Commissioning<br />

1.23 DOMESTIC HOT WATER - 2<br />

1.23.0 Thermal Cleanse target temp<br />

Defines the setpoint of thermal cleanse cycle.<br />

1.23.1 Antilegionella target temperature duration<br />

Defines the time in which the Thermal cleanse Target temp has<br />

to be mantained.<br />

1.23.2 Max Duration Antilegionella<br />

Defines the Max time in which the system can perform and<br />

complete the Thermal cleanse cycle.<br />

1.24.4 Backup electric heaters nominal power<br />

Backup Heating Element Nominal Power Consumption.<br />

1.24.5 Tank electric heaters nominal power<br />

Tank electric heaters nominal power consumption.<br />

1.24.6 Backup electric heaters efficiency<br />

Backup Heating Element Nominal efficiency.<br />

1.24.7 Tank electric heaters efficiency<br />

Tank electric heaters nominal efficiency.<br />

1.24 ENERGY METER<br />

1.24.0 Energy pulse unit<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

Define if the S0 input is used or not:<br />

0 None: S0 signal input is not used.<br />

1 kWh: S0 signal input is used.<br />

Press the selector to confirm.<br />

1.24.1 Energy pulse value number<br />

1.24.2 Energy pulse value factor<br />

The multiplication of Energy pulse value factor and the Energy<br />

pulse value number gives the number of pulses representing<br />

an energy consumption of 1 kWh. These parameters must be<br />

set according to the connected pulse meter. Specifications.<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

0 /1000<br />

1 /100<br />

2 /10<br />

3 1<br />

4 x10<br />

5 x100<br />

6 x1000<br />

Press the selector to confirm.<br />

1.24.3 Energy pulse measuring type<br />

Defines if the S0 input signals measures the HP consumption<br />

(0) or the sum HP and resistors consumption (1).<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

0 Only HP.<br />

1 HP + Electric Heater.<br />

Press the selector to confirm.<br />

EN / 57