04.03.2024 Views

Nimbus Compact M NET R32 Installation Manual UK

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Hydraulic connections<br />

4. Hydraulic connections<br />

4.1 Indoor unit hydraulic connections<br />

Preliminary checks:<br />

a<br />

– Check that the system has been cleaned;<br />

– Check that there are no impurities in the circuit water;<br />

– Check that compatible components are used (e.g. do<br />

not connect copper and steel to each other);<br />

– Check that the connection to the heating system has<br />

been made correctly;<br />

– check that the water supply distribution network pressure<br />

does not exceed 0.5 MPa (5 bar), otherwise install a<br />

pressure reducer at the system's intake;<br />

– check that a disconnect device with cock is installed<br />

between the system and the domestic water supply<br />

distribution network (if present);<br />

– check that the supplied expansion vessel is large<br />

enough to handle the water in the system and, if necessary,<br />

install an additional one;<br />

Remove the rubber protective caps before making<br />

the hydraulic connections. The plugs are<br />

used exclusively as a protective device during<br />

transport.<br />

After the checks:<br />

Z1<br />

OUT<br />

1<br />

2<br />

3<br />

B<br />

7<br />

4<br />

5<br />

IN<br />

A<br />

6<br />

8<br />

OUT<br />

Z1<br />

IN<br />

Fig. 41<br />

(*) If recirculation is used, remove the brass plug before using<br />

the connection<br />

1-ZONE configuration<br />

– Mount the quick couplings (present inside the machine)<br />

on the water pipes (1), (3), (7) and (8).<br />

8<br />

1<br />

7<br />

3<br />

Fig. 40<br />

Consider the following hydraulic connections:<br />

– System flow (1)<br />

– Safety valve drain (2)<br />

– Delivery to heat pump (3)<br />

– Recirculation (4) (if present) (*)<br />

– Domestic hot water return (5)<br />

– Domestic hot water flow (6)<br />

– System return (7)<br />

– Return from heat pump (8).<br />