<strong>Sheet</strong> <strong>No</strong>. <strong>Component</strong> /<strong>Detail</strong> <strong>Description</strong><br />

1 Draw ing Guide MGE Galaxy 3500 10-20kVA, 3:3 1 MOD Narrow w ith XR Battery draw ing guide<br />

2-4 Solution MGE Galaxy 3500 Narrow Tow er 10-20kVA 1 MOD, 400V, w ith 1-XR cabinet<br />

5-6 UPS MGE Galaxy 3500 10-20kVA 400V, 3Ph In 3Ph Out, Narrow Tow er<br />

7 Battery XR Cabinet MGE Galaxy 3500 Extended Run Enclosure w ith MCCB, bat mods Exp to 6<br />

8-9 System One Line Diagram MGE Galaxy 3500 10-20kVA 400V 1MOD Narrow w ith XR Battery System One Line Diagram<br />

10 System Wiring Diagram MGE Galaxy 3500 10-20kVA 400V 1MOD Narrow w ith XR Battery System Control Wiring Diagram


Weight and Runtime details for 2 module UPS (10-20kVA) with 1 XR Battery<br />

Cabinet per UPS<br />

Battery position<br />

<strong>No</strong>. of bat shelves<br />

Net Solution Weight (kg)<br />

G35T10KH1B2S<br />

Runtime in Min<br />

Net Solution Weight (kg)<br />

G35T10KH2B2S<br />

UPS 1 428 6 n.a n.a n.a n.a n.a n.a.<br />

UPS 2 612 18 612 18 804 10 804 6<br />

XR1 3 1196 32 1196 32 1388 18 1388 12<br />

XR1 4 1388 47 1388 47 1580 27 1580 18<br />

XR1 5 1580 62 1580 62 1772 37 1772 25<br />

XR1 6 1772 78 1772 78 1964 47 1964 32<br />

XR1 7 1964 95 1964 95 2156 57 2156 40<br />

XR1 8 2156 112 2156 112 2348 68 2348 47<br />

XR2 9 2740 130 2740 130 2932 79 2932 55<br />

XR2 10 2932 148 2932 148 3124 90 3124 63<br />

XR2 11 3124 166 3124 166 3316 101 3316 71<br />

XR2 12 3316 185 3316 185 3508 113 3508 79<br />

XR2 13 3508 204 3508 204 3700 124 3700 87<br />

XR2 14 3700 223 3700 223 3892 136 3892 96<br />

XR3 15 4284 243 4284 243 4476 148 4476 105<br />

XR3 16 4476 262 4476 262 4668 161 4668 113<br />

XR3 17 4668 282 4668 282 4860 173 4860 122<br />

XR3 18 4860 303 4860 303 5052 185 5052 131<br />

XR3 19 5052 323 5052 323 5244 198 5244 140<br />

XR3 20 5244 344 5244 344 5436 211 5436 149<br />

XR4 21 5828 365 5828 365 6020 224 6020 158<br />

XR4 22 6020 386 6020 386 6212 237 6212 168<br />

XR4 23 6212 408 6212 408 6404 250 6404 177<br />

XR4 24 6404 429 6404 429 6596 263 6596 187<br />

XR4 25 6596 451 6596 451 6788 277 6788 196<br />

XR4 26 6788 473 6788 473 6980 290 6980 206<br />

Runtime in Min<br />

Net Solution Weight (kg)<br />

G35T15KH2B2S<br />

Runtime in Min<br />

Net Solution Weight (kg)<br />

G35T20KH2B2S<br />

Runtime in Min


<strong>No</strong>. of Battery<br />

SKU Number<br />

Modules<br />

Dimensions Weight<br />

H x W x D (mm) in kg<br />

Floor Loading<br />

Data in kg/sq.m<br />

G35TXR2B6 2 1490 x 523 x 834 388 890<br />

3 1490 x 523 x 834 484 1110<br />

4 1490 x 523 x 834 580 1330<br />

5 1490 x 523 x 834 676 1550<br />

G35TXR6B6 6 1490 x 523 x 834 772 1770<br />

Rating SKU Number<br />

COG <strong>Detail</strong>s in mm<br />

X-Distance Y-Distance Z-Distance<br />

10kVA<br />

G35T10KH1B2S<br />

G35T10KH2B2S<br />

176<br />

176<br />

655<br />

650<br />

400<br />

398<br />

15kVA G35T15KH2B2S 176 650 398<br />

20kVA G35T20KH2B2S 176 650 398<br />

SKU Number<br />

<strong>No</strong>. of Battery<br />

Modules<br />

COG <strong>Detail</strong>s in mm<br />

X-Distance Y-Distance Z-Distance<br />

G35TBXR2B6 2 261 500 403<br />

3 261 496 401<br />

4 261 520 399<br />

5 261 560 398<br />

G35TBXR6B6 6 261 610 397


Galaxy 3500® 10K and 40K UPS Frame (1 Module) Site Planning Data<br />

Battery - <strong>No</strong>minal Voltage : +/-192V DC<br />

Input and output Voltage : 400V AC<br />

UPS<br />

Rating<br />

SKU Number<br />

EFFICIENCY DETAILS<br />

System Mains Input<br />

<strong>No</strong>minal<br />

Current(A)<br />

Maximum<br />

Current(A)<br />

SYSTEM 25% LOAD 50% LOAD 75% LOAD 100% LOAD<br />

10KVA 400V 92.9 94.8 94.9 94.9<br />

15KVA 400V 92.9 95.3 95.5 95.5<br />

20KVA 400V 94.4 95.5 95.5 95.4<br />

30KVA 400V 94.1 96 95.9 96.1<br />

40KVA 400V 95 96 95.9 95.5<br />

System<br />

Bypass<br />

Input<br />

<strong>No</strong>minal<br />

Current(A)<br />

System Output<br />

System<br />

output<br />

Power<br />

<strong>No</strong>minal<br />

Current(A)<br />

Batte ry<br />

Current(A)<br />

(in UPS<br />

Cabinet)<br />

Recommended Over current<br />

Protection Device Ratings<br />

UPS<br />

Mains<br />

Input (A)<br />

UPS<br />

Bypass<br />

Input (A)<br />

UPS<br />

System<br />

Output<br />

(A)<br />

Typical<br />

Dimensions<br />

H x W x D (mm)<br />

see note 14<br />

UPS Mechanical Data<br />

weight<br />

(Kg) see<br />

<strong>No</strong>te 14<br />

G35T10KH1B2S 1491x352x838 214 725<br />

G35T10KH2B2S 1491x352x838 306 1037<br />

10kVA/ G35T10KH1B4S 10kVA/<br />

1491x523x838 351 801<br />

12.3 13.5 14.4<br />

14.4 27.5 16 16 16<br />

440<br />

8kW G35T10KH2B4S 8kW<br />

1491x523x838 443 1011<br />

G35T10KH3B4S 1491x523x838 535 1221<br />

G35T10KH4B4S 1491x523x838 627 1431<br />

G35T15KH2B2S 1491x352x838 402 1363<br />

15kVA/ G35T15KH2B4S 15kVA/<br />

1491x523x838 443 1011<br />

18.5 20.3 21.7<br />

21.7 41.2 25 25 25<br />

516<br />

12kW G35T15KH3B4S 12kW<br />

1491x523x838 535 1221<br />

G35T15KH4B4S 1491x523x838 627 1431<br />

G35T20KH2B2S 1491x352x838 402 1363<br />

20kVA/ G35T20KH2B4S 20kVA/<br />

1491x523x838 443 1011<br />

24.7 27.2 28.9<br />

28.9 55 32 32 32<br />

751<br />

16kW<br />

G35T20KH3B4S 16kW<br />

1491x523x838 535 1221<br />

G35T20KH4B4S 1491x523x838 627 1431<br />

30kVA/ G35T30KH3B4S 30kVA/<br />

1491x523x838 570 1301<br />

36.7 40.3 43.3 43.3 82.5 50 50 50<br />

839<br />

24kW G35T30KH4B4S 24kW<br />

1491x523x838 662 1510<br />

40kVA/<br />

40kVA/<br />

G35T40KH4B4S 49.1 54 57.7<br />

57.7 110.1 63 63 63 1491x523x838 662 1510 1279<br />

32kW<br />

32kW<br />

<strong>No</strong>tes.<br />

1. <strong>No</strong>minal Input current based on nominal mains voltage + batteries fully charged at 100% ohmic load.<br />

2. Maximum Input current based on fully battery recharge + nominal mains voltage at 100% ohmic load.<br />

3. Suggested input overcurrent protection based on continuous full load.<br />

4. <strong>No</strong>minal battery voltage assumed to be 2.0 volts/ cell (lead technology)<br />

5. Over current protection device rating selection based on <strong>No</strong>minal input current is acceptable provided battery recharge time is short.<br />

Consult Schneider Electric for application specific assistance.<br />

6. Voltage tolerance is 304 - 477V, 47 - 53Hz for nominal 50Hz.<br />

7. Input power-factor is 0.98 for > 50% loading.<br />

8. Cable installation to comply with EN60364-5-52, max ambient 30 deg C, cable sizes shown<br />

refer to 600V rated,90 degree C multicore copper conductors with thermosetting insulation unless otherwise mentioned<br />

9. AC input & output to be L1, L2, L3, N & PE depending on 400/230V configuration, PE may be separate or SWA of armored cable<br />

10. Overcurrent protective devices (OCPD) may be either gL fuse type or MCB/MCCB rated at 30kA fault rating<br />

11. DC cabling should be sized to give < 1% voltage drop at the nominal battery discharge current<br />

using three-wire separate conductors in positive, centre-tap and negative poles<br />

12. Top or bottom cable entry with removable gland plates<br />

13. Control wiring to be run separately using screened conductors away from power cabling preferably in a separate conduit or cable tray<br />

14. Weights and dimensions are with internal batteries, with extended battery cabinets use battery discharge current<br />

in conjunction with cable drop to size cabling from cabinet to UPS<br />

15. Heat loss refers to max loading and fully charged batteries<br />

16. Refers to maximum battery recharge conditions<br />

17. Input: THD < 5% at Full Load<br />

18. Output:THD