - programmed during commissioning -<br />
such as operational experience data, environmental influences, change of use in premises, etc.
Delta FireWin<br />
FireWin presentation and control software<br />
Two PC-software packets have been developed for programming Eltek Fire & Safety control units and networks.<br />
FireWin is a Windows-program that can be set up in the vessels control room, bride, communication centre etc.<br />
Via this program all the normal functions of the Delta OP can be accessed. Graphics of deck plans showing<br />
detectors and fire doors etc. are fed into the system. This then gives a visual indication of the detector giving an<br />
alarm signal or those that are non-operative. By means of these indications it is possible to follow the course of a<br />
fire situation and therefore to give value added information in order for the crew onboard to take corrective actions.<br />
FireWin Explorer is a programming tool for setting up a fire-alarm system and configuration of a network.<br />
Technicians use it when they install or service a system. The logical sequence of screen displays ensures the<br />
correct set-up of detector addresses and alarm values.<br />
5 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
COMPACT CONTROL UNITS - CONVENTIONAL<br />
Data: Description: List price:<br />
Art. no. 251062.3<br />
Delta Compact 5 loops w/eBus conventional<br />
The Delta Compact is a centralised fire detection and alarm control unit that complies with<br />
EN 54.2 and EN 54.4. The unit consists of DELTA OP control panel, DELTA DA module<br />
(incl. power-supply), ebus and batteries.<br />
Features:<br />
5 loops,<br />
3 monitored voltage outputs (e.g. alarm circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
Supplied with built-in batteries for 72 hours of emergency operation.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
DECENTRALIZED CONTROL UNITS - CONVENTIONAL<br />
Art. no. 251072.5<br />
Art. no. 251073.10<br />
Delta decentralized 5 loops w/eBus conventional<br />
The Delta unit is a decentralized fire detection and alarm control unit that complies with EN<br />
54.2 and EN 54.4. The unit may be used together with the DELTA OP or as either a stand<br />
alone control unit in a network. The Delta unit consist of a Delta DA module (incl. powersupply),<br />
ebus and batteries.<br />
Features:<br />
5 loops,<br />
3 monitored voltage outputs (e.g. alarm circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
Supplied with built-in batteries for 72 hours of emergency operation.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Delta decentralized Quad 10 loops w/eBus conventional<br />
The Delta unit is a decentralized fire detection and alarm control unit that complies with EN<br />
54.2 and EN 54.4. The unit may be used together with the DELTA OP or as either a stand<br />
alone control unit in a network. The Delta unit consist of a Delta DA module (incl. powersupply),<br />
ebus and batteries.<br />
Features:<br />
10 loops,<br />
3 monitored voltage outputs (e.g. alarm circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
Supplied with built-in batteries for 72 hours of emergency operation.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
6 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
OPERATOR PANELS for both addressable & conventional decentralized control units<br />
Data: Description: List price:<br />
Art. no. 251261.1<br />
Art. No. 251157.1<br />
Delta OP flush mounted w/eBus<br />
The flush-mounted version of the Delta OP only protrudes 5 mm above its surroundings.<br />
The Delta OP conforms to the requirements for operating-units in fire-alarm networks<br />
stated in NS-EN-54.2.<br />
Features:<br />
graphic display,<br />
output for programmable control of 64 LED’s,<br />
Incorporates communication port for eBus or RS 485.<br />
input for direct PC programming of connected units<br />
Communication:<br />
Slave/master on RS 485 and network, eBus on RS 232 and external communication on<br />
RS 232 with provision for hook-up to printer, PC, beeper etc.. NMEA 0183 to VDR.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Delta OP wall mounted w/eBus<br />
The operating panel is primarily used as an operating unit in Delta network system.<br />
The Delta OP meets the NS-EN-54.2.<br />
Features:<br />
graphic display,<br />
output for programmable control of 64 LED’s,<br />
Incorporates communication port for eBus or RS 485.<br />
Input for direct PC programming of connected units<br />
Communication:<br />
Slave/master on RS 485 and network, eBus on RS 232 and external communication on<br />
RS 232 with provision for hook-up to printer, PC, beeper etc.. NMEA 0183 to VDR.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
7 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
COMPACT CONTROL UNITS - ADDRESSABLE<br />
Data: Description: List price:<br />
Art. no. 251808.2<br />
Art. no. 251808.4<br />
Art. no. 251808.10<br />
Delta Compact Quad 2 loops addressable<br />
The Delta Compact is a centralised fire detection and alarm control unit that complies with<br />
EN 54.2 and EN 54.4. The unit consists of DELTA OP control panel, DELTA DA module<br />
(incl. power-supply) and batteries.<br />
Features:<br />
2 analogue loops,<br />
3 monitored voltage outputs (e.g. alarm circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
Supplied with built-in batteries for 72 hours of emergency operation.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Delta Compact Quad 2 loops w/eBus addressable<br />
The Delta Compact is a centralised fire detection and alarm control unit that complies with<br />
EN 54.2 and EN 54.4. The unit consists of DELTA OP control panel, DELTA DA module<br />
(incl. power-supply), ebus and batteries.<br />
Features:<br />
2 analogue loops,<br />
3 monitored voltage outputs (e.g. alarm circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
Supplied with built-in batteries for 72 hours of emergency operation.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Delta Compact 2 loops w/eBus and converter addressable<br />
The Delta Compact is a centralised fire detection and alarm control unit that complies with<br />
EN 54.2 and EN 54.4. The unit consists of DELTA OP control panel, DELTA DA module<br />
(incl. power-supply), ebus and batteries.<br />
Features:<br />
2 loops,<br />
3 monitored voltage outputs (e.g. alarm circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
1 24/12 VDC Converter<br />
Supplied with built-in batteries for 72 hours of emergency operation.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
8 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DECENTRALIZED CONTROL UNITS - ADDRESSABLE<br />
Data: Description: Price NOK:<br />
Art. no. 251807.2<br />
Art. no. 251807.4<br />
Delta decentralized Quad 2 loops w/eBus addressable<br />
The Delta unit is a decentralized fire detection and alarm control unit that complies with EN<br />
54.2 and EN 54.4. The unit may be used together with the DELTA OP or as either a stand<br />
alone control unit in a network. The Delta unit consist of a Delta DA module (incl. powersupply),<br />
ebus and batteries.<br />
Features:<br />
2 analogue loops,<br />
3 monitored voltage outputs (e.g. alarm circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
Supplied with built-in batteries for 72 hours of emergency operation.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Delta decentralized Quad 4 loops w/eBus addressable<br />
The Delta unit is a decentralized fire detection and alarm control unit that complies with EN<br />
54.2 and EN 54.4. The unit may be used together with the DELTA OP or as either a stand<br />
alone control unit in a network. The Delta unit consist of a Delta DA module (incl. powersupply),<br />
ebus and batteries.<br />
Features:<br />
4 analogue loops,<br />
3 monitored voltage outputs (e.g. alarm circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
Supplied with built-in batteries for 72 hours of emergency operation.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
9 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
<strong>NET</strong>WORK and COMMUNICATION MODULES<br />
Data: Description: Price NOK:<br />
Art. no. 251800.1<br />
Art. no. 251245.2<br />
Art. no. 235762<br />
PA-MUTE KIT<br />
Art. no. 251373.1<br />
Delta addressable DA Quad w/eBus<br />
Cost-effective detection and alarm-module for decentralised solutions. Fully meets EN<br />
54.2 requirements regarding fail-safe networks. The Delta DA is operated via the Delta OP<br />
panel.<br />
Features:<br />
2 analogue loops,<br />
3 monitored voltage outputs (e.g. alarm-bell circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
1 eBus (LON-kit)<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Delta conventional DA w/eBus<br />
Cost-effective detection and alarm-module for decentralised solutions. Fully meets EN<br />
54.2 requirements regarding fail-safe networks. The Delta DA is operated via the Delta OP<br />
panel.<br />
Features:<br />
5 conventional loops,<br />
3 monitored voltage outputs (e.g. alarm-bell circuits),<br />
2 voltage-free relay outputs<br />
1 monitored multi-function output.<br />
1 eBus (LON-kit)<br />
Approvals: DNV, GL, LR, ABS and BV<br />
eNode<br />
eNode is a marine approved interface between the FireWin PC and the communication<br />
network.<br />
The eNode is also used as an interface unit for all the fire alarm modules connected to the<br />
multi-master eBus network.<br />
Approvals: DNV<br />
Kit for muting the Fire Alarm<br />
The kit consists of a printed circuit board and a cable. When the kit is installed inside the<br />
DELTA OP it enables an input from the PA system to mute the fire alarm system.<br />
10 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DETECTORS <strong>–</strong> ADDRESSABLE range IQ8<br />
Data: Description: List price:<br />
Art. no. 802371<br />
Art. no. 802373<br />
Art. no. 802374<br />
IQ8 optical smoke detector, type O<br />
Automatic point-type fire detector with built-in scatter sensor with processor-controlled<br />
signal processing and decentralised intelligence. Suitable for the early detection of<br />
smouldering fires.<br />
Features:<br />
-slimline design<br />
-built-in isolator, in compliance with pr EN 54-17<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-alarm and operating data storage, built-in operating hours counter<br />
-approved in compliance with EN 54-7<br />
-powered loop compatible<br />
Approvals: DNV, GL, LR, ABS and BV<br />
IQ8 multisensor, type OT<br />
Multisensor with built-in optical smoke sensor and additional heat detector, sensor<br />
evaluation, with time-based signal analysis and signal correlation of both sensors for<br />
detecting smouldering fires with strong heat generation. Intelligent fire detector with<br />
decentralised intelligence, automatic function self-test, emergency mode, automatic<br />
adaptation to the environments, alarm and operating data storage, alarm indication and<br />
soft addressing.<br />
Features:<br />
-slimline design<br />
-built-in isolator, in compliance with pr EN 54-17<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-time and event controlled deactivation of sensors<br />
-powered loop compatible<br />
Approvals: DNV, GL, LR, ABS and BV<br />
IQ8 multisensor, type O 2 T<br />
Multisensor detector with two built-in optical smoke sensors with different scattered light<br />
angles as well as additional heat detector sensor evaluation for detecting everything from<br />
smouldering fires to open fires with consistent response behaviour. Smoke sensor signal<br />
identification to ensure smoke classification and reduction of deceptive alarms caused, for<br />
instance, by water vapour or dust.<br />
Features:<br />
-slimline design<br />
-built-in isolator, in compliance with pr EN 54-17<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-detection using the forward and backward scatter principle<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-time and event controlled deactivation of sensors<br />
-approved in compliance with DIN EN 54-7/5 B2, CEA 4021<br />
-powered loop compatible<br />
Approvals: DNV, GL, LR, ABS and BV<br />
11 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DETECTORS <strong>–</strong> ADDRESSABLE range IQ8<br />
Data: Description: List price:<br />
Art. no. 802375<br />
Art. no. 802473<br />
Art. no. 802171<br />
IQ8 multisensor optical smoke and heat, Type OT blue<br />
Multisensor detector with built-in optical smoke and heat detector to ensure preventive fire<br />
detection. The detector uses blue light and is meant to replace the traditionally used Ione<br />
detector. Through combined scattered light, temperature and gas evaluation, the early<br />
detection of everything from smouldering fires to open fires is guaranteed.<br />
Features:<br />
-slimline design<br />
-built-in isolator, in compliance with pr EN 54-17<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-time and event controlled deactivation of sensors<br />
-approved in compliance with DIN EN 54-7/5 A1S, CEA 4021<br />
-powered loop compatible<br />
Approvals: DNV, GL, LR, ABS and BV<br />
IQ8 multisensor, Type OTG<br />
Multisensor detector with built-in optical smoke detector, heat sensor as well as a built-in<br />
sensor for detecting carbon monoxide to ensure preventive fire detection. Through<br />
combined scattered light, temperature and gas evaluation, the early detection of everything<br />
from smouldering fires to open fires is guaranteed.<br />
Features:<br />
-slimline design<br />
-built-in isolator, in compliance with pr EN 54-17<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-time and event controlled deactivation of sensors<br />
-approved in compliance with DIN EN 54-7/5 A1S, CEA 4021<br />
-powered loop compatible<br />
Approvals: DNV, GL, LR, ABS and BV<br />
IQ8 fixed heat detector, type Tmax<br />
Heat detector with integrated limit value actuation (60°C) for the detection of fires with<br />
slowly rising temperature. Detector with processor-controlled signal processing and<br />
decentralised intelligence.<br />
Features:<br />
-slimline design<br />
-built-in isolator, in compliance with pr EN 54-17<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-constant response behaviour for detecting slowly and quickly rising temperatures<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-approved in compliance with EN 54 T 5 A1<br />
-powered loop compatible<br />
Approvals: DNV, GL, LR, ABS and BV<br />
12 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DETECTORS <strong>–</strong> ADDRESSABLE range IQ8<br />
Data: Description: List price:<br />
Art. no. 802271<br />
IQ8 rate-of-rise heat detector, type T<br />
Heat detector with fast semiconductor sensor to guarantee safe detection of fires with<br />
quickly rising temperature. The detector is also fitted with integrated limit value actuation<br />
(60°C) for the detection of fires with slowly rising temperature. Detector with processorcontrolled<br />
signal processing and decentralised intelligence.<br />
Features:<br />
-slimline design<br />
-built-in isolator, in compliance with pr EN 54-17<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-constant response behaviour for detecting slowly and quickly rising temperatures<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-approved in compliance with EN 54 T 5 A1<br />
-powered loop compatible<br />
Approvals: DNV, GL, LR, ABS and BV<br />
13 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DETECTORS <strong>–</strong> ADDRESSABLE range IQ8QUAD<br />
Data: Description: List price:<br />
Art. no. 802382<br />
Art. no. 802383<br />
IQ8QUAD multisensor with integrated sounder, type O/So<br />
Scatter smoke detector for safe and early detection of mouldering fires with light smoke<br />
generation. Intelligent detector with decentralised intelligence, automatic function self-test,<br />
CPU failure mode, alarm and operating data memory, alarm indicator, soft-addressing and<br />
operating indication. The detector is provided with a loop isolator. Along with smoke<br />
detection components, the detector is provided with a built-in sounder.<br />
Features:<br />
-slimline design<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-detection using the forward and backward scatter principle<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-time and event controlled deactivation of sensors<br />
-approved in compliance with DIN EN 54-7/5 B2, CEA 4021<br />
-powered loop compatible<br />
-built-in bus supplied and optical alarm signalling device<br />
-3.5km maximum loop length<br />
Approvals: DNV, GL, LR, ABS and BV<br />
IQ8QUAD multisensor with integrated flash, type O 2 T/F<br />
Multisensor detector with two built-in optical smoke sensors with different scattered light<br />
angles as well as additional heat detector sensor evaluation for detecting everything from<br />
smouldering fires to open fires with consistent response behaviour. The detector is<br />
provided with a built-in loop isolator and a built-in, bus supplied optical alarm signalling<br />
device. Smoke sensor signal identification to ensure smoke classification and reduction of<br />
deceptive alarms caused, for instance, by water vapour or dust. The maximum loop length<br />
amounts to 3.5km.<br />
Features:<br />
-slimline design<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-detection using the forward and backward scatter principle<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-time and event controlled deactivation of sensors<br />
-approved in compliance with DIN EN 54-7/5 B2, CEA 4021<br />
-powered loop compatible<br />
-built-in bus supplied and optical alarm signalling device<br />
-3.5km maximum loop length<br />
Approvals: DNV, GL, LR, ABS and BV<br />
14 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DETECTORS <strong>–</strong> ADDRESSABLE range IQ8QUAD<br />
Data: Description: List price:<br />
Art. no. 802384<br />
Art. no. 802385<br />
IQ8QUAD multisensor with integrated sounder, type O 2 T/So<br />
Multisensor detector with two built-in optical smoke sensors with different scattered light<br />
angles as well as additional heat detector sensor evaluation for detecting everything from<br />
smouldering fires to open fires with consistent response behaviour. The detector is<br />
provided with a built-in loop isolator and a built-in alarm signalling device. Smoke sensor<br />
signal identification to ensure smoke classification and reduction of deceptive alarms<br />
caused, for instance, by water vapour or dust. Decentralised storage of up to 19 freely<br />
programmable tone models in the detector. The volume control can be adjusted in 8 levels<br />
with additional event based programming of the volume damping level. As a precaution, a<br />
soft-start mode for optimum rising sound levels of the alarm volume can be selected. The<br />
respective alarm tone can be played with a maximum repetition rate of four times for each<br />
alarm. The maximum loop length amounts to 3.5km.<br />
Features:<br />
-slimline design<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-detection using the forward and backward scatter principle<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-time and event controlled deactivation of sensors<br />
-approved in compliance with DIN EN 54-7/5 B2, CEA 4021<br />
-powered loop compatible<br />
-built-in bus supplied alarm signalling device<br />
-Soft-start mode for protection against sudden exposure to acoustic alarm signalling<br />
-3.5km maximum loop length<br />
Approvals: DNV, GL, LR, ABS and BV<br />
IQ8QUAD multisensor w/ Sounder, flash and speech, type O2T/FSp<br />
Multisensor detector with two built-in optical smoke sensors with different scattered light<br />
angles as well as additional heat detector sensor evaluation for detecting everything from<br />
smouldering fires to open fires with consistent response behaviour. The detector is<br />
provided with a built-in loop isolator and a built-in, bus supplied optical and acoustic alarm<br />
signalling device. Smoke sensor signal identification to ensure smoke classification and<br />
reduction of deceptive alarms caused, for instance, by water vapour or dust. Decentralised<br />
storage of up to 19 freely programmable tone models as well as up to four additional texts,<br />
each announced in three languages, in the detector. The volume control can be adjusted in<br />
8 levels with additional event based programming of the volume damping level. For<br />
protecting people, a soft-start mode for optimum rising sound levels of the alarm volume<br />
can be selected. The respective alarm tone can be played with a maximum repetition rate<br />
of four times for each alarm. The maximum loop length amounts to 3.5km.<br />
Features<br />
-slimline design<br />
-centralised 360° alarm indicator<br />
-individual operating display<br />
-detection using the forward and backward scatter principle<br />
-360° thermal monitoring with one sensor<br />
-alarm and operating data storage, built-in operating hours counter<br />
-time and event controlled deactivation of sensors<br />
-approved in compliance with DIN EN 54-7/5 B2, CEA 4021<br />
-powered loop compatible<br />
-built-in bus supplied optical and acoustic alarm signalling device<br />
-multilingual announcement texts in the detector<br />
-soft-start mode for optimum protection against sudden exposure to acoustic alarm<br />
-3.5km maximum loop length<br />
Approvals: DNV, GL, LR, ABS and BV<br />
15 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
BASES for the addressable IQ8 / IQ8QUAD detectors<br />
Data: Description: List price:<br />
Art. no. 805590<br />
Art. no. 805591<br />
Art. no. 805591.01<br />
Art. no. 805572<br />
Art. no. 805571<br />
IQ8 base<br />
Standard detector base for IQ8 / IQ8QUAD detectors.<br />
IQ8 base, relay for NO w/alarm<br />
Detector base for IQ8 detectors with relay contact output.<br />
Contact: floating NO.<br />
Note: Not to be used with IQ8QUAD detectors<br />
IQ8 base, relay for NC<br />
IQ8 detector base with relay contact output.<br />
Contact: floating NC.<br />
Note: Not to be used with IQ8QUAD detectors<br />
IQ8 base, sealed for watertight applications<br />
• IP 65<br />
Requires art. no. 805590, 805591 or 805591.01 to complete the base.<br />
Note: 805591 or 805591.01 can not be used with IQ8QUAD detectors<br />
IQ8 base adapter flush mounting<br />
Adapter for installation in ceilings and for mounting the detector bases to the bottom side of<br />
false ceilings.<br />
Require art. no. 805590, 805591 or 805591.01 to complete the base<br />
Note: 805591 or 805591.01 can not be used with IQ8QUAD detectors<br />
16 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DETECTORS <strong>–</strong> CONVENTIONAL range<br />
Data: Description: List price:<br />
Art. no. 251604.08<br />
Art. no. 251604.09<br />
Art. no. 251604.02<br />
Art. no. 251604.03<br />
Art. no. 251604.04<br />
Orbis optical smoke detector<br />
Photo-electric detection of light scattered by smoke particles over a wide range of angles.<br />
The optical arrangement comprises an infra-red emitter with a prism and a photo-diode at<br />
90° to the light beam with a wide field of view. The detector’s microprocessor uses<br />
algorithms to process the sensor readings.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Orbis multisensor smoke detector<br />
Photo-electric detection of light scattered by smoke particles over a wide range of angles.<br />
The optical arrangement comprises an infra-red emitter with a prism and a photo-diode at<br />
90° to the light beam with a wide field of view. The detector’s microprocessor uses<br />
algorithms to process the sensor readings. The heat sensing element increases the<br />
sensitivity of the detector as the temperature rises.<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Orbis heat detector A1R for maximum application temp: 50°C<br />
Are temperatures in excess of 65°C likely in normal operation? NO<br />
Does the room have a maximum temperature greater than 50°C? NO<br />
Are sudden increases in heat likely in normal operations? NO<br />
If your application is as above, your choice should be: A1R<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Orbis heat detector A2S for maximum application temp: 50°C<br />
Are temperatures in excess of 65°C likely in normal operation? NO<br />
Does the room have a maximum temperature greater than 50°C? NO<br />
Are sudden increases in heat likely in normal operations? YES<br />
Is the detector likely to be at or below freezing (0°C) in normal operation: NO<br />
If your application is as above, your choice should be: A2S<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Orbis heat detector BR for maximum application temp: 65°C<br />
Are temperatures in excess of of 65°C likely in normal operation? NO<br />
Does the room have a maximum temperature greater than 50°C? YES<br />
Are sudden increases in heat likely in normal operations? NO<br />
If your application is as above, your choice should be: BR<br />
Approvals: DNV, GL, LR, ABS and BV<br />
17 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DETECTORS <strong>–</strong> CONVENTIONAL range<br />
Data: Description: List price:<br />
Art. no. 251604.05<br />
Art. no. 251604.07<br />
Orbis heat detector BS for maximum application temp: 65°C<br />
Are temperatures in excess of 65°C likely in normal operation? NO<br />
Does the room have a maximum temperature greater than 50°C? YES<br />
Are sudden increases in heat likely in normal operations? YES<br />
If your application is as above, your choice should be: BS<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Orbis heat detector CS for maximum application temp: 80°C<br />
Are temperatures in excess of 65°C likely in normal operation? YES<br />
Are sudden increases in heat likely in normal operations? YES<br />
If your application is as above, your choice should be: CS<br />
Approvals: DNV, GL, LR, ABS and BV<br />
BASES for the conventional Orbis detectors<br />
Art. no. 251604<br />
Art. no. 251604.01<br />
Art. no. 235562<br />
Orbis base<br />
• Operating Voltage: 10 <strong>–</strong> 33 VDC<br />
• Alarm current: 30 <strong>–</strong> 45 µA<br />
• Weight: 60g<br />
• Material: White polycarbonate<br />
Orbis base with relay<br />
• Operating Voltage: 10 <strong>–</strong> 33 VDC<br />
• Alarm current: 7mA at 24 VDC<br />
• Contact: NO / NC<br />
• Weight: 60g<br />
• Material: White polycarbonate<br />
Orbis base, for watertight applications<br />
• IP 65<br />
18 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
HEAT DETECTORS FOR SAUNA and COLD STORE<br />
Data: Description: List price:<br />
Art. no. 242963<br />
Art. no. 242963.01<br />
Art. no. 805864<br />
FLAME DETECTORS<br />
Art. no. 243019.01<br />
Art. no. 251811.10<br />
Heat detector sealed SW-1K, 140dgr, IP67<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Heat detector sealed SW-1K, 60dgr, IP67<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Address unit 1 in/1 out IP54<br />
An interface unit connected to art.no. 242923 and 242963.01 for the usage in an<br />
addressable system<br />
Conventional flame detector 601F-M<br />
The 601F-M is a full featured solar blind flame detector for enclosed use and boasts a high<br />
degree of false alarm immunity. The 601F-M is designed for connection to a conventional<br />
zone of point type fire detectors that may include any mix of detection technologies.<br />
Features:<br />
Unlike UV and UV/IR detection, not blinded by oil mist in machinery spaces<br />
Reduces cabling, no interface required<br />
No additional power source required<br />
Easy installation, uses a common plug in base for smoke and heat detectors<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Address unit<br />
• Supply Voltage: 230 VAC<br />
• Alarm resistor: 470ohm/2W<br />
• Quiescent current pr zone: 6mA<br />
The unit consists of a 230VAC/12VDC power converter and the refurbishment transponder<br />
unit art no 808630.<br />
19 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
EX EQUIPMENT<br />
Data: Description: List price:<br />
Art. no. 251601.01<br />
Art. no. 251601.02<br />
Art. no. 251601.04<br />
Art. No. 251601.03<br />
Art. no. 251811<br />
Optical smoke detector conventional: MF601Ex<br />
• Supply Voltage: 16 <strong>–</strong> 28 VDC<br />
• Alarm current: 48mA typical<br />
• Quiescent current: 100µA typical<br />
• Alarm indication. LED red<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Optical heat detector conventional: MF601Ex<br />
• Supply Voltage: 16 <strong>–</strong> 28 VDC<br />
• Alarm current: 48mA typical<br />
• Quiescent current: 100µA typical<br />
• Alarm indication. LED red<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Base 600/800 Ex<br />
• To be used together with detectors art.no 251601, 251601.01 & 251601.02<br />
Base for watertight applications, DHM69<br />
• IP rating: 65<br />
• To be used together with art.no 251601, 251601.01 & 251601.02<br />
Address unit Ex<br />
• Supply Voltage: 230 VAC<br />
• Alarm current: 470R/2W<br />
• Quiescent current pr zone: 6mA<br />
• 1 input for EX detectors which includes zener barrier (art. No: 07099)<br />
• 3 inputs which requires additional zener barrier art. No: 07099<br />
20 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
EX EQUIPMENT<br />
Data: Description: List price:<br />
Art. no. 07099<br />
Art. no. 235525<br />
Art. no 251561<br />
Art. no. 251589<br />
Zener barrier: KFD0-CS-Ex1.51P<br />
• IP rating: IP20<br />
• Voltage rating: Loop powered<br />
• Rated voltage: 4 - 35VDC<br />
• Current: 0-40 mA<br />
• EEx ia IIC<br />
• EMC acc. to NAMUR NE 21<br />
Zener barrier Conventional<br />
To be used together with conventional Ex detectors series MF601<br />
Manual call point EX: MEDC<br />
• Conventional<br />
• IP rating: 66<br />
Alarm siren DB7 EExia<br />
• IP rating: 65<br />
• Sound output: 103dB<br />
• Voltage rating: 24VDC<br />
• Alarm current: 14mA<br />
21 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
MANUAL CALL POINTS <strong>–</strong> For conventional system<br />
Data: Description: List price:<br />
Art. no. 251615<br />
Manual call point w/isolator<br />
• IP rating: IP43<br />
• Voltage rating: 8 <strong>–</strong> 42 VDC (for 12VDC supply)<br />
• Rated voltage: 19VDC<br />
• Alarm current: Typical 9mA, pulsed<br />
Art. no. 243037 Surface mounting base for manual call point<br />
To be used together with art.no 251615<br />
Art. no. 251615.10 Hinged Cover for manual call point<br />
Art. no. 234800<br />
To be used together with art.no 251615<br />
Manual call point w/cover<br />
• IP rating: IP55<br />
• Voltage rating: 8 <strong>–</strong> 42 VDC (for 12VDC supply)<br />
• Rated voltage: 19VDC<br />
• Alarm current: Typical 9mA, pulsed<br />
MANUAL CALL POINTS <strong>–</strong> For addressable system<br />
Art. no. 804971<br />
Manual call point w/isolator<br />
• IP rating: IP43 (IP55 with hinged cover art no.:704965)<br />
• Voltage rating: 8 <strong>–</strong> 42 VDC (for 12VDC supply)<br />
• Rated voltage: 19VDC<br />
• Alarm current: Typical 9mA, pulsed<br />
Approvals: DNV, GL, LR, ABS and BV<br />
Art. no. 704980 Surface mounting base for manual call point<br />
To be used together with art.no 804971<br />
Art. no. 704965 Hinged Cover for manual call point<br />
To be used together with art.no 804971<br />
GENERAL ALARM UNIT <strong>–</strong> For addressable & conventional system<br />
Art. no. 251406<br />
General Alarm<br />
• Switch: On/off<br />
• IP rating: IP42<br />
• Max Voltage: 230VAC 50Hz<br />
• Operating temp: -25…55°C<br />
22 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
I/O and ADDRESS UNITS<br />
Data: Description: List price:<br />
Art. no. 788611<br />
Art. no. 788612<br />
Art. no. 805863<br />
Art. no. 805864<br />
Art. no. 804864<br />
Bus transponder unit 32 LEDS<br />
Driver PCB for DELTA mimic to be connected to the loop in order to display fire<br />
doors, fire dampers, fire zones etc.<br />
Isolator<br />
Plug-in isolator for the address units. To be used for isolating loops between decks or to<br />
isolate short circuit failure on the loop etc.<br />
Technical Alarm Module, 1 input/isolator<br />
• IP rating: IP54<br />
• Loop powered<br />
• Alarm indicator: LED 5 mm, red<br />
Technical Alarm Module, 1 input/1 output<br />
• IP rating: IP54<br />
• Loop powered<br />
• Output: 1 relay NC/NO<br />
• Alarm indicator: LED 5 mm, red<br />
Technical Alarm Module, 1 input/1 output<br />
• IP rating: IP42<br />
• Loop powered<br />
• Output: 1 relay NC/NO<br />
• Alarm indicator: LED 5 mm, red<br />
23 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
I/O and ADDRESS UNITS<br />
Data: Description: List price:<br />
Art. no. 804869<br />
Art. no. 808610<br />
Art. no. 808613<br />
Art. no. 808617<br />
Art. no. 808630<br />
Technical Alarm Module, DIN-rail mounted<br />
The technical alarm module is a bus device of the fire alarm system for recognition,<br />
transmission and individual display of technical alarms.<br />
Each module includes an integrated loop isolator, which opens in case of loop short circuit<br />
to isolate the part of the loop between two loop isolators. A single wire break does not<br />
affect the loop and all devices remain in operation. The module does not require external<br />
voltage supply, as voltage is supplied by the field bus.<br />
Address unit: 12R<br />
• IP rating: 40 (IP54 when fitted in housing art.no.788650)<br />
• Supply voltage rating: 12 <strong>–</strong> 24 VDC<br />
• Analogue loop voltage:19 <strong>–</strong> 42 VDC<br />
• Current consumption:
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
I/O and ADDRESS UNITS<br />
Data: Description: List price:<br />
Art. no. 788650<br />
Art. no. 251576<br />
Enclosure for I/O and address units;<br />
• 788611, 808610, 808613, 808617 and 808630<br />
Watertight enclosure for I/O and address units;<br />
• 788611, 808610, 808613, 808617 and 808630<br />
• IP rating: 65<br />
• 4 x PG 13,5mm cable glands<br />
Requires art. no. 259546 to complete the enclosure<br />
Art. no. 259546 Mounting kit for art. no. 251576<br />
TIMER UNITS<br />
Art. no. 235685.100<br />
To be installed in art. no. 251576 to form a complete kit for a watertight solution<br />
Manual isolating unit<br />
This unit is used locally to start/stop a predefined time limited function of one or more<br />
detectors or other equipment via a multifunction (macro) embedded in the Delta OP.<br />
Art. no. 251373.3 Delta OP multi function input Card<br />
DOOR RETAINER<br />
Art. no. 243210<br />
Interface PCB located in the Delta OP receiving input from the isolating unit art.no<br />
235685.100.<br />
DOOR RETAINER: GPT/AG W/BUTTON<br />
• Holding power: 420 Nm<br />
• IP rating: 40<br />
• Power rating: 21 <strong>–</strong> 30 VDC<br />
• Push button for release<br />
25 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
ALARM UNITS<br />
Data: Description: List price:<br />
Art. no. 243104.01<br />
Art. no. 243108.01<br />
Art. no. 243118<br />
Art. no. 243120<br />
Art. no. 235312<br />
Art. no. 251516<br />
Alarm bell: MBF-6EV<br />
• Diameter: 150 mm<br />
• IP rating: 23C<br />
• Sound output: 98,8 dB(A)<br />
• Voltage rating: 20,4 <strong>–</strong> 27,6 VDC<br />
• High reliability, long life unit.<br />
Alarm-bell: MBA6-BBX4<br />
• Diameter: 150 mm<br />
• IP rating: 55<br />
• Sound output: 100,1 dB(A)<br />
• Voltage rating: 20,4 <strong>–</strong> 27,6 VDC<br />
• High reliability, long life unit.<br />
Beacon XL<br />
• Red light<br />
• 5 joule<br />
• IP rating: 55<br />
• Voltage rating: 20..28 VDC<br />
• Current consumption: 300mA<br />
Acoustic alarm<br />
• Diameter: 92 mm<br />
• IP rating: 65<br />
• Sound output: Based on the chosen 32 tones<br />
• Voltage rating: 15 <strong>–</strong> 28VDC<br />
Sealed base<br />
To be used for siren art no.: 243120 to obtain IP65 for the alarm unit<br />
Acoustic alarm<br />
• IP rating: 65<br />
• Sound output: 105 dB(A)<br />
26 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
ALARM UNITS<br />
Data: Description: List price:<br />
Art. no. 251404<br />
Art. no. 251517<br />
Art. no. 251584<br />
Art. no. 243103.01<br />
Art. no. 251364<br />
Art. no. 251424<br />
Lamp retailing<br />
• Red light (may also be delivered as orange)<br />
• IP rating: 65<br />
• 230V<br />
• Current consumption: 270 mA<br />
Sounder/strobe<br />
• 103dBA<br />
• Red light<br />
• 30-50mA<br />
Beacon XL<br />
• Red light<br />
• 10 joule<br />
• 24V<br />
Alarm buzzer, white<br />
• IP rating: 20<br />
• Sound output : 90dB/1m<br />
• Voltage: 24VDC<br />
Typhoon Air horn<br />
• Diameter: 135 mm<br />
• IP rating: Watertight<br />
• Sound output: 115 - 130 dB(A)<br />
• Air driven<br />
Typhoon Air horn w/solenoid valve 24VDC<br />
• Diameter: 135 mm<br />
• IP rating: Watertight<br />
• Sound output: 115 - 130 dB(A)<br />
• Air driven<br />
27 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
SOFTWARE<br />
Data: Description: List price:<br />
Art. no. 234676<br />
FireWin presentation. Network / client one user licence<br />
FireWin is a marine approved Windows-program that can be set up in the vessels control<br />
room, bride, communication centre etc. Via this program all the normal functions of the<br />
Delta OP can be accessed. Graphics of deck plans showing detectors and fire doors etc.<br />
are fed into the system. This then gives a visual indication of the detector giving an alarm<br />
signal or those that are non-operative. By means of these indications it is possible to follow<br />
the course of a fire situation and therefore to give value added information in order for the<br />
crew onboard to take corrective actions.<br />
Approvals: DNV<br />
Art. no. 234676.02 FireWin Network / client user licence<br />
Additional user licence towards the FireWin server<br />
Art. no. 234676.03 FireWin per. point/address from 1…500<br />
FireWin programming for systems with less than 500 addresses<br />
Art. no. 234676.04 FireWin per. point/address from 501…1000<br />
Additional FireWin programming for systems from 500 addresses and up 1000.<br />
Art. no. 234676.05 FireWin per. point/address from 1001…<br />
Additional FireWin programming for systems from 1001 addresses and upwards.<br />
28 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
HARDWARE<br />
Data: Description: List price:<br />
Art. no. 251457<br />
Art. no. 251458<br />
Art. no. 251264<br />
Art. no. 251458<br />
Workstation<br />
Art no.: 251457 - <strong>Marine</strong> approved PC<br />
Art no.: 251458 - <strong>Marine</strong> approved LCD 15” monitor<br />
Approvals: DNV<br />
DELTA MIMIC Panel<br />
Customized mimic fire alarm panel, price on request based on customers specifications.<br />
PRINTER<br />
Art. no. 245031 Paper for printer<br />
To be connected to the RS232 com port on the Delta OP, used for service and<br />
commissioning….<br />
Paper for printer art. no.: 251458<br />
Art. no. 30893.3 Cable printer <strong>–</strong> Delta OP<br />
Art. no. 235750.006 Cable eNode <strong>–</strong> PC<br />
The cable to be used between the printer art. no.: 251458 and the Delta OP’s.<br />
The cable between the FireWin PC and the eNode. Galvanic isolator is included in the<br />
cable.<br />
Cable length: 9 metre<br />
Art. no. 235750 Cable Laptop <strong>–</strong> Delta OP<br />
Cable between a laptop and the Delta OP for hook up locally regarding configurations,<br />
parameter settings and/or uploading new software version in the Delta system.<br />
Delta <strong>Product</strong> Range 29 (34) - <strong>Marine</strong>
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
ACCESSORIES<br />
Data: Description: List price:<br />
Art. no. 251454<br />
Art. no. 704966<br />
Art. no. 805588<br />
Art. no. 805589<br />
Eltek detector programmer<br />
ELTEK programming hand held tool for setting addresses for the IQ8 / IQ8QUAD<br />
detectors. The tool is recommended to be kept onboard for easy programming if a detector<br />
is to be replaced.<br />
Test key for manual call point<br />
The test key is to be used for the addressable manual call point art no: 804971<br />
Dust cover IQ8<br />
To be fitted on the IQ8 addressable detector range for dust protection<br />
Dust cover IQ8 QUAD<br />
To be fitted on the IQ8 QUAD addressable detector range for dust protection<br />
30 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
TEST EQUIPMENT<br />
Data: Description: List price:<br />
Art. no. 251613<br />
Art. no. 10325<br />
Art. no. 805580<br />
Smoke detector test starter kit<br />
Test gas for smoke detectors<br />
Eltek detector remover for IQ8 / IQ8QUAD detectors<br />
Detector removal tool for the IQ8 / IQ8QUAD detector range when height is an issue for<br />
cleaning or replacing a detector<br />
31 (34)
Delta <strong>Product</strong> Range - <strong>Marine</strong><br />
DETECTOR LABELS<br />
Data: Description: List price:<br />
Art. no. 259525.01 Labels detector no.01.001-01.126<br />
Art. no. 259525.02 Labels detector no. 02.001-02.126<br />
Art. no. 259525.03 Labels detector no. 03.001-03.126<br />
Art. no. 259525.04 Labels detector no. 04.001-04.126<br />
Art. no. 259525.05 Labels detector no. 05.001-05.126<br />
Art. no. 259525.06 Labels detector no. 06.001-06.126<br />
Art. no. 259525.07 Labels detector no. 07.001-07.126<br />
Art. no. 259525.08 Labels detector no. 08.001-08.126<br />
Art. no. 259525.09 Labels detector no. 09.001-09.126<br />
Art. no. 259525.10 Labels detector no.10.001-10.126<br />
Art. no. 259525.11 Labels detector no.11.001-14.126<br />
32 (34)
33 (34)
Frode Lundeby: Sales Manager <strong>Marine</strong><br />
� +47 32 24 48 77<br />
� +47 907 74 178<br />
� frode.lundeby@honeywell.com<br />
Gisle Kevin: Area Sales Manager <strong>Marine</strong><br />
� +47 32 24 48 49<br />
� +47 905 79 130<br />
� gisle.kevin@honeywell.com<br />
Kjetil Venås: Project Manager <strong>Marine</strong><br />
� +47 32 24 48 46<br />
� +47 481 31 526<br />
� kjetil.venas@honeywell.com<br />
Customer Support <strong>Marine</strong><br />
� +47 815 44 045<br />
� nordic.support@honeywell.com<br />
Honeywell Life Safety AS<br />
34 (34)<br />
Honeywell Life Safety<br />
Company Address:<br />
Terminalen 16, Lierstranda Ind.<br />
3400 Lier<br />
NORWAY<br />
Postal Address:<br />
P.O. Box 3514<br />
3007 Drammen<br />
NORWAY<br />
Phone.: +47 32 24 48 00<br />
Fax. : +47 32 24 48 01<br />
www.eltek-fs.com<br />
Lierstranda Industriområde, P.O. Box 3514, 3007 Drammen, Norway Phone: +47 32 24 48 00<br />
E-mail: fire.safety@honeywell.com Bank Giro Acc.: 6138.06.30140<br />
Internet: www.eltek-fs.com Registered No: NO 981 336 305 MVA<br />
Fax: +47 32 24 48 01