elief valve , vent discharge, filling<br />

connection, or regulator<br />

vent:<br />

Gas Container/System Type Minimum Separation<br />

Propane tank (exchanged) 5 feet<br />

Propane tank (filled on-site) 10 feet<br />

Propane regulators 5 feet<br />

Natural gas (piped) vented<br />

equipment<br />

5 feet<br />

809. SELF-CONTAINED METERING<br />

A. GENERAL<br />

Self-contained meters shall generally be used for the<br />

following<br />

services:<br />

Single-Phase: Volts Max. Amps Wire<br />

120<br />

60 2 (3-wire meter)<br />

120/240 400 3<br />

240/480<br />

200 3<br />

120/208 200 3 (network meter)<br />

Polyphase:<br />

Volts<br />

Max. Amps Wire<br />

120 /208 400 4 (4-wire wye)<br />

277/480<br />

200 4 (4-wire wye)<br />

120/240 400 4 (4-wire delta)<br />

240 200 3<br />

Refer to Illustration No. 13 in Section XII for self-contained<br />

meter socket connections.<br />

Whenever connection of the grounding electrode conductor<br />

is made in the self-contained meter enclosure, it must<br />

be<br />

57<br />