HANDBOOK REQUIREMENTS - Central Maine Power Company
HANDBOOK REQUIREMENTS - Central Maine Power Company
HANDBOOK REQUIREMENTS - Central Maine Power Company
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
V. SERVICE ENTRANCE CONDUCTORS<br />
500.<br />
GENERAL<br />
For overhead service, the service entrance conductors<br />
comprise that part of the service which extends from the point of<br />
attachment of the overhead service drop on the building or<br />
structure to the service equipment, i.e., disconnecting means and<br />
overcurrent protection (breaker or switch-fuse). For underground<br />
service, the service entrance conductors<br />
run from the “point of<br />
connection” of the underground service lateral<br />
to the service<br />
equipment. The service lateral typically terminates<br />
in the meter<br />
enclosure on the outside of the building wall. Where there is no<br />
meter enclosure<br />
or terminal box, the “point of connection” is<br />
considered<br />
to be where the conductors penetrate the building wall.<br />
All service entrance conductors shall be service entrance<br />
cable or conductors installed in rigid or<br />
intermediate metal<br />
conduit,<br />
steel electrical tubing, or rigid non-metallic conduit<br />
recognized for use above ground as permitted by NEC Article<br />
352.<br />
See Par. 504 of this Handbook for conduit details. Conduit<br />
is suggested where the exterior construction of the building<br />
consists of rough stone, stucco or metal siding.<br />
On the line side of the meter, service entrance cable or<br />
conduit shall not be installed within the building wall or concealed<br />
in any way. On the load side of the meter, service entrance cable<br />
or conduit may be concealed but must be protected against<br />
physical<br />
damage per NEC Sections 230.50 and 300.4 and<br />
supported per 230.51(A). All services shall be installed<br />
in<br />
accordance with NEC Article 230.<br />
For overhead service entrance conductors 4/0 and smaller<br />
size, the conductors must extend at least 24 inches beyond the<br />
weatherhead to accommodate connection to the <strong>Company</strong>'s<br />
service drop. For larger than 4/0 size (or paralleled), the<br />
35<br />
35