733<br />

707.13<br />

9.3 A bell <strong>and</strong> spigot joint per ASTM A760 (A760M) may be used with the<br />

following modifications:<br />

9.3.1 These joints may be used for conduits ranging in size from 18<br />

(450mm) to 48 (1200mm) inches in diameter.<br />

9.3.2 Ensure the bell <strong>and</strong> spigot has a soil tight joint by use <strong>of</strong> a shop<br />

applied gasket on the bell end <strong>and</strong> a field applied gasket on the spigot end.<br />

9.3.3 Provide a minimum <strong>of</strong> 0.064 (1.63mm) inch nominal sheet<br />

thickness or not more than two (2) nominal sheet thickness thinner than the<br />

thickness <strong>of</strong> the pipe to be joined.<br />

14.1 Ensure that the certification <strong>and</strong> sampling conforms to 707.01.<br />

707.13 Bituminous Lined Corrugated Steel Pipe [1/2-inch (13 mm)<br />

Corrugations]. Provide pipe according to 707.01 <strong>and</strong> AASHTO M 190, Type D.<br />

707.14 Bituminous Lined Corrugated Steel Pipe [1-inch (25 mm)<br />

Corrugations]. Provide pipe according to 707.02 <strong>and</strong> AASHTO M 190, Type D.<br />

707.15 Corrugated Steel Box Culverts. Provide corrugated steel box culverts<br />

according to ASTM A 964.<br />

Ensure that all manufacturers are pre-approved. Ensure that manufacturers not<br />

pre-approved submit a structural design criteria <strong>and</strong> analysis method to the<br />

<strong>Department</strong> before the project letting for approval. The <strong>Department</strong> maintains a<br />

list <strong>of</strong> all pre-approved manufacturers.<br />

Ensure that the manufacturer submits shop drawings <strong>and</strong> design calculations for<br />

review <strong>and</strong> written approval before manufacture. Submit a minimum <strong>of</strong> seven<br />

copies <strong>of</strong> the drawings. Allow a minimum <strong>of</strong> four weeks for approval. Ensure that<br />

the shop drawings include the following:<br />

A. All structural design <strong>and</strong> loading information.<br />

B. All material specifications.<br />

C. All plan view.<br />

D. All elevation view.<br />

E. All headwall <strong>and</strong> wingwall attachment requirements.<br />

F. All dimensions.<br />

G. All maintenance <strong>of</strong> traffic phases.<br />

H. All plate size <strong>and</strong> dimensions.<br />

The manufacturer may modify an approved shop drawing <strong>and</strong> resubmit for<br />

approval to the <strong>Department</strong>.<br />

707.17 Spiral Rib Steel Pipe Arch. Provide conduits according to AASHTO<br />

M36, Type IIA, with the following modifications:<br />

6.1 Fabricate pipe from aluminum coated sheet according to AASHTO M 274.<br />

7.2.2 The ribs shall conform to AASHTO M 196, Section 7.2.2.