Commissioning<br />

6. Commissioning<br />

6.1 Checking for electrical dispersions and gas<br />

leakages<br />

6.1.1 Electrical safety checks<br />

Upon completing the installation, check that all the power cables<br />

have been installed in conformity to the relevant national<br />

and local regulations and according to the instructions contained<br />

in the installation manual.<br />

PRIOR TO THE OPERATIONAL TEST<br />

Check the integrity of the earthing circuit.<br />

Measure the earth resistance with a visual inspection and with<br />

a specific tester. The earth resistance must be below 0.1 Ω.<br />

For TT system the earth resistance must be below 15Ω. Please<br />

ensure that differential switch is compliant with that ohmic value<br />

of earth impedance.<br />

DURING THE OPERATIONAL TEST<br />

Check for electrical dispersions.<br />

During the functional test, carry out a complete electrical<br />

check, e.g. with the help of a multimeter, in order to identify<br />

any electrical dispersions.<br />

If an electrical dispersion is detected, switch off the unit immediately<br />

and contact a qualified electrician to identify and solve<br />

the cause of the problem.<br />

a<br />

All electrical connections must be made by an<br />

authorised electrician in conformity to the national<br />

and local electrical standards.<br />

6.2 Preliminary checks<br />

OUTDOOR UNIT<br />

– The unit must be positioned on a sturdy and perfectly<br />

horizontal base, in a place that is easily accessible for<br />

subsequent maintenance operations.<br />

– If there are strong draughts, mount a protective screen<br />

at a suitable distance.<br />

– There must not be any obstacle hindering the flow of<br />

air.<br />

– The supporting structure must be able to withstand the<br />

weight of the outdoor unit.<br />

– If the installation site is subject to frequent snowfalls,<br />

the outdoor unit must be positioned at least 200 mm<br />

above the usual snowfall level.<br />

INDOOR UNIT<br />

– The unit must be positioned in an enclosed space and<br />

in a place easily accessible for subsequent maintenance<br />

operations.<br />

– The unit must be anchored firmly to the floor or wall.<br />

– If the user interface is installed on the appliance, check<br />

that the relative humidity in the installation room does<br />

not exceed the allowed limit.<br />

6.1.2 Check for gas leakages<br />

If a leak detector is used, follow the instructions contained in<br />

the user manual of the device.<br />

EN / 45