CMP STANDARD UG SERVICE OPTIONS<br />
Standard CMP Cable<br />
Service Meter Max. Min.<br />
Size<br />
Size<br />
Socket<br />
Length Conduit<br />
100A 100/125 #2 AL Triplex 150 FT. 2 IN.<br />
100A 200 #4/0 AL Triplex 220 FT. 2 1/2 IN.<br />
200A 200 #4/0 AL Triplex 220 FT. 2 1/2 IN.<br />
400A 320* (2) #4/0 AL Tri. 220 FT. 4 IN.<br />
* The 320 amp meter socket must be provided with twin line side<br />
lugs to accommodate<br />
connection of the parallel #4/0 triplex cable.<br />
If the cable is furnished and installed by the customer,<br />
particula r notice should be made of the maintenance provisions of<br />
Paragraph 916. The maximum length of customer owned<br />
residential underground secondary shall be in accordance with<br />
Illustration No. 31 in Section XII. For services or conductor sizes<br />
other than those listed in Illustration No. 31, contact the<br />
<strong>Company</strong> 's local Service Coordinator. Where service runs exceed<br />
the length s listed in Illustration No. 31 in Section XII, or become<br />
impractical,<br />
a primary<br />
underground feed to a padmount<br />
transformer will be required.<br />
There shall not be more than eight (8) conductors per spade<br />
for a three phase padmount. There shall not be more than<br />
six (6)<br />
conductors per spade for a single phase padmount. Cases<br />
involving more conductors than these limits<br />
must be referred to<br />
the company for special design and prior<br />
approval.<br />