05.01.2013 Views

HANDBOOK REQUIREMENTS - Central Maine Power Company

HANDBOOK REQUIREMENTS - Central Maine Power Company

HANDBOOK REQUIREMENTS - Central Maine Power Company

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

44<br />

VII. GROUNDING<br />

AND BONDING<br />

700. GENERAL<br />

Service entrance grounding must be in compliance with the<br />

NEC a nd all applicable municipal and State requirements. NEC<br />

Sectio n 250.4 covers the “General Requirements for Grounding<br />

and Bonding.”<br />

A grounded electrical system shall have its neutral<br />

conne cted to earth in a manner that will limit voltage imposed by<br />

lightning<br />

or line surges; as well as, stabilize the voltage during<br />

normal<br />

operation. Electrical enclosures and other electrically<br />

conductive<br />

material likely to become energized shall be installed<br />

in a manner<br />

that creates an effective ground-fault current path;<br />

as defined<br />

in NEC 250.2, "an intentionally constructed,<br />

permanent,<br />

low-impedance electrically conductive path designed<br />

and intended to carry current, under ground-fault<br />

conditions, from<br />

the point of a ground fault on a wiring system to the electrical<br />

supply source . . ."<br />

In accordance with NEC Section 250.24, any grounded ac<br />

system operating at less than 1,000 volts, shall have the grounded<br />

condu ctor (neutral) run to each service disconnecting means and<br />

bonded<br />

to each disconnecting means enclosure or assembly.<br />

Additionally,<br />

the neutral (for a grounded system) and service<br />

equipment enclosures<br />

(for a grounded or ungrounded system)<br />

shall be<br />

bonded together and connected by a grounding electrode<br />

conductor<br />

to the grounding electrode system. Connection of the<br />

grounding<br />

electrode conductor to the service neutral may be made<br />

at any accessible<br />

point from the load end of the service drop or<br />

service lateral to, and including, the neutral terminal or bus at the<br />

service<br />

disconnecting means. This connection is normally<br />

made<br />

to the service entrance panel neutral bus or meter enclosure<br />

neutral/ground<br />

lug, whichever will result in the shortest grounding<br />

44

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!