65<br />

65<br />

• The compartment shall be isolated by barriers; and,<br />

metered and unmetered busses shall be separated by<br />

barriers.<br />

• Bus arrangements for low voltage (below 600) shall<br />

accommodate 12 inch long CT bars (multiple bars<br />

are<br />

¼” x 3” x 12”).<br />

• Units with voltage above 300 (phase-to-phase),<br />

shall<br />

have<br />

provisions for mounting VTs.<br />

• Any removable<br />

or hinged covers over unmetered busses<br />

or connections shall have sealing provisions or approved<br />

tamper-proof fasteners.<br />

Upo n installation of the switchgear, any existing removable<br />

CT links/supports must be removed. For all switchgear<br />

or<br />

transclosure installations, it shall be the responsibility of the<br />

customer<br />

to install instrument transformers and make primary<br />

connections.<br />

For an installation where the neutral conductor does not<br />

pass through<br />

the instrument transformer compartment, an<br />

insulated stranded copper neutral conductor,<br />

not smaller than #12<br />

AWG, shall be brought into and connected to an insulated<br />

terminal in the instrument transformer compartment.<br />

A 1 1/4 inch minimum metallic conduit, furnished and<br />

installed by the customer, shall be run continuous from the meter<br />

enclosure to the instrument transformer<br />

compartment. This<br />

conduit shall be either rigid metal conduit (RMC) or intermediate<br />

metal conduit (IMC) and be properly bonded<br />

to provide an<br />

effecti ve ground-fault<br />

current path (per Section VII of this<br />

handbook and<br />

NEC Article 250). Note: the metering<br />

cable/conduit<br />

shall not pass thru any other vertical<br />

sections/compartments<br />

of the switchgear.