20<br />
20<br />
service (whenever possible) for this application (see Para.<br />
D & E, above). See also Para. 302.<br />
G. 277/480 volts, three-phase, four-wire, wye--<br />
For power and general service installations typically having<br />
demands in excess of 50 KVA. Single-phase load shall<br />
be<br />
balanced between phases in accordance with Para. 305.<br />
H. 240/480 volts, single-phase, three- wire--<br />
For power and general service where the higher voltage is<br />
required to limit voltage drop in secondary feeds and three<br />
phase power is not readily available (available from<br />
<strong>Company</strong> padmount transformers where load does not<br />
exceed 50 KVA).<br />
I. 480 volts, three-phase, three-wire--<br />
Normally for power installations having demands of not<br />
less than 50 KVA (not available from<br />
<strong>Company</strong> padmount<br />
transformers).<br />
Note: to limit the available voltage-to-ground, the<br />
<strong>Company</strong> recommends four wire, wye service (whenever<br />
possible) for this application. See Para. G, above.<br />
J. Service voltages higher than 480 volts--<br />
Available only by negotiation with the <strong>Company</strong>. The size<br />
and type of customer's<br />
load must warrant such an<br />
installation.