505. SERVICE MAST CONSTRUCTION<br />
Unless otherwise approved by the<br />
<strong>Company</strong>, masts shall be<br />
constructed of rigid steel conduit or steel intermediate metal<br />
conduit (IMC) with an inside diameter of no less than 2 inches.<br />
Refer to Illustration No. 3 in Section XII.<br />
Aluminum conduit, rigid non-metallic conduit or electrical<br />
metallic tubing (EMT) shall not be used for masts.<br />
Because the mast is grounded through the meter socket hub,<br />
it should not be bonded to the neutral (grounded conductor) at<br />
the top end.<br />