725.15<br />

Ensure that the box <strong>and</strong> cover meet the structural requirements <strong>of</strong> Society <strong>of</strong> Cable<br />

Telecommunications Engineers Tier 5.<br />

Furnish materials according to the <strong>Department</strong>’s Qualified Products List (QPL).<br />

725.15 Circuit Cable Connections <strong>and</strong> Terminations. Ensure that each<br />

connector or terminator is <strong>of</strong> the same voltage rating as the wire being connected<br />

or terminated except that 600 volt connectors may be used with 5000 volt<br />

(secondary service) cable used in 600 volt service for the highway lighting circuits.<br />

Ensure that each connector or terminator is a compression style which fully<br />

encloses the conductor(s) <strong>and</strong> is <strong>of</strong> high strength copper alloy not a metal other<br />

than copper which has been plated. Ensure that each connector used for a butt<br />

splice is a sleeve type with a "stop" in the center.<br />

A. Termination <strong>of</strong> Oversize Wire. Ensure that each cable terminal <strong>of</strong> each<br />

device can properly accommodate the size <strong>of</strong> the wire being terminated. If a<br />

terminal <strong>of</strong> adequate size cannot be furnished, ensure that a short length <strong>of</strong> smaller<br />

wire is connected to the oversize conductor through the use <strong>of</strong> a proper butt style<br />

crimp connector or a terminal block, that no str<strong>and</strong>s have been cut back in the<br />

oversize conductor to make the connection <strong>and</strong> that the smaller wire is rated to<br />

carry the full ampacity <strong>of</strong> the circuit protection device.<br />

B. Fused Pull-Apart Connection. Ensure that each fused pull-apart cable<br />

connector kit is a molded synthetic rubber housing consisting <strong>of</strong> a female line side<br />

with two ports <strong>and</strong> a male load side with one port containing a socket type fuse<br />

holder wherein the fuse also acts as the pin for the load connection which is<br />

designed to break the circuit when the two halves <strong>of</strong> the connector body are<br />

separated. Ensure that the assembled kit is rated for direct burial <strong>and</strong> exposure to<br />

sunlight. Ensure that the metal parts <strong>of</strong> connector are <strong>of</strong> copper with a<br />

conductivity <strong>of</strong> 90 percent, have individual compression connections for each wire<br />

on the line side, have a crimp connection for the wire on the load side <strong>and</strong> have<br />

annular spring on the socket for each end <strong>of</strong> the fuse. Ensure that the fuse holder is<br />

for a st<strong>and</strong>ard midget [13/32" x 1-1/2" (10 mm x 38 mm)]fuse. Ensure that the<br />

fuse is rated 600 VAC, 100,000 AIC <strong>and</strong> does not have a glass body. Ensure that<br />

each cable port is sized for the wire or cable entering the entering the port <strong>and</strong> that<br />

there is a closure for the second line port if it is not to be used.<br />

C. Unfused Pull-Apart Connection. Ensure that each unfused pull-apart cable<br />

connector kit is a molded synthetic rubber housing consisting <strong>of</strong> a female line side<br />

with two ports <strong>and</strong> a male load side with one port containing a line side socket <strong>and</strong><br />

load side pin making a connection which is designed to break the circuit when the<br />

two halves <strong>of</strong> the connector body are separated. Ensure that the assembled kit is<br />

rated for direct burial <strong>and</strong> exposure to sunlight. Ensure that the metal parts <strong>of</strong><br />

connector are <strong>of</strong> copper with a conductivity <strong>of</strong> 90 percent, have an individual<br />

compression connection for each wire on the line side, have a crimp connection for<br />

the wire on the load side, <strong>and</strong> have an annular spring on the socket for the pin.<br />

Ensure that each cable port is sized for the wire or cable entering the port <strong>and</strong> that<br />

there is a closure for the second line port if it is not to be used.<br />

D. Unfused Bolted Connection. Ensure that each unfused re-enterable cable<br />

connector kit is a rigid molded plastic sleeve closed on each end by a molded