elief valve , vent discharge, filling<br />
connection, or regulator<br />
vent:<br />
Gas Container/System Type Minimum Separation<br />
Propane tank (exchanged) 5 feet<br />
Propane tank (filled on-site) 10 feet<br />
Propane regulators 5 feet<br />
Natural gas (piped) vented<br />
equipment<br />
5 feet<br />
809. SELF-CONTAINED METERING<br />
A. GENERAL<br />
Self-contained meters shall generally be used for the<br />
following<br />
services:<br />
Single-Phase: Volts Max. Amps Wire<br />
120<br />
60 2 (3-wire meter)<br />
120/240 400 3<br />
240/480<br />
200 3<br />
120/208 200 3 (network meter)<br />
Polyphase:<br />
Volts<br />
Max. Amps Wire<br />
120 /208 400 4 (4-wire wye)<br />
277/480<br />
200 4 (4-wire wye)<br />
120/240 400 4 (4-wire delta)<br />
240 200 3<br />
Refer to Illustration No. 13 in Section XII for self-contained<br />
meter socket connections.<br />
Whenever connection of the grounding electrode conductor<br />
is made in the self-contained meter enclosure, it must<br />
be<br />