Electrical connections<br />

5.1 Outdoor unit electrical connections<br />

In accordance with the installation instructions, all systems<br />

for disconnecting the main power supply must have an open<br />

contact (4 mm) that guarantees full disconnection as per the<br />

indications of the Class III overvoltage conditions.<br />

a<br />

a<br />

a<br />

Make the earth connection before proceeding<br />

with all the other electrical connections.<br />

The indoor and outdoor units must be powered<br />

separately.<br />

To avoid any risk, the power cable of the indoor<br />

and outdoor units must be installed and replaced<br />

only by specialised technicians.<br />

– Remove the front panel to access the electrical parts.<br />

– Remove the pre-cut sections (1) with the aid of a screwdriver<br />

in order to pass the electrical cables.<br />

1-ph outdoor unit terminal board<br />

M1<br />

EH1 EH1 ST1 ST1 L N ⏚<br />

M2<br />

1ph<br />

G S<br />

ATG<br />

Fig. 53<br />

1<br />

M1 Main power supply terminal board<br />

M2 Signal terminal board<br />

ATG ATG Bus connection between indoor and outdoor units<br />

1ph Connection to single-phase power supply<br />

EH1 Anti-freeze electrical heating element for protecting<br />

hydraulic pipes<br />

ST1 Safety thermostat (230 V) connection for the under-floor<br />

system (bridged by default)<br />

3-ph outdoor unit terminal board<br />

a<br />

Fig. 51<br />

Prior to accessing the terminals, all the supply<br />

circuits must be disconnected.<br />

M1<br />

EH1 EH1 ST1 ST1 L1 L2 L3 N<br />

⏚<br />

M2<br />

M2<br />

M1<br />

3ph<br />

G<br />

S<br />

ATG<br />

Fig. 54<br />

Fig. 52<br />

M1 Main power supply terminal board<br />

M2 Signal terminal board<br />

ATG ATG Bus connection between indoor and outdoor units<br />

3ph Connection to three-phase power supply<br />

EH1 Anti-freeze electrical heating element for protecting<br />

hydraulic pipes<br />

ST1 Safety thermostat (230 V) connection for the under-floor<br />

system (bridged by default)<br />

EN / 35