20<br />

20<br />

service (whenever possible) for this application (see Para.<br />

D & E, above). See also Para. 302.<br />

G. 277/480 volts, three-phase, four-wire, wye--<br />

For power and general service installations typically having<br />

demands in excess of 50 KVA. Single-phase load shall<br />

be<br />

balanced between phases in accordance with Para. 305.<br />

H. 240/480 volts, single-phase, three- wire--<br />

For power and general service where the higher voltage is<br />

required to limit voltage drop in secondary feeds and three<br />

phase power is not readily available (available from<br />

<strong>Company</strong> padmount transformers where load does not<br />

exceed 50 KVA).<br />

I. 480 volts, three-phase, three-wire--<br />

Normally for power installations having demands of not<br />

less than 50 KVA (not available from<br />

<strong>Company</strong> padmount<br />

transformers).<br />

Note: to limit the available voltage-to-ground, the<br />

<strong>Company</strong> recommends four wire, wye service (whenever<br />

possible) for this application. See Para. G, above.<br />

J. Service voltages higher than 480 volts--<br />

Available only by negotiation with the <strong>Company</strong>. The size<br />

and type of customer's<br />

load must warrant such an<br />

installation.