Notes:<br />
1. Aluminum electrodes are NOT permitted.<br />
2. Per NEC Section 250.56, where a single made electrode<br />
(5, 6 or 7 above) exceeds 25 ohms resistance to ground,<br />
an additional electrode consisting of any one of 2<br />
through 8 must be utilized. When this additional<br />
electrode is a made electrode (5 ,6 or 7), it shall be<br />
installed at least 6 feet away from, and bonded together<br />
with, the first electrode. Although the NEC requires a<br />
minimum separation of only 6 feet, the <strong>Company</strong> highly<br />
recommends a minimum separation of 16 feet (between<br />
8 foot ground rods) in order to maximize the paralleling<br />
effectiveness.<br />
For much of <strong>Central</strong> <strong>Maine</strong> <strong>Power</strong> <strong>Company</strong>’s service<br />
territory, meeting the “25 ohms or less” requirement is<br />
highly unlikely; therefore, installation of an additional<br />
electrode should be anticipated.<br />
It is the responsibility<br />
of the customer/electrician to verify the 25 ohms, or<br />
less, resistance and/or install the additional<br />
electrode.<br />
3. See NEC Sections 250.50 thru 250.70 for further details<br />
on grounding electrode systems.<br />
702. BONDING<br />
To prevent any potential differences from occurring<br />
between them, all of the grounding electrodes listed in paragraph<br />
701, as well as, CATV, communications or any other system<br />
grounding electrodes that are available on the premises, shall be<br />
bonded together. Intersystem bonding shall be installed in<br />
accordance with NEC 250.94 and shall have the capacity for at<br />
least 3 intersystem bonding conductors. It is the<br />
responsibility of<br />
the customer/electrician to ensure intersystem bonding<br />
provisions are provided. In the case where<br />
the grounding<br />