2. Specifications<br />

2.1 General specifications<br />

NOTE<br />

AC Power type<br />

DC Power type<br />

38 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

Item <strong>T1</strong>-<strong>16S</strong><br />

Power supply voltage 100 to 240Vac (+10/-15%), 50/60 Hz<br />

Power consumption 45VA or less<br />

Inrush current 50A or less (at 240Vac, cold start)<br />

Output 24Vdc<br />

0.2A (for external devices and/or for input signals)<br />

rating (24Vdc, ±10%)<br />

(Note) 5Vdc 1.5A (for I/O module)<br />

Power supply voltage 24Vdc (+20/-15%)<br />

Power consumption 18W or less<br />

Inrush current 25A or less (at 24Vdc)<br />

5Vdc output rating (Note) 1.5A (for I/O module)<br />

Retentive power interruption 10ms or less<br />

Insulation resistance 10MΩ or more<br />

(between power terminals and ground terminal)<br />

Withstand voltage 1500Vac - 1 minute<br />

Ambient temperature 0 to 55°C (operation), -20 to 75°C (storage)<br />

Ambient humidity 5 to 95%RH, no condensation<br />

Noise immunity 1000Vp-p/1µs, Conform to EMC Directive 89/336/EEC<br />

Vibration immunity 9.8m/s 2 (1g)<br />

(for 30 minutes per axis, on 3 mutually perpendicular axes)<br />

Shock immunity 98m/s 2 (10g)<br />

(3 shocks per axis, on 3 mutually perpendicular axes)<br />

Approximate weight 500g<br />

6F3B0253<br />

(1) 24Vdc service power output is not provided on the DC power supply type.<br />

(2) The maximum output current of the 5Vdc is 1.5A. However there is the following<br />

restrictions, depending on the conditions.<br />

• When HP911 is used:<br />

→ Redused by 0.2A<br />

• When RS-485 port is used:<br />

→ Reduced by 0.1A<br />

• When 24Vdc service power is used:<br />

→ Refer to the right chart.<br />

5Vdc<br />

maximum load current<br />

(A)<br />

1.5<br />

1.0<br />

0.1 0.2 (A)<br />

24Vdc service power<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net