6. Commissioning<br />
6.1 Checking for electrical dispersions and gas<br />
leakages<br />
6.1.1 Electrical safety checks<br />
Upon completing the installation, check that all the power cables<br />
have been installed in conformity to the relevant national<br />
and local regulations and according to the instructions contained<br />
in the installation manual.<br />
PRIOR TO THE OPERATIONAL TEST<br />
Check the integrity of the earthing circuit.<br />
Measure the earth resistance with a visual inspection and with<br />
a specific tester. The earth resistance must be below 0.1 Ω.<br />
For TT system the earth resistance must be below 15Ω. Please<br />
ensure that differential switch is compliant with that ohmic value<br />
of earth impedance.<br />
DURING THE OPERATIONAL TEST<br />
Check for electrical dispersions.<br />
During the functional test, carry out a complete electrical<br />
check, e.g. with the help of a multimeter, in order to identify<br />
any electrical dispersions.<br />
If an electrical dispersion is detected, switch off the unit immediately<br />
and contact a qualified electrician to identify and solve<br />
the cause of the problem.<br />
a<br />
All electrical connections must be made by an<br />
authorised electrician in conformity to the national<br />
and local electrical standards.<br />
6.2 Preliminary checks<br />
OUTDOOR UNIT<br />
– The unit must be positioned on a sturdy and perfectly<br />
horizontal base, in a place that is easily accessible for<br />
subsequent maintenance operations.<br />
– If there are strong draughts, mount a protective screen<br />
at a suitable distance.<br />
– There must not be any obstacle hindering the flow of<br />
air.<br />
– The supporting structure must be able to withstand the<br />
weight of the outdoor unit.<br />
– If the installation site is subject to frequent snowfalls,<br />
the outdoor unit must be positioned at least 200 mm<br />
above the usual snowfall level.<br />
INDOOR UNIT<br />
– The unit must be positioned in an enclosed space and<br />
in a place easily accessible for subsequent maintenance<br />
operations.<br />
– The unit must be anchored firmly to the floor or wall.<br />
– If the user interface is installed on the appliance, check<br />
that the relative humidity in the installation room does<br />
not exceed the allowed limit.<br />
6.1.2 Check for gas leakages<br />
If a leak detector is used, follow the instructions contained in<br />
the user manual of the device.<br />
EN / 45