steel electrical metallic tubing, standardized metal troughs<br />

or<br />

suitable rigid non-metallic conduit as permitted by the NEC.<br />

Metered and unmetered wires shall not be run in the same<br />

conduit, raceway or gutter. Exception: where the meter is pole<br />

mounted and the service is to pole mounted equipment, both sets<br />

of wires may be installed in a single vertical conduit run. Refer to<br />

Illustration No. 6, CATV <strong>Power</strong> Supply Installation, in Section<br />

XII. Coded conductors should always be used for positive<br />

identification.<br />

603. EMERGENCY OR STANDBY POWER<br />

Where a customer makes provisions for or installs an<br />

emergency or standby source of electric service, whether<br />

permanently mounted or portable, which is designed to<br />

energize the normal wiring system at the service entrance, the<br />

customer shall notify the <strong>Company</strong> in advance by calling 1-800-<br />

750-4000 (for Residential) or 1-800-565-3181 (for Commercial &<br />

Industrial). No electrical connection shall be made to the service<br />

entrance conductors or equipment until approved by the <strong>Company</strong>.<br />

All installations must comply with the applicable sections of<br />

the NEC. See NEC Article 700 "Emergency Systems" (legally<br />

required), 701 "Legally Required Standby Systems", or 702<br />

"Optional Standby Systems" (permanent or portable). Exception,<br />

the State of <strong>Maine</strong> amended the 2008 NEC 702.5(B), (2) as<br />

follows:<br />

For optional standby systems that supply single-family<br />

dwellings, the standby source shall not be required to be capable<br />

of supplying the full load that is transferred by the automatic<br />

transfer equipment.<br />

A positive acting, “listed” (by UL or other organization<br />

acceptable to the “authority having jurisdiction”)<br />

41<br />