825<br />

733.03<br />

l. Terminal Blocks. Furnish cabinets that include terminal blocks<br />

mounted on panels on the walls <strong>of</strong> the cabinet. Ensure that the blocks are not<br />

obstructed by shelf-mounted devices. Furnish sufficient terminal sets for each<br />

individual harness wire as well as for contacts <strong>of</strong> signal load switches, flasher<br />

transfer relays, flasher, <strong>and</strong> other components. Also, provide separate terminal sets<br />

for field wiring connections, including power, signal, interconnection, <strong>and</strong> detector<br />

lead-in cables. Group terminal sets to separate higher voltage (120 VAC) from<br />

lower voltage, <strong>and</strong> arrange them into logical groups. Protect terminal blocks from<br />

accidental contact during the installation <strong>and</strong> removal <strong>of</strong> shelf-mounted equipment.<br />

Locate the blocks no closer than 4 inches (100 mm) from the bottom <strong>of</strong> pole <strong>and</strong><br />

pedestal mounted cabinets, <strong>and</strong> no closer than 6 inches (150 mm) from the bottom<br />

<strong>of</strong> foundation mounted cabinets.<br />

Ensure that the terminal points are UL listed as suitable to carry the<br />

rated loading. Ensure that the capacity <strong>and</strong> size <strong>of</strong> the terminals are as specified in<br />

NEMA TS-1, Section 10.2.5. Ensure that the terminal points for signal field<br />

wiring for each circuit accommodates at least four 12 AWG conductors with spade<br />

type terminals.<br />

Furnish terminal points for incoming power wiring that accepts either<br />

spade terminals or bare str<strong>and</strong>ed wire <strong>and</strong> are suitable for either aluminum or<br />

copper conductors.<br />

Space terminal sets for easy wiring. Furnish at least six reserve<br />

terminal sets for controllers. Harnesses may terminate on the back <strong>of</strong> terminal<br />

blocks using through-panel terminals. Clearly mark terminal sets for ready<br />

identification including through-panel terminals that are identified on both sides.<br />

Ensure that the contact between adjacent terminal points are made by bus bar, or<br />

by wire jumpers having spade type terminals securely attached to each end.<br />

m. Terminal Buses. Furnish a cabinet with supply terminal buses<br />

fed from the line side <strong>of</strong> the incoming 120 VAC power line, after the phase wire<br />

has passed through the main power switch. Ensure that the requirements for use <strong>of</strong><br />

radio interference filters are according to Item 8 <strong>of</strong> this Section, with the buses<br />

supplying load switches <strong>and</strong> with flashers being filtered when required. Ensure<br />

that a signal bus relay controls power to the bus supplying power for the signal<br />

load switches. . The following overrides NEMA requirements for signal bus<br />

relays. A solid-state relay shall be used for the signal bus relay. The signal bus<br />

relay shall maintain output equal to or above the rating <strong>of</strong> the cabinet main<br />

overcurrent protection device over the NEMA TS-2 Environmental Operating<br />

Range <strong>of</strong> -50 to +185 degrees F (-45 to +85 degrees C).<br />

Furnish a common terminal bus for the connection <strong>of</strong> the neutral<br />

wire <strong>of</strong> the incoming 120 VAC power line. Ensure that the common bus has<br />

sufficient terminal points to accommodate all potential cabinet wiring as well as<br />

field wiring. Use a separate common terminal, insulated from the panel, for the<br />

interconnect common.<br />

Furnish bus terminal points that comply with Item 12 <strong>of</strong> this<br />

Section for conductor accommodation, attachment <strong>and</strong> identification.