Hydraulic connections<br />
4.1.1 Safety valve drain<br />
a<br />
– Make sure that the drainage pipe (1) supplied is connected<br />
to the safety valve (2) and comes out through<br />
the hole (3).<br />
The drainage pipe must be connected to the<br />
sewerage system.<br />
2<br />
1<br />
3<br />
Fig. 42<br />
4.1.2 Minimum water content<br />
a<br />
The system must be sized for a minimum water<br />
content of at least 5 litres for every kW of rated<br />
power. If the minimum water content is not observed,<br />
the appliance is not guaranteed to function.<br />
To optimise the system’s efficiency, comfort and correct operation,<br />
we recommend:<br />
– reducing the set-point temperature of the room during<br />
winter operation when the outdoor temperature<br />
increases.<br />
– increasing the set-point temperature of the room during<br />
summer operation when the outdoor temperature<br />
decreases.<br />
Should this not be possible, we recommend increasing the water<br />
content in the system.<br />
If, for an extended period of time, the minimum thermal load is<br />
lower than the minimum power delivered by the machine, we<br />
recommend increasing the water content in the system.<br />
4.1.3 Expansion vessel<br />
The indoor unit is equipped with an expansion vessel with a 12<br />
l nominal capacity pre-charged to 0.1 MPa (1 bar) and with a<br />
0.3 MPa (3 bar) safety valve on the hydraulic circuit.<br />
i<br />
The installer is responsible fro ensuring that the<br />
expansion vessel is suitably sized in relation to<br />
the system’s total water content, regardless of<br />
the valves that can exclude certain parts of the<br />
hydraulic circuit.<br />
4.1.4 Rated and minimum flow rate<br />
The minimum flow rate must always be guaranteed in all operating<br />
conditions.<br />
Model<br />
NIMBUS M<br />
EXT <strong>R32</strong> 35 M<br />
NIMBUS M<br />
EXT <strong>R32</strong> 50 M<br />
NIMBUS M<br />
EXT <strong>R32</strong> 80 M<br />
& M-T<br />
NIMBUS M<br />
EXT <strong>R32</strong> 120<br />
M & M-T<br />
NIMBUS M<br />
EXT <strong>R32</strong> 150<br />
M & M-T<br />
Nominal<br />
flow rate<br />
[l/h]<br />
Minimum<br />
flow rate<br />
[l/h]<br />
Flow meter<br />
ON threshold<br />
[l/h]<br />
600 430 390<br />
860 430 390<br />
1200 600 540<br />
1550 770 702<br />
1900 940 852<br />
26 / EN