Commissioning<br />

Parameter<br />

Description<br />

Default<br />

Default<br />

(IDU: M)<br />

(IDU: L)<br />

Range - Value<br />

5. 2. 3 Offset 0°C 0°C [-7 [LT] or -14 [HT] - 7 [LT] or 14 [HT]]°C<br />

5. 2. 4 Room Influence Proportional 2 [LT] or 10 [HT] 2 [LT] or 10 [HT] [0 - 20] (visible by setting par 4.2.7 = 0)<br />

5. 2. 5 Max T<br />

60°C [HT] or 45°C 60°C [HT] or 45°C<br />

[LT ]<br />

[LT ]<br />

[20 - 70 [HT] or 45 [LT]]°C<br />

5. 2. 6 Min T<br />

20°C[HT] or 20°C[HT] or<br />

20°C[LT]<br />

20°C[LT]<br />

[20 - 60 [HT] or 45 [LT]]°C<br />

5. 2. 7 Thermoregulation logic 0 0 0 = Classic ¦ 1 = Smart<br />

5. 2. 8 Quick night setback 0 0 0 = OFF ¦ 1 = ON<br />

5. 2. 9 Heat request mode 0 0<br />

0 = Standard ¦ 1 = RT Time Programs Exclusion ¦ 2 = Forcing<br />

Heat Demand<br />

5. 3 Diagnostics<br />

5. 3. 0 Room T °C<br />

5. 3. 1 Room T setpoint °C<br />

5. 3. 2 Flow temperature °C (Visible only with Zone Module)<br />

5. 3. 3 Return temperature °C (Visible only with Zone Module)<br />

5. 3. 4 Heat Request Z2 0 = OFF ¦ 1 = ON<br />

5. 3. 5 Pump status<br />

(Visible only with Zone Module)<br />

0 = OFF ¦ 1 = ON<br />

5. 3. 7 Relative humidity %<br />

5. 3. 8 Zone flow temperature setpoint °C<br />

5. 4 Zone module settings (Visible only with Zone Module)<br />

5. 4. 0 Zone pump modulation<br />

0 = Fixed ¦ 1 = Modulating on DeltaT ¦ 2 = Modulating on<br />

pressure<br />

5. 4. 1 Target deltaT for pump modulation<br />

20°C [HT] or 7°C 20°C [HT] or 7°C<br />

[LT ]<br />

[LT ]<br />

[4 - 25]°C<br />

5. 4. 2 Pump fixed speed 1 1 [0.2 - 1]%<br />

5. 5 Cooling (always visible by setting par 1.8.0 = 1)<br />

5. 5. 0 T Set Cool<br />

7°C[FC] or 7°C[FC] or<br />

18°C[UFH] 18°C[UFH]<br />

[par 5.5.7 - par 5.5.6]°C<br />

5. 5. 1 Cooling Temp Range 1 1<br />

(0 = [FC]; 1 = [UFH])<br />

0 = Fan Coil ¦ 1 = Underfloor<br />

5. 5. 2 Thermoregulation 0 0 0 = ON/OFF Thermostat ¦ 1 = Fix Flow T ¦ 2 = Outdoor T Only<br />

5. 5. 3 Slope<br />

25 [FC] or 20 25 [FC] or 20<br />

[UFH]<br />

[UFH]<br />

[18 [FC] or 0 [UFH] - 33 [FC] or 60 [UFH]]<br />

5. 5. 4 Offset 0°C 0°C [-2,5 - 2,5]°C<br />

5. 5. 6 Max T<br />

12°C [FC] 23°C 12°C [FC] 23°C<br />

[UFH]<br />

[UFH]<br />

[7 [FC] or 18 [UFH] - 15 [FC] or 23°[UFH]]°C<br />

5. 5. 7 Min T<br />

7°C [FC] 18°C 7°C [FC] 18°C<br />

[UFH]<br />

[UFH]<br />

[7 [FC] or 15 [UFH] - 12 [FC] or 23 [UFH]]°C<br />

5. 5. 8 Target deltaT for pump modulation 5°C 5°C [4 - 20]°C (Visible only with Zone Module)<br />

5. 7 Zone regulation parameters (visible by setting par 4.2.7 or 5.2.7 = 1)<br />

5. 7. 0 Heating Type 0 0<br />

(visible by setting par 4.2.7 = 1)<br />

0 = Floor Heating ¦ 1 = Radiators ¦ 2 = Floor Heating (main) +<br />

Radiators ¦ 3 = Radiators (main) + Floor Heating ¦ 4 = Convection<br />

¦ 5 = Air Heating<br />

5. 7. 1 Room Influence 0 0<br />

(visible by setting par 4.2.7 = 1)<br />

0 = OFF ¦ 1 = Less ¦ 2 = Medium ¦ 3 = More<br />

5. 7. 2 Building Isolation Level 0 0<br />

(visible by setting par 4.2.7 = 1)<br />

0 = Poor ¦ 1 = Average ¦ 2 = Good<br />

5. 7. 3 Building Size 0 0<br />

(visible by setting par 4.2.7 = 1)<br />

0 = Small ¦ 1 = Average ¦ 2 = Large<br />

5. 7. 4 Climatic Zone 0°C 0°C [-20 - 30]°C (visible by setting par 4.2.7 = 1)<br />

5. 7. 5 Auto Slope Adaptation 0 0<br />

(visible by setting par 4.2.7 or 5.2.7 = 1)<br />

0 = OFF ¦ 1 = ON<br />

5. 8 Advanced settings<br />

5. 8. 3 Heating controller 2 2 0 = None ¦ 1 = Room thermostat ¦ 2 = Room Sensor<br />

5. 8. 4 Cooling controller 1 1<br />

(always visible by setting par 1.8.0 = 1)<br />

0 = None ¦ 1 = Room thermostat ¦ 2 = Room Sensor<br />

5. 8. 7 Humidity Control Threshold 70% 70% [40 - 100]% (visible by setting par 1.8.0 = 1)<br />

5. 8. 8 Humidity Control Hysteresis 10% 10% [0 - 30]% (visible by setting par 1.8.0 = 1)<br />

5. 8. 9 Humidity Alarm 0 0<br />

(visible by setting par 1.8.0 = 1)<br />

0 = None ¦ 1 = Stop<br />

7 Zone Module (Visible only with Zone Module)<br />

7. 1 <strong>Manual</strong> mode (Visible only with Zone Module)<br />

7. 1. 0 <strong>Manual</strong> mode activation 0 0 0 = OFF ¦ 1 = ON<br />

7. 1. 1 Z1 Pump control 0 0 0 = OFF ¦ 1 = ON<br />

7. 1. 2 Z2 Pump control 0 0 0 = OFF ¦ 1 = ON<br />

7. 1. 3 Z3 Pump control 0 0 0 = OFF ¦ 1 = ON<br />

7. 1. 4 Z2 Mix Valve Control 0 0 0 = OFF ¦ 1 = Open ¦ 2 = Close<br />

7. 1. 5 Z3 Mix Valve Control 0 0 0 = OFF ¦ 1 = Open ¦ 2 = Close<br />

7. 1. 6 Z1 Mix Valve Control 0 0 0 = OFF ¦ 1 = Open ¦ 2 = Close<br />

7. 2 General Zone Module<br />

7. 2. 0 Hydraulic scheme 0 0<br />

0 = Not defined ¦ 1 = MCD ¦ 2 = MGM II ¦ 3 = MGM III ¦ 4 = MGZ<br />

I ¦ 5 = MGZ II ¦ 6 = MGZ III<br />

7. 2. 1 FlowT Offset 1°C 1°C [0 - 40]°C<br />

7. 2. 2 Auxiliary output setting 0 0 0 = Heat request ¦ 1 = External pump ¦ 2 = Alarm<br />

7. 2. 3 External temperature correction 0°C 0°C [-3 - 3]°C<br />

EN / 67