Commissioning<br />

6.6 Technical parameters<br />

Simultaneously press the “Esc” and “Menu” buttons until “Insert<br />

Code” appears on the display.<br />

Turn the selector to enter the technical code (234) then press<br />

the selector to confirm; the display will show TECHNICAL<br />

AREA.<br />

Turn the selector to choose the desired item.<br />

– COMPLETE MENU<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

1 ENERGY MANAGER<br />

1.0 BASIC PARAMETERS<br />

1.0.0 IDU type<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

0 None.<br />

1 Hybrid Mode: hybrid hydraulic unit.<br />

2 Hydraulic module: wall-hung or floor-standing hydraulic<br />

unit.<br />

3 Light: hydraulic power pack (if any) present, PCB only.<br />

Press the selector to confirm.<br />

1.0.1 ODU type<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

1 Heat Pump: electric heat pump.<br />

Press the selector to confirm.<br />

1.0.2 Tank management<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

0 None.<br />

1 Storage with NTC: presence of a DHW cylinder with temperature<br />

sensor for the NTC cylinder.<br />

2 Storage with Thermostat: presence of a DHW cylinder with<br />

temperature managed through a mechanical thermostat<br />

(ON/OFF).<br />

Press the selector to confirm.<br />

1.0.6 Thermoregulation<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

0 Not active.<br />

1 Active.<br />

Press the selector to confirm.<br />

1.1 INPUT CONFIGURATION<br />

1.1.0 HV input 1 (input configurable to 230 V)<br />

Press the selector . Turn the selector to choose the desired<br />

item.<br />

1 Absent: input not active.<br />

2 EDF: Input not active (0 V). If the comfort function (Par.<br />

1.9.2 Comfort Function) is set as HC-HP, the heat pump and<br />

the heating elements are inhibited for heating of the DHW<br />

cylinder; if the comfort function is set as HC-HP-40°C, heating<br />

of the cylinder is limited to the minimum between the<br />

reduced set-point temperature and 40°C.<br />

Input active (230V). The heat pump and the heating elements<br />

are enabled for heating of the cylinder according to<br />

standard logics.<br />

3 SG1: input 1 for the Smart Grid Ready protocol (refer to the<br />

paragraph “Standard SG ready”).<br />

4 External switch off signal: switches the machine OFF. Every<br />

heating, cooling and DHW request is interrupted while the<br />

anti-freeze protection logics are active.<br />

5 Photovoltaic integration: input not active (0 V), no integration.<br />

Input active (230 V), the energy surplus is used to increase<br />

the DHW set-point by the quantity defined through parameter<br />

1.20.0 PV offset DHW setpoint temperature. If the<br />

DHW cylinder has reached the new set-point, it is possible<br />

to use this energy to increase the set-point of the inertial<br />

storage tank (if present) through parameter 20.4.4 Buffer<br />

electric integration offset or of the heating / cooling function<br />

to the comfort set-point.<br />

Press the selector to confirm.<br />

48 / EN