05.01.2013 Views

HANDBOOK REQUIREMENTS - Central Maine Power Company

HANDBOOK REQUIREMENTS - Central Maine Power Company

HANDBOOK REQUIREMENTS - Central Maine Power Company

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

18<br />

III. STANDARD<br />

CHARACTERISTICS<br />

300. STANDARD<br />

SERVICE CHARACTERISTICS<br />

The<br />

following service characteristics<br />

are generally standard;<br />

however, all types of service are not available in all localities,<br />

those that are available shall be obtained from the <strong>Company</strong><br />

before any wiring is installed or equipment purchased. In<br />

cases of<br />

multiple occupancy installations, the combined load may be such<br />

that the<br />

characteristics of the service required will be different<br />

from that which the individual customer's<br />

loads might indicate. In<br />

such cases the <strong>Company</strong> reserves the right to determine the type of<br />

service wh ich will be supplied at 60 hertz. The maximum<br />

capacities as listed below may<br />

be exceeded, under certain<br />

conditions,<br />

with prior <strong>Company</strong> approval. Metering note: see<br />

para. 809<br />

and 810 of this handbook for metering options.<br />

A. 120 volts, single-phase, two-wire, (up to and including<br />

60 Amp)--<br />

For highway signs, trailers, traffic controllers,<br />

CATV<br />

amplifiers<br />

or other small power loads. The<br />

service from the<br />

<strong>Company</strong>'s facilities up to, and including, the meter shall be<br />

a 120/240 volt, single-phase, three-wire circuit. <strong>Company</strong><br />

approval must always be obtained in advance. Refer to<br />

Para. 409 for special requirements for travel trailers.<br />

B. 120/240 volts, single-phase, three-wire--<br />

For general lighting and/or heating and cooking, and small<br />

power loads with individual motors generally not over 5 hp.<br />

Where the total load exceeds 50 KVA, the <strong>Company</strong> may,<br />

at its option, require the customer to arrange the wiring for<br />

three-phase service.<br />

18