Commissioning<br />

1.1.1 HV input 2 (input configurable to 230 V)<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

1 Absent: input not active.<br />

2 DLSG: Input not active (0 V), the heating elements are disabled<br />

in every operating cycle.<br />

3 SG2: input 2 for the Smart Grid Ready protocol (refer to the<br />

paragraph “Standard SG ready”).<br />

4 External switch off signal: switches the machine OFF. Every<br />

heating, cooling and DHW request is interrupted while the<br />

anti-freeze protection logics are active.<br />

5 Photovoltaic integration: input not active (0 V), no integration.<br />

Input active (230 V), the energy surplus is used to increase<br />

the DHW set-point by the quantity defined through parameter<br />

1.20.0 PV offset DHW setpoint temperature. If the<br />

DHW cylinder has reached the new set-point, it is possible<br />

to use this energy to increase the set-point of the inertial<br />

storage tank (if present) through parameter 20.4.4 Buffer<br />

electric integration offset or of the heating / cooling function<br />

to the comfort set-point.<br />

Press the selector to confirm.<br />

1.1.3 AUX input 1<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

0 None.<br />

1 Humidistat sensor: when the contact is closed, the heat<br />

pump is turned off during the cooling cycle. Use Par. 1.1.9<br />

Humidity input zone to set the zone pumps that will stop<br />

as a result.<br />

2 Heat / Cool by external control: when the contact is closed,<br />

the operating mode is set to cooling; when the contact is<br />

opened, the operating mode is set to heating.<br />

3 Room thermostat HC3: the signal is interpreted as a contact<br />

for a thermostat in zone 3. When the contact is closed,<br />

it is sent as a heat request for zone 3.<br />

4 Safety thermostat: connect an underfloor safety thermostat<br />

to the contact. When the contact is closed, water circulation<br />

is interrupted.<br />

5 Photovoltaic integration: input not active (contact open),<br />

no integration.<br />

Input active (contact closed), the energy surplus is used<br />

to increase the DHW set-point by the quantity defined<br />

through parameter 1.20.0 PV offset DHW setpoint temperature<br />

- Delta T Setpoint DHW photovoltaic. If the DHW<br />

cylinder has reached the new set-point, it is possible to use<br />

this energy to increase the set-point of the inertial storage<br />

tank (if present) through parameter 20.4.4 Buffer electric<br />

integration offset or of the heating / cooling function to<br />

the comfort set-point.<br />

Press the selector to confirm.<br />

1.1.4 AUX input 2<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

0 None.<br />

1 Humidistat sensor: when the contact is closed, the heat<br />

pump is turned off during the cooling cycle. Use Par. 1.1.9<br />

Humidity input zone to set the zone pumps that will stop<br />

as a result.<br />

2 Heat / Cool by external control: when the contact is closed,<br />

the operating mode is set to cooling; when the contact is<br />

opened, the operating mode is set to heating.<br />

3 Room thermostat HC3: the signal is interpreted as a contact<br />

for a thermostat in zone 3. When the contact is closed,<br />

it is sent as a heat request for zone 3.<br />

4 Safety thermostat: connect an underfloor safety thermostat<br />

to the contact. When the contact is closed, water circulation<br />

is interrupted.<br />

5 Photovoltaic integration: input not active (contact open),<br />

no integration.<br />

Input active (contact closed), the energy surplus is used<br />

to increase the DHW set-point by the quantity defined<br />

through parameter 1.20.0 PV offset DHW setpoint temperature<br />

- Delta T Setpoint DHW photovoltaic. If the DHW<br />

cylinder has reached the new set-point, it is possible to use<br />

this energy to increase the set-point of the inertial storage<br />

tank (if present) through parameter 20.4.4 Buffer electric<br />

integration offset or of the heating / cooling function to<br />

the comfort set-point.<br />

Press the selector to confirm.<br />

EN / 49