C. 120/208 volts, single-phase (network), three-wire,<br />
(from four-wire system)--<br />
For general<br />
lighting and/or heating and cooking, and small<br />
power<br />
loads with motors generally not over 5 hp. Where<br />
the total load exceeds 40 KVA, the <strong>Company</strong> may,<br />
at its<br />
option,<br />
require the customer to arrange the wiring for three-<br />
phase, four-wire service.<br />
D. 120/208 volts, three-phase, four-wire, wye--<br />
For large lighting loads,<br />
or combination lighting,<br />
heating/cooking<br />
and power. Single-phase load shall be<br />
balanced between phases in accordance with<br />
Para. 305. See<br />
also<br />
Para. 302.<br />
E. 120/240 volts, three-phase, four-wire, delta--<br />
For<br />
combination 120/240 volts, three- wire, single-phase<br />
and 240 volts, three- phase service, where the load of<br />
either<br />
class substantially exceeds that of the other (not available<br />
from <strong>Company</strong> padmount transformers). See also Para.<br />
302.<br />
F.<br />
240 volts, three-phase, three-wire--<br />
For installations supplying a total of not less than 5 hp. in<br />
polyphase motors,<br />
and/or large commercial heating<br />
equipment (not available from <strong>Company</strong> padmount<br />
transformers). Wherever three-phase service is already<br />
available, the <strong>Company</strong> may, at its option and without<br />
obligation to continue such service indefinitely, accept<br />
additional installations requiring service for three-phase<br />
motors of less than 5 hp. total. Note: due to the increase<br />
in<br />
electronics used in motor drives which may require a stable<br />
grounded neutral, the <strong>Company</strong><br />
recommends four wire<br />
19<br />
19