Nimbus Compact M NET R32 Installation Manual UK
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Commissioning<br />
Parameter<br />
Description<br />
Default<br />
(IDU: M)<br />
Default<br />
(IDU: L)<br />
Range - Value<br />
1. 17. 1 Room Thermostat 2 0 = OFF ¦ 1 = ON<br />
1. 17. 2 AUX input 1 0 = Open ¦ 1 = Close<br />
1. 17. 3 AUX input 2 0 = Open ¦ 1 = Close<br />
1. 17. 4 HV input 1 0 = OFF ¦ 1 = ON<br />
1. 17. 5 HV input 2 0 = OFF ¦ 1 = ON<br />
1. 18 EM diagnostics - 1 output<br />
1. 18. 0 Main circulator status 0 = OFF ¦ 1 = ON<br />
1. 18. 1 Tank electric heater 0 = OFF ¦ 1 = ON ¦ 2 = Integration ¦ 3 = Lockout<br />
1. 18. 2 HC Pump 2 0 = OFF ¦ 1 = ON<br />
1. 18. 3 Diverter Valve (CH/DHW) 0 = DHW ¦ 1 = CH<br />
1. 18. 4 Diverter Valve 2 (CH/Cooling) 0 = CH ¦ 1 = COOLING<br />
1. 18. 5 CH backup resistance 1 0 = OFF ¦ 1 = ON<br />
1. 18. 6 CH backup resistance 2 0 = OFF ¦ 1 = ON<br />
1. 18. 7 CH backup resistance 3 0 = OFF ¦ 1 = ON<br />
1. 18. 8 AUX output 1 0 = Open ¦ 1 = Close<br />
1. 18. 9 AUX output 2 0 = Open ¦ 1 = Close<br />
1. 19 Service<br />
1. 19. 0 SW Version main<br />
1. 20 System integration<br />
1. 20. 0 PV offset DHW setpoint temperature 0°C 0°C [0 - 20]°C<br />
1. 20. 2 Tank solar integration 0 0 0 = Absent ¦ 1 = Present<br />
1. 20. 3 OpenTherm gateway activation 0 0 0 = OFF ¦ 1 = ON<br />
1. 21 Error History<br />
1. 21. 0 Last 10 errors<br />
1. 21. 1 Reset error list<br />
0 = Do you really want to perform the reset ? If you press OK<br />
button, the reset command will be executed otherwise, by way<br />
of ESC, the previous page is shown.<br />
1. 22 Reset Menu<br />
1. 22. 0 Reset factory settings<br />
0 = Do you really want to perform the reset ? If you press OK<br />
button, the reset command will be executed otherwise, by way<br />
of ESC, the previous page is shown.<br />
1. 23 Domestic hot water - 2<br />
1. 23. 0 Thermal Cleanse target temp 60°C 60°C [60 - 60]°C<br />
1. 23. 1<br />
Antilegionella target temperature<br />
duration<br />
1h 1h [1 - 2]h<br />
1. 23. 2 Max Duration Antilegionella 6h 6h [4 - 12]h<br />
1. 24 Energy meter<br />
1. 24. 0 Energy pulse unit 0 0 0 = None ¦ 1 = kWh<br />
1. 24. 1 Energy pulse value number 1 1 [1 - 10]<br />
1. 24. 2 Energy pulse value factor 6 6<br />
1. 24. 3 Energy pulse measuring type 1 1 0 = Only HP ¦ 1 = HP + Electric Heater<br />
1. 24. 4<br />
Backup electric heaters nominal<br />
power<br />
2kW 2kW [1 - 3]kW<br />
1. 24. 5 Tank electric heaters nominal power 2kW 2kW [1 - 3]kW<br />
1. 24. 6 Backup electric heaters efficiency 95% 95% [0 - 100]%<br />
1. 24. 7 Tank electric heaters efficiency 95% 95% [0 - 100]%<br />
4 Zone 1 parameters<br />
0 = /1000 ¦ 1 = /100 ¦ 2 = /10 ¦ 3 = 1 ¦ 4 = x10 ¦ 5 = x100 ¦ 6 =<br />
x1000<br />
4. 0 Setpoint<br />
4. 0. 0 T Day<br />
19°C Heat - 24°C 19°C Heat - 24°C<br />
Cool<br />
Cool<br />
[10 - 30]°C<br />
4. 0. 1 T Night<br />
13°C Heat - 30°C 13°C Heat - 30°C<br />
Cool<br />
Cool<br />
[10 - 30]°C<br />
4. 0. 2 T set Z1<br />
40°C [HT] - 20°C 40°C [HT] - 20°C<br />
[LT ]<br />
[LT ]<br />
[20 - 60]°C<br />
4. 0. 3 Zone frost temperature 5°C 5°C [2 - 15]°C<br />
4. 1 Automatic winter mode<br />
4. 1. 0 Automatic winter mode activation 0 0 0 = OFF ¦ 1 = ON<br />
4. 1. 1 Automatic winter mode threshold 20°C 20°C [0 - 30]°C<br />
4. 1. 2 Automatic winter mode delay time 300min 300min [0 - 600]min<br />
4. 2 Settings<br />
4. 2. 0 Zone temperature range 1 1<br />
(0 = [LT]; 1 = [HT])<br />
0 = Low Temp ¦ 1 = High Temp<br />
4. 2. 1 Thermoregulation 1 1<br />
0 = Fix Flow T ¦ 1 = Basic Thermoreg ¦ 2 = Room T Only ¦ 3 =<br />
Outdoor T Only ¦ 4 = Room+Outdoor T<br />
4. 2. 2 Slope<br />
0.6 [LT] or 1.5 0.6 [LT] or 1.5 [0,2 [LT] or 0,4 [HT] - 1 [LT]or 3,5 [HT]] (visible by setting par<br />
[HT]<br />
[HT] 4.2.7 = 0)<br />
4. 2. 3 Offset 0°C 0°C [-7 [LT] or -14 [HT] - 7 [LT] or 14[HT]]°C<br />
4. 2. 4 Room Influence Proportional 10 [HT] or 2 [LT] 10 [HT] or 2 [LT] [0 - 20] (visible by setting par 4.2.7 = 0)<br />
4. 2. 5 Max T<br />
60°C [HT] or 45°C 60°C [HT] or 45°C<br />
[20 - 70 [HT] or 45 [LT]]°C<br />
4. 2. 6 Min T<br />
[LT ]<br />
20°C[HT] or<br />
20°C[LT]<br />
[LT ]<br />
20°C[HT] or<br />
20°C[LT]<br />
[20 - 60 [HT] or 45[LT]]°C<br />
EN / 65