38<br />

505. SERVICE MAST CONSTRUCTION<br />

Unless otherwise approved by the<br />

<strong>Company</strong>, masts shall be<br />

constructed of rigid steel conduit or steel intermediate metal<br />

conduit (IMC) with an inside diameter of no less than 2 inches.<br />

Refer to Illustration No. 3 in Section XII.<br />

Aluminum conduit, rigid non-metallic conduit or electrical<br />

metallic tubing (EMT) shall not be used for masts.<br />

Because the mast is grounded through the meter socket hub,<br />

it should not be bonded to the neutral (grounded conductor) at<br />

the top end.<br />

38