Hydraulic connections<br />

4.1.1 Safety valve drain<br />

a<br />

– Make sure that the drainage pipe (1) supplied is connected<br />

to the safety valve (2) and comes out through<br />

the hole (3).<br />

The drainage pipe must be connected to the<br />

sewerage system.<br />

2<br />

1<br />

3<br />

Fig. 42<br />

4.1.2 Minimum water content<br />

a<br />

The system must be sized for a minimum water<br />

content of at least 5 litres for every kW of rated<br />

power. If the minimum water content is not observed,<br />

the appliance is not guaranteed to function.<br />

To optimise the system’s efficiency, comfort and correct operation,<br />

we recommend:<br />

– reducing the set-point temperature of the room during<br />

winter operation when the outdoor temperature<br />

increases.<br />

– increasing the set-point temperature of the room during<br />

summer operation when the outdoor temperature<br />

decreases.<br />

Should this not be possible, we recommend increasing the water<br />

content in the system.<br />

If, for an extended period of time, the minimum thermal load is<br />

lower than the minimum power delivered by the machine, we<br />

recommend increasing the water content in the system.<br />

4.1.3 Expansion vessel<br />

The indoor unit is equipped with an expansion vessel with a 12<br />

l nominal capacity pre-charged to 0.1 MPa (1 bar) and with a<br />

0.3 MPa (3 bar) safety valve on the hydraulic circuit.<br />

i<br />

The installer is responsible fro ensuring that the<br />

expansion vessel is suitably sized in relation to<br />

the system’s total water content, regardless of<br />

the valves that can exclude certain parts of the<br />

hydraulic circuit.<br />

4.1.4 Rated and minimum flow rate<br />

The minimum flow rate must always be guaranteed in all operating<br />

conditions.<br />

Model<br />

NIMBUS M<br />

EXT <strong>R32</strong> 35 M<br />

NIMBUS M<br />

EXT <strong>R32</strong> 50 M<br />

NIMBUS M<br />

EXT <strong>R32</strong> 80 M<br />

& M-T<br />

NIMBUS M<br />

EXT <strong>R32</strong> 120<br />

M & M-T<br />

NIMBUS M<br />

EXT <strong>R32</strong> 150<br />

M & M-T<br />

Nominal<br />

flow rate<br />

[l/h]<br />

Minimum<br />

flow rate<br />

[l/h]<br />

Flow meter<br />

ON threshold<br />

[l/h]<br />

600 430 390<br />

860 430 390<br />

1200 600 540<br />

1550 770 702<br />

1900 940 852<br />

26 / EN