733.06<br />

The master controller is typically located in a local intersection cabinet; however,<br />

in special circumstances it may be located at a Remote Monitoring Station site.<br />

The master controller is capable <strong>of</strong> uploading/downloading information to local<br />

intersection controllers <strong>and</strong> the Remote Monitoring Station.<br />

B. Functional Requirements.<br />

1. Design. Furnish a solid state, digital microprocessor master<br />

controller design. Furnish a controller that uses menu driven prompts, unless <strong>of</strong><br />

Type 170 design. If the master controller is used with Type 170E or Type 2070<br />

controllers, provide s<strong>of</strong>tware unless otherwise shown on the plans.<br />

Furnish a master controller that has a RS-232 port for connection to a<br />

laptop computer or printer. Furnish s<strong>of</strong>tware <strong>and</strong> connector cables for<br />

communication with a laptop.<br />

2. Local Controllers. Ensure that each master controller is able to<br />

supervise <strong>and</strong> communicate with at least 24 local intersection controllers.<br />

3. System Detectors. Ensure that each master controller is able to<br />

analyze traffic sensor data from at least 32 system detectors. Distribute system<br />

detectors up to eight per intersection, but do not exceed the total system sensor<br />

capacity.<br />

Ensure that the detectors are assignable to each <strong>of</strong> the computational<br />

channels in each group, with the channels representing cycle selection,<br />

directionality (<strong>of</strong>fset), non-arterial flow (split), <strong>and</strong> special congestion indicators <strong>of</strong><br />

queue or occupancy.<br />

Furnish a master controller that is capable <strong>of</strong> monitoring <strong>and</strong> detecting<br />

system detector failure <strong>and</strong> removing failed detectors from volume <strong>and</strong> occupancy<br />

calculations. Upon resumption <strong>of</strong> satisfactory sensor operation, sensors shall<br />

automatically resume input to volume <strong>and</strong> occupancy calculations.<br />

4. Timing Patterns. Ensure that each master controller provides a<br />

minimum <strong>of</strong> 16 selectable patterns. Ensure that each pattern shall consist <strong>of</strong> a<br />

combination <strong>of</strong> cycle, <strong>of</strong>fset, <strong>and</strong> split numbers for each intersection in the system.<br />

Furnish a master controller that is capable <strong>of</strong> implementing a “free”<br />

mode whereby all intersection controllers will operate without system coordination<br />

<strong>and</strong> a “flash” mode whereby all intersection controllers will operate in a flashing<br />

operation.<br />

5. Operational Modes. Ensure that each master controller is able to<br />

operate in the following modes <strong>of</strong> operational control:<br />

a. Traffic responsive mode whereby pattern selection is based on<br />

dynamic traffic conditions as measured by system sensors located in the control<br />

area. As a minimum, base the pattern selection on the quantitative traffic flow<br />

parameters <strong>of</strong> volume, occupancy, <strong>and</strong> directionality <strong>of</strong> the arterial traffic.<br />

Base transfer <strong>of</strong> patterns on programmable threshold values. Furnish<br />

system sensors that are capable <strong>of</strong> selective weighting.<br />

842