HANDBOOK REQUIREMENTS - Central Maine Power Company
HANDBOOK REQUIREMENTS - Central Maine Power Company
HANDBOOK REQUIREMENTS - Central Maine Power Company
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
36<br />
36<br />
conductors<br />
must extend at least 36 inches beyond the<br />
weatherhead. Current transformer installations require at least 48<br />
inch leads. The weatherhead should be installed above the level<br />
of the point of<br />
attachment of the service drop with suitable drip<br />
loops provided to prevent the entrance of moisture.<br />
For overhead service connection, the <strong>Company</strong> will provide<br />
and install connectors and covers for conventional copper or<br />
aluminum conductors up to and including 500 kCM or multiples<br />
thereof. For service entrance conductors larger than 500 kCM, the<br />
customer must provide connectors and insulating covers which are<br />
acceptable to the <strong>Company</strong>. Advance approval is recommended.<br />
501. CONDUCTOR IDENTIFICATION<br />
The neutral or grounded conductor shall be positively<br />
identified (generally by white color) in accordance with NEC<br />
Section 200.6.<br />
Note: In no case shall a phase conductor be identified with<br />
white or gray.<br />
The conductor with the higher phase voltage to ground on a<br />
four-wire delta service shall be positively identified (orange color)<br />
in accordance with NEC Section 230.56.<br />
502. LOCATION FOR PROPER CLEARANCES<br />
Meter enclosures, service entrance cable, conduit and drip<br />
loops, shall always be located so that the proper clearances will be<br />
provided for rain spouts, fire escapes, telephone wires, windows,<br />
blinds, and lightning rod conductors, as required by other sections<br />
of this handbook and the NEC.