725.20 Ensure that placards designating the function of the apparatus contained in an enclosure or other such information are of white letters on a black placard. Ensure that placards warning of high voltage possibly present in an enclosure or other such warning are of white letters on a red placard. H. Customer Service Pole. Furnish a wood pole that complies with Supplement 1072. Ensure that the pole and any cross arms or pole key is Southern Pine or Western Red Cedar, full length, pressure treated in compliance with specifications of the American Wood Preservers Association using either creosote or pentachlorophenol. Ensure that the retention of preservative in Southern Pine is 7.5 pounds (120 kg) of creosote by assay or 0.38 pounds (6 kg) of pentachlorophenol by lime-ignition assay per cubic foot (cubic meter) of wood. Ensure that the retention of preservative in Western Red Cedar is 16 pounds (256 kg) of creosote by assay or 0.8 pounds (13 kg) of pentachlorophenol by lime-ignition assay per cubic foot (cubic meter) of wood. Ensure that the pole is 35 feet (10.5 m) minimum in length and Class 4 or heavier and conforming to ANSI 05.1 Specifications and Dimensions for wood poles. Ensure that the pole is reasonably straight without pronounced sweep or short crooks. Ensure that all pole hardware, including racks, braces, straps, guy anchors, guy wire, clamps, bolts, nuts, washers, screws, nails, etc. is hot dip galvanized in accordance with 711.02. Ensure that the grounding conductor is fastened to the pole with copper clad, rolled point staples of adequate size. Ensure that the grounding conductor molding is either wood or plastic, in sections not less than 8 feet (2.4 m) long, of sufficient width and groove depth to completely enclose the grounding conductor. Ensure that each pole anchor is of malleable iron or galvanized steel, 6 inch (150 mm) minimum diameter, two-way or four-way expanding type. Ensure that each anchor rod is 5/8 inch (16 mm) minimum diameter, 8 feet (2.4 m) minimum length galvanized steel with thimble eye. Ensure that each guy wire is 3/8 inch (10 mm) minimum diameter, conforming to ASTM A 475, galvanized steel. 725.20 Multiple Cell Polyvinyl Chloride Conduit and Fittings. Ensure that the multiple cell conduit consists of inner ducts conforming to NEMA TC-8 type DB in an outer conduit conforming to NEMA TC-2 (type EPC-40 or EPC-80 as specified except that size shall be the true inside diameter) in a factory preassembled unit. Ensure that fittings are factory made couplings that couple inner ducts and the outer conduit simultaneously, maintain the continuity and indexing of the inner ducts and are of a push fit design mechanically locked in place. Furnish materials according to the Department’s Qualified Products List (QPL). 725.21 Luminaire Supports. Ensure that the complete luminaire support from the luminaire(s) down through the connection to the foundation or other structure to which the luminaire support is attached conforms to the requirements of AASHTO’s "Standard Specifications for Structural Supports for Highway Signs, 784

785 725.21 Luminaires and Traffic Signals". Ensure that the combined stress ratio above the first field joint is greater than the combined stress ratio at the base of the pole. The design wind speed for all areas of the State shall be 90 mph (145 km/h). The Director may require various tests including destructive tests at either the factory or on site prior to acceptance of a support in which case the Department s representative will supervise the Contractor and/or manufacturer as the appropriate entity perform the tests on supports selected at random by the Department from the lot produced for the project. Ensure that any support damaged by the testing is replaced at no additional cost to the Department. Ensure that the support identification labels are adhesive labels with silver white reflective characters on a reflective green background meeting the requirements of 730.18. Furnish certified luminaire supports according to Supplement 1091 A. Light Poles. Ensure that the deflection of the pole from vertical when placed under the load of the bracket arm, and a weight of 75 pounds (35 kg) in place of each luminaire does not exceed an angle of 1 degree 10 minutes when tested in accordance with Supplement 1025 and that certified copies of the results obtained from the deflection tests are furnished the Laboratory. A pole and arm constructed from either aluminum or steel but not a combination of the two may be furnished. Ensure that each bracket arm is made from straight or tapered stock round or ovaliptic in cross section not less in size than 2 inch (50 mm) nominal pipe. Ensure that the luminaire end of each bracket arm has an outside diameter equal to 2 inch (50 mm) pipe, is straight for a distance of eight inches (203 mm), with the longitudinal axis canted not less than 1 degree nor more than 4 degrees above horizontal. Ensure that the bracket has an internal raceway with a minimum internal diameter of 1-3/32 inches (28 mm) free of projections and obstructions, which, when assembled to the shaft, will permit installation of luminaire supply conductors without insulation damage and which will not require bending the conductors to a radius less than 3 inches (75 mm). Ensure that the pole does not have more than two sections, that the shorter section of a sectional is at the top and that the shorter section of a sectional pole is not less than 10 feet (3 m) in length. Ensure that the pole sections are joined by telescoping the bottom of the upper section over the top of the lower section for a minimum length of 1 1/2 times the external diameter of the bottom of the upper section, driving the joint tight, and securing by through bolting with a stainless steel hex head bolt of a minimum diameter of 5/8 inch (16 mm). Ensure that a pole section does not have more than one longitudinal, automatically electrically welded seam and no transverse seams. Ensure that the longitudinal welded seam is neat and uniform in appearance, that the weld is not be less than the thickness of the base material and that the bead height does not exceed 1/16 inch (2 mm). Ensure that the wall thickness is uniform throughout,

785<br />

725.21<br />

Luminaires <strong>and</strong> Traffic Signals". Ensure that the combined stress ratio above the<br />

first field joint is greater than the combined stress ratio at the base <strong>of</strong> the pole.<br />

The design wind speed for all areas <strong>of</strong> the State shall be 90 mph (145 km/h).<br />

The Director may require various tests including destructive tests at either the<br />

factory or on site prior to acceptance <strong>of</strong> a support in which case the <strong>Department</strong> s<br />

representative will supervise the Contractor <strong>and</strong>/or manufacturer as the appropriate<br />

entity perform the tests on supports selected at r<strong>and</strong>om by the <strong>Department</strong> from the<br />

lot produced for the project. Ensure that any support damaged by the testing is<br />

replaced at no additional cost to the <strong>Department</strong>.<br />

Ensure that the support identification labels are adhesive labels with silver white<br />

reflective characters on a reflective green background meeting the requirements <strong>of</strong><br />

730.18.<br />

Furnish certified luminaire supports according to Supplement 1091<br />

A. Light Poles. Ensure that the deflection <strong>of</strong> the pole from vertical when placed<br />

under the load <strong>of</strong> the bracket arm, <strong>and</strong> a weight <strong>of</strong> 75 pounds (35 kg) in place <strong>of</strong><br />

each luminaire does not exceed an angle <strong>of</strong> 1 degree 10 minutes when tested in<br />

accordance with Supplement 1025 <strong>and</strong> that certified copies <strong>of</strong> the results obtained<br />

from the deflection tests are furnished the Laboratory.<br />

A pole <strong>and</strong> arm constructed from either aluminum or steel but not a<br />

combination <strong>of</strong> the two may be furnished.<br />

Ensure that each bracket arm is made from straight or tapered stock round or<br />

ovaliptic in cross section not less in size than 2 inch (50 mm) nominal pipe.<br />

Ensure that the luminaire end <strong>of</strong> each bracket arm has an outside diameter equal<br />

to 2 inch (50 mm) pipe, is straight for a distance <strong>of</strong> eight inches (203 mm), with<br />

the longitudinal axis canted not less than 1 degree nor more than 4 degrees above<br />

horizontal.<br />

Ensure that the bracket has an internal raceway with a minimum internal<br />

diameter <strong>of</strong> 1-3/32 inches (28 mm) free <strong>of</strong> projections <strong>and</strong> obstructions, which,<br />

when assembled to the shaft, will permit installation <strong>of</strong> luminaire supply<br />

conductors without insulation damage <strong>and</strong> which will not require bending the<br />

conductors to a radius less than 3 inches (75 mm).<br />

Ensure that the pole does not have more than two sections, that the shorter<br />

section <strong>of</strong> a sectional is at the top <strong>and</strong> that the shorter section <strong>of</strong> a sectional pole is<br />

not less than 10 feet (3 m) in length. Ensure that the pole sections are joined by<br />

telescoping the bottom <strong>of</strong> the upper section over the top <strong>of</strong> the lower section for a<br />

minimum length <strong>of</strong> 1 1/2 times the external diameter <strong>of</strong> the bottom <strong>of</strong> the upper<br />

section, driving the joint tight, <strong>and</strong> securing by through bolting with a stainless<br />

steel hex head bolt <strong>of</strong> a minimum diameter <strong>of</strong> 5/8 inch (16 mm).<br />

Ensure that a pole section does not have more than one longitudinal,<br />

automatically electrically welded seam <strong>and</strong> no transverse seams. Ensure that the<br />

longitudinal welded seam is neat <strong>and</strong> uniform in appearance, that the weld is not<br />

be less than the thickness <strong>of</strong> the base material <strong>and</strong> that the bead height does not<br />

exceed 1/16 inch (2 mm). Ensure that the wall thickness is uniform throughout,