Electrical connections<br />

The cross-sectional size of the cables used must comply with the system power (see data plate).<br />

The cross-sectional size of the power cables indicated in the table must be regarded as the minimum cross-sectional -size.<br />

i<br />

Prior to accessing the terminals, all the supply circuits must be disconnected.<br />

OUTDOOR UNIT<br />

35 M 50 M 80 M 80<br />

M-T<br />

NIMBUS M EXT <strong>R32</strong><br />

Rated current / live A 11,0 13,5 20,0 7,6 22,5 9,0 26,9 11,0<br />

Maximum current / live A 11,7 14,3 21,3 8,1 23,9 10,0 28,7 12,2<br />

Thermal cut-out size A C-16 C-20 C-32 C-13 C-32 C-13 C-32 C-16<br />

Residual-current circuit breaker<br />

mA F-30 / B-30 B-30 F-30 / B-30 F-30 / B-30<br />

(RCCB) size<br />

B-30<br />

B-30<br />

Surge current A < 3<br />

Rated voltage V 230 230 230 400 230 400 230 400<br />

Permissible voltage fields V 216-<br />

243<br />

216-<br />

243<br />

216-<br />

243<br />

376-<br />

424<br />

216-<br />

243<br />

376-<br />

424<br />

216-<br />

243<br />

376-<br />

424<br />

Cos phi > 0,9<br />

Power supply wiring Reference H07RN-F<br />

Cable min. cross-sectional<br />

3G4 3G4 3G4 5G2,5 3G6 5G2,5 3G6 5G2,5<br />

size<br />

Max. diameter [mm] 14 16,2 16,2 17 17 17 18 18<br />

Recommended cable 3G4 3G4 3G6 5G4 3G6 5G4 3G6 5G4<br />

cross-sectional size<br />

Communication cabling Reference H05RN-F<br />

Cable cross-sectional<br />

3 x 0,75mm 2<br />

size<br />

Max. length<br />

50 m<br />

The power supplies of the indoor and outdoor units must be connected respectively to a dedicated residual-current circuit breaker<br />

(RCCB) with a minimum threshold of 30 mA. For units equipped with an inverter (outdoor unit), we recommend using type B<br />

residual-current devices for 3 ph power supplies and type B or F devices (depending on the electrical system to which they are<br />

connected) for 1 ph power supplies. For units lacking an inverter (indoor unit), a type A residual-current device will suffice. The type<br />

of connection must nonetheless be made in a workmanlike manner by qualified personnel in order to comply with the national<br />

regulations in force.<br />

Main power supply table.<br />

INDOOR UNIT NIMBUS FS-<strong>UK</strong> M <strong>R32</strong> NIMBUS FS-L-<strong>UK</strong> M <strong>R32</strong><br />

Power supply V - ph - Hz 230 - 1 -50 400 - 3 -50 230 - 1 -50 400 - 3 -50<br />

Permissible voltage fields V 196 ÷ 253 340 ÷ 440 196 ÷ 253 340 ÷ 440<br />

Nominal absorbed power kW 4 4 6 6<br />

Maximum current A 19,1 9,6 30 10<br />

Thermal cut-out A C-25 C-16 C-32 C-16<br />

Residual-current circuit breaker<br />

mA A-30<br />

(RCCB) size<br />

Power supply wiring Reference H07RN-F<br />

Cable min. cross-sectional<br />

3G4 5G2,5 3G6 5G2,5<br />

size<br />

Max. diameter [mm] 16,2 17 18 17<br />

Recommended cable 3G4 5G4 3G6 5G4<br />

cross-sectional size<br />

Max. diameter [mm] 16,2 19,9 18 19,9<br />

EDF, AFR, PV signal cabling mm 2 H05RN-F 2 x 0,75 mm 2 - H07RN-F 2 x 1,0 mm 2<br />

Note: in making the connection between the communication cable from the indoor unit to the outdoor unit, use a shielded cable<br />

to prevent interference problems.<br />

120<br />

M<br />

120<br />

M-T<br />

150<br />

M<br />

150<br />

M-T<br />