78<br />

78<br />

Primary service requiring higher amperage or voltage ratings is<br />

beyond the scope of this policy. Information for such service may<br />

be obtained by contacting the <strong>Company</strong>'s local Service<br />

Coordinator.<br />

All industrial and commercial primary 3 phase underground<br />

distribution will be installed in a conduit system. The conduit<br />

system will consist of standard size concrete<br />

manholes/handholes as needed to splice joints, junctions, or to<br />

meet cable pulling requirements. The ducts will be a minimum of<br />

schedule 40 PVC of a diameter adequate for the largest cable that<br />

may be necessary to serve the total anticipated load. The conduit<br />

system<br />

will include an adequate number of ducts for all necessary<br />

cables plus one spare duct (capped at both ends), and will provide<br />

a loop or alternate feed cable configuration. The conduit will be<br />

properly pitched to ensure water drainage into<br />

manholes/handholes.<br />

Conduit configuration will be limited to a<br />

single horizontal layer, if encased in sand. Multiple layer<br />

configurations must be encased in concrete. In urban areas or<br />

where site conditions make digging for repair of ducts<br />

impracticable or cost prohibitive, the conduit system will be<br />

encased in concrete regardless of conduit configuration.<br />

The <strong>Company</strong>'s Distribution Engineer must approve all<br />

conduit layouts prior to construction and will provide the design<br />

requirements (number and size of ducts, size and location of<br />

manholes and splice boxes) upon request.<br />

910. CONDUIT <strong>REQUIREMENTS</strong>/SPECIFICATIONS<br />

A. GENERAL<br />

The customer shall furnish, install, own and maintain the<br />

necessary ducts which must conform to the specifications of<br />

the