HANDBOOK REQUIREMENTS - Central Maine Power Company
HANDBOOK REQUIREMENTS - Central Maine Power Company
HANDBOOK REQUIREMENTS - Central Maine Power Company
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
78<br />
78<br />
Primary service requiring higher amperage or voltage ratings is<br />
beyond the scope of this policy. Information for such service may<br />
be obtained by contacting the <strong>Company</strong>'s local Service<br />
Coordinator.<br />
All industrial and commercial primary 3 phase underground<br />
distribution will be installed in a conduit system. The conduit<br />
system will consist of standard size concrete<br />
manholes/handholes as needed to splice joints, junctions, or to<br />
meet cable pulling requirements. The ducts will be a minimum of<br />
schedule 40 PVC of a diameter adequate for the largest cable that<br />
may be necessary to serve the total anticipated load. The conduit<br />
system<br />
will include an adequate number of ducts for all necessary<br />
cables plus one spare duct (capped at both ends), and will provide<br />
a loop or alternate feed cable configuration. The conduit will be<br />
properly pitched to ensure water drainage into<br />
manholes/handholes.<br />
Conduit configuration will be limited to a<br />
single horizontal layer, if encased in sand. Multiple layer<br />
configurations must be encased in concrete. In urban areas or<br />
where site conditions make digging for repair of ducts<br />
impracticable or cost prohibitive, the conduit system will be<br />
encased in concrete regardless of conduit configuration.<br />
The <strong>Company</strong>'s Distribution Engineer must approve all<br />
conduit layouts prior to construction and will provide the design<br />
requirements (number and size of ducts, size and location of<br />
manholes and splice boxes) upon request.<br />
910. CONDUIT <strong>REQUIREMENTS</strong>/SPECIFICATIONS<br />
A. GENERAL<br />
The customer shall furnish, install, own and maintain the<br />
necessary ducts which must conform to the specifications of<br />
the