simatic<br />
SIMATIC PCS 7<br />
Process Control <strong>System</strong><br />
Catalog ST PCS 7 · October 2004
Related catalogs<br />
SIMATIC<br />
Add-Ons for the SIMATIC PCS 7<br />
Process Control <strong>System</strong><br />
Order No.:<br />
E86060-K4678-A121-A4-7600<br />
SIMATIC<br />
Products for<br />
Totally Integrated <strong>Automation</strong><br />
<strong>and</strong> Micro <strong>Automation</strong><br />
Order No.:<br />
E86060-K4670-A101-A9-7600<br />
SIMATIC HMI<br />
Human Machine Interface<br />
<strong>System</strong>s<br />
Order No.:<br />
E86060-K4680-A101-B2-7600<br />
Industrial Communication<br />
Industrial Communication for<br />
<strong>Automation</strong> <strong>and</strong> <strong>Drives</strong><br />
Order No.:<br />
E86060-K6710-A101-B4-7600<br />
TELEPERM M<br />
AS 488/TM<br />
<strong>Automation</strong> <strong>System</strong>s<br />
Order No.:<br />
E86060-W3812-A100-A3-7600<br />
Field instruments for<br />
Process <strong>Automation</strong><br />
Order No.:<br />
E86060-K6201-A101-A6-7600<br />
Trademarks<br />
ST PCS 7.A<br />
ST 70<br />
ST 80<br />
IK PI<br />
PLT 112<br />
FI 01<br />
All product designations may be trademarks or product<br />
names of <strong>Siemens</strong> AG or supplier companies whose<br />
use by third parties for their own purposes could violate<br />
the rights of the owners.<br />
SITRAIN ITC<br />
Training for <strong>Automation</strong> <strong>and</strong><br />
Industrial Solutions<br />
Order No.:<br />
E86060-K6850-A101-B5<br />
CD-ROM: E86060-D6850-A100-C2-7400<br />
Components<br />
for <strong>Automation</strong><br />
Order No.:<br />
E86060-D4001-A100-C2-7600<br />
A&D Mall<br />
CA 01<br />
Internet:<br />
www.siemens.com/automation/mall
SIMATIC PCS 7<br />
Process Control <strong>System</strong><br />
Catalog<br />
ST PCS 7 · October 2004<br />
Online Edition<br />
The products listed in this catalog<br />
are also available in the electronic<br />
Catalog CA 01 on CD-ROM<br />
Order No.:<br />
E86060-D4001-A100-C3-7600<br />
Please contact your nearest<br />
<strong>Siemens</strong> branch office<br />
© <strong>Siemens</strong> AG 2004<br />
The products <strong>and</strong> systems<br />
described in this<br />
catalog are manufactured/distributed<br />
under<br />
application of a certified<br />
quality management<br />
system in accordance<br />
with DIN EN ISO 9001<br />
(Certified Registration<br />
No. 1323-03). The certificate<br />
is recognized by<br />
all IQNet countries.<br />
s<br />
Introduction<br />
<strong>System</strong>-neutral components<br />
SIMATIC PCS 7 BOX<br />
<strong>Engineering</strong> <strong>System</strong><br />
Operator <strong>System</strong><br />
Batch automation<br />
SIMATIC Route Control<br />
IT world<br />
Communication<br />
<strong>Automation</strong> systems<br />
Process I/O<br />
Migration to SIMATIC PCS 7<br />
Appendix<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
13
1/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Welcome to<br />
<strong>Automation</strong> <strong>and</strong> <strong>Drives</strong><br />
We would like to welcome you to <strong>Automation</strong> <strong>and</strong><br />
<strong>Drives</strong> <strong>and</strong> our comprehensive range of products,<br />
systems, solutions <strong>and</strong> services for production <strong>and</strong><br />
process automation <strong>and</strong> building technology<br />
worldwide.<br />
With Totally Integrated <strong>Automation</strong> <strong>and</strong> Totally<br />
Integrated Power, we deliver solution platforms based<br />
on st<strong>and</strong>ards that offer you a considerable savings<br />
potential.<br />
Discover the world of our technology now. If you need<br />
more detailed information, please contact one of your<br />
regional <strong>Siemens</strong> partners.<br />
They will be glad to assist you.
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
1/3
1/4<br />
Industrial<br />
Industrial<br />
Ethernet<br />
PROCESS FIELD<br />
PROFIBUS<br />
Ethernet<br />
AS-Interface<br />
GAMMA instabus<br />
Control<br />
Safety Integrated<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Totally Integrated <strong>Automation</strong> –<br />
innovations for more productivity<br />
With the launch of Totally Integrated <strong>Automation</strong>, we were<br />
the first ones on the market to consistently implement the<br />
trend from equipment to an integrated automation solution,<br />
<strong>and</strong> have continuously improved the system ever since.<br />
Whether your industry is process- <strong>and</strong> production-oriented or<br />
a hybrid, Totally Integrated <strong>Automation</strong> is a unique "common<br />
solution" platform that covers all the sectors.<br />
Totally Integrated <strong>Automation</strong> is an integrated platform for the<br />
entire production line - from receiving to technical processing<br />
SIMATIC NET<br />
Industrial<br />
Communication<br />
ERP<br />
Enterprise<br />
Resource<br />
Planning<br />
MES<br />
Manufacturing<br />
Execution<br />
<strong>System</strong>s<br />
SINAUT Telecontrol<br />
<strong>System</strong><br />
PC-based <strong>Automation</strong><br />
Building<br />
Technology<br />
Ethernet<br />
Production<br />
Order<br />
Management<br />
Production<br />
Operations<br />
Recording<br />
SIMATIC<br />
Machine Vision<br />
Ethernet<br />
SIMATIC<br />
Software<br />
Micro-<strong>Automation</strong><br />
<strong>and</strong><br />
Actuator-Sensor<br />
Interface Level<br />
Material<br />
Management<br />
Equipment<br />
Management<br />
Industrial Wireless<br />
Communication/<br />
MOBIC<br />
ECOFAST IP65<br />
Decentral<br />
<strong>Automation</strong> <strong>System</strong>
SIMATIC<br />
Controller/<br />
<strong>Automation</strong><br />
<strong>System</strong><br />
SIMATIC IT Framework<br />
Production Modeler<br />
SENTRON<br />
Circuit<br />
Breakers<br />
SIMATIC<br />
Distributed<br />
I/O<br />
<strong>and</strong> production areas to shipping. Thanks to the system-oriented<br />
engineering environment, integrated, open communications<br />
as well as intelligent diagnostics options, your plant now<br />
benefits in every phase of the life cycle.<br />
In fact, to this day we are the only company worldwide that<br />
can offer a control system based on an integrated platform<br />
for both the production <strong>and</strong> process industry.<br />
SIMATIC PCS 7<br />
Process Control<br />
<strong>System</strong><br />
Field Instrumentation/<br />
Analytics<br />
Plant<br />
Information<br />
Management<br />
Detailed<br />
Production<br />
Scheduling<br />
SINUMERIK<br />
Numeric<br />
Control<br />
Product Specification<br />
Management <strong>System</strong><br />
Laboratory Information<br />
Management <strong>System</strong><br />
SIMOTION<br />
Motion Control<br />
<strong>System</strong><br />
Sensor<br />
Technology<br />
IQ-Sense<br />
HART<br />
SIMOCODE-DP<br />
Motor<br />
PROFIBUS PA<br />
Protection<br />
<strong>and</strong> Control<br />
SIWAREX<br />
Weighing<br />
Technology<br />
SIMODRIVE SINAMICS<br />
SIMATIC HMI<br />
Human Machine<br />
Interface<br />
Drive <strong>System</strong>s/<br />
SINAMICS<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
1/5
1/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Totally Integrated Power –<br />
energy distribution <strong>and</strong> management<br />
from one source<br />
Totally Integrated Power by <strong>Siemens</strong> offers integrated<br />
solutions for energy distribution in functional <strong>and</strong> industrial<br />
buildings covering everything from medium-high voltage to<br />
power outlets.<br />
Totally Integrated Power is based on integration in<br />
planning <strong>and</strong> configuration as well as coordinated products<br />
<strong>and</strong> systems. In addition, it features communications <strong>and</strong><br />
software modules for connecting power distribution systems<br />
to industrial automation <strong>and</strong> building automation, thereby<br />
offering a substantial savings potential.<br />
Communications<br />
Process/production<br />
automation<br />
Products <strong>and</strong> systems<br />
Planning <strong>and</strong> configuration<br />
PROCESS FIELD BUS<br />
HMI Load<br />
Graphs Prognoses<br />
management<br />
U<br />
I<br />
cos o<br />
P<br />
W<br />
£ 110 kV
Maintenance<br />
Substation<br />
Distribution<br />
Maintenance<br />
task<br />
Hall 1 Air conditioning system<br />
checkup<br />
Distribution 3 Replacing circuit<br />
breaker contacts<br />
Infeed II Replacing meters<br />
Message/<br />
error<br />
management<br />
central ON<br />
OFF<br />
local ON<br />
OFF<br />
tripped<br />
Selective<br />
protection<br />
Protocols Power<br />
DATE:<br />
quality<br />
EMPLOYEE<br />
COST CENTER<br />
PAY PERIOD BEGINNING<br />
PAY PERIOD ENDING<br />
DATE<br />
SUN MON TUE WED THUR FRI SAT SUN TOTAL<br />
IN<br />
OUT<br />
IN<br />
OUT<br />
OVERTIME<br />
TOTAL HOURS<br />
DATE<br />
SUN MON TUE WED THUR FRI SAT SUN TOTAL<br />
IN<br />
OUT<br />
IN<br />
OUT<br />
OVERTIME<br />
TOTAL HOURS<br />
DATE<br />
SUN MON TUE WED THUR FRI SAT SUN TOTAL<br />
IN<br />
OUT<br />
IN<br />
OUT<br />
OVERTIME<br />
TOTAL HOURS<br />
CODES<br />
V=VACATION<br />
H=HOLIDAY<br />
S=SICK<br />
REGULAR HOLIDAY OTHER<br />
OVER THE HOURS<br />
SICK VACATION<br />
TIME & ONE-HALF<br />
Cost center<br />
instabus EIB<br />
Building<br />
automation<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
1/7
Introduction<br />
<strong>System</strong> architecture<br />
SIMATIC PCS 7<br />
■ Overview<br />
SIMATIC PCS 7 <strong>System</strong> Configuration<br />
SIMATIC PCS 7 – The process control system for Totally Integrated<br />
<strong>Automation</strong><br />
Using Totally Integrated <strong>Automation</strong> (TIA), <strong>Siemens</strong> provides uniform<br />
automation technology on one single platform for all applications<br />
of process automation, starting with input logistics, covering<br />
production or primary processes as well as downstream<br />
(secondary) processes, up to output logistics. This uniform automation<br />
technology also facilitates the optimization of all company<br />
operations, covering the enterprise resource planning<br />
(ERP) level, the management execution system (MES) level, the<br />
process control level, down to the field level.<br />
Horizontal integration<br />
Horizontal integration means that common <strong>and</strong> st<strong>and</strong>ard hardware/software<br />
components from the SIMATIC product portfolio<br />
are used for the complete production process - covering input<br />
logistics, primary <strong>and</strong> secondary processes, up to output logistics.<br />
As the process control system component of Totally Integrated<br />
<strong>Automation</strong>, SIMATIC PCS 7 uses st<strong>and</strong>ard hardware <strong>and</strong> software<br />
components from the SIMATIC TIA range. The uniform data<br />
management, communication <strong>and</strong> configuration capabilities of<br />
TIA offer an open platform for advanced, future-oriented <strong>and</strong><br />
economical automation solutions in all sectors of the process industry,<br />
manufacturing industry <strong>and</strong> hybrid industries (which include<br />
a mixture of continuous/batch/discrete processes such as<br />
in the glass or pharmaceuticals industries).<br />
While secondary <strong>and</strong> logistics processes in the process <strong>and</strong> hybrid<br />
industries are often automated by Motion Control <strong>and</strong><br />
SIMATIC components, the primary processes are a domain of<br />
the SIMATIC PCS 7 process control system.<br />
1/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Within the TIA network, SIMATIC PCS 7 not only h<strong>and</strong>les st<strong>and</strong>ard<br />
(primary) process control tasks, but it can also automate<br />
secondary processes (e.g. filling, packaging) or input/output logistics<br />
(e.g. raw material distribution, storage) for a production<br />
location.<br />
Vertical integration<br />
Vertical integration is characterized by uniform <strong>and</strong> transparent<br />
data communication from the ERP level, through the MES level<br />
<strong>and</strong> the Control level, down to the field level. It is reflected in the<br />
increased fusion of automation technology <strong>and</strong> information technology<br />
<strong>and</strong> their st<strong>and</strong>ards in the wake of establishing companywide<br />
information networks. This enables the modularization <strong>and</strong><br />
st<strong>and</strong>ardization of whole subprocesses, resulting in far higher<br />
flexibility of production.<br />
Vertical integration of SIMATIC PCS 7 into the company environment<br />
includes:<br />
Integration in the company-wide information network<br />
Integration of field systems<br />
By linking the automation level to the IT world, process data becomes<br />
available throughout the company for evaluation, planning,<br />
coordination <strong>and</strong> optimization of operation, production processes<br />
<strong>and</strong> commercial processes. Also taken into account are<br />
the geographical requirements of distributed production facilities,<br />
as is the case with global companies.
SIMATIC PCS 7 is optimized for integration of distributed field<br />
systems into the process control system, <strong>and</strong> is based on<br />
PROFIBUS technology. PROFIBUS is simple, rugged <strong>and</strong> reliable,<br />
<strong>and</strong> is used worldwide in all sectors of the process, manufacturing<br />
<strong>and</strong> hybrid industries – for input/output logistics as well<br />
as for primary <strong>and</strong> secondary processes. It supports redundancy<br />
<strong>and</strong> failsafe architectures, in addition to online expansions,<br />
<strong>and</strong> can be used in st<strong>and</strong>ard environments or in hazardous<br />
areas. The plant can be equipped with classical signal<br />
inputs/outputs on the ET 200 distributed I/O station, or with<br />
state-of-the-art, intelligent field devices.<br />
■ Benefits<br />
The innovative design of SIMATIC PCS 7 is based on a modular<br />
<strong>and</strong> open architecture using state-of-the-art SIMATIC technology,<br />
consistent implementation of industrial st<strong>and</strong>ards, <strong>and</strong> process<br />
control functionalities combined with high performance.<br />
This means that with the SIMATIC PCS 7 process control system,<br />
users can achieve cost-effective implementation <strong>and</strong> economical<br />
operation of process control facilities during all phases of<br />
their life cycle <strong>and</strong> with due allowance for all aspects: from planning,<br />
engineering, commissioning <strong>and</strong> training to operation,<br />
maintenance, servicing, expansion <strong>and</strong> renovation. In the process,<br />
SIMATIC PCS 7 unifies high performance <strong>and</strong> reliability<br />
with simple <strong>and</strong> safe operation <strong>and</strong> maximum convenience.<br />
Customers benefit from Totally Integrated <strong>Automation</strong> <strong>and</strong> the<br />
SIMATIC PCS 7 process control system mainly through<br />
calculable development, implementation <strong>and</strong> life cycle costs,<br />
minimization of engineering resources,<br />
process optimization options,<br />
flexibility to adapt quickly to changes in requirements,<br />
advantages resulting from the use of SIMATIC st<strong>and</strong>ard components,<br />
such as<br />
- low hardware <strong>and</strong> engineering costs,<br />
- proven quality <strong>and</strong> stability,<br />
- simple, fast definition <strong>and</strong> selection of system components,<br />
- low costs for spare parts,<br />
- short delivery times for spare parts <strong>and</strong> expansion components,<br />
- worldwide availability,<br />
- savings in logistics, maintenance <strong>and</strong> training costs.<br />
■ Function<br />
A consistent <strong>and</strong> homogeneous overall system<br />
SIMATIC PCS 7 is a modern process control system that can be<br />
used alone <strong>and</strong> in combination with Motion Control <strong>and</strong> SIMATIC<br />
as a consistent <strong>and</strong> homogeneous overall system. The appeal of<br />
SIMATIC PCS 7 is likely to increase in keeping with the dem<strong>and</strong><br />
for seamless, consistent automation engineering, fueled by unrelenting<br />
competition <strong>and</strong> pressure on prices, <strong>and</strong> the dem<strong>and</strong><br />
for production plants of increasing flexibility, <strong>and</strong> the need to enhance<br />
productivity.<br />
Against the background of increasing complexity, due in particular<br />
to the merging of automation engineering with information<br />
technology, the importance of system platforms that are uniform<br />
in both horizontal <strong>and</strong> vertical directions is growing, while that of<br />
automation solutions with so-called "best-in-class products“ is<br />
waning. As a component of Totally Integrated <strong>Automation</strong>, SI-<br />
MATIC PCS 7 is therefore ideally equipped for the challenges of<br />
the future.<br />
Introduction<br />
<strong>System</strong> architecture<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
SIMATIC PCS 7<br />
High performance <strong>and</strong> outst<strong>and</strong>ing system characteristics - together<br />
with consistent data management, communication <strong>and</strong><br />
configuration - guarantee that the typical dem<strong>and</strong>s made of a<br />
process control system are fully met by SIMATIC PCS 7:<br />
7 simple <strong>and</strong> reliable process control,<br />
7 user-friendly operation <strong>and</strong> visualization,<br />
7 powerful, fast <strong>and</strong> consistent system-wide engineering,<br />
7 system-wide online alterability,<br />
7 open system architecture at all levels,<br />
7 flexibility <strong>and</strong> scalability,<br />
7 redundancy at all levels,<br />
7 failsafe automation solutions,<br />
7 comprehensive field bus integration,<br />
7 flexible solutions for batch processes,<br />
7 direct connection to the IT world.<br />
Flexibility <strong>and</strong> scalability<br />
As a result of its modular <strong>and</strong> open architecture, which is based<br />
on selected hardware <strong>and</strong> software components from the st<strong>and</strong>ard<br />
SIMATIC range, SIMATIC PCS 7 can be applied effectively<br />
in small <strong>and</strong> large plants alike. It allows easy expansion or system<br />
modification to enable customers to meet the changing production<br />
requirements of their facility. SIMATIC PCS 7 is scalable<br />
from a small single system consisting of approx. 160 process<br />
objects (motors, valves, PID controllers), such as might be used<br />
for a laboratory system or a test center, up to a distributed multiuser<br />
system with client/server architecture <strong>and</strong> approx.<br />
60,000 process objects, such as might be used for automation<br />
of a very large production plant or for groups of connected facilities.<br />
SIMATIC PCS 7 thus covers all sizes of plant - <strong>and</strong> if the plant<br />
grows, SIMATIC PCS 7 grows with it!<br />
Open for the future<br />
SIMATIC PCS 7 is based on modular hardware <strong>and</strong> software<br />
components, which are perfectly matched to one another due to<br />
their conformance with TIA. These components are flexible <strong>and</strong><br />
exp<strong>and</strong>able, <strong>and</strong> are open for future enhancements through the<br />
use of st<strong>and</strong>ard interfaces with long-term stability. This means it<br />
is possible to provide long-term protection for customer investments<br />
despite high innovation speeds <strong>and</strong> short product life cycles.<br />
SIMATIC PCS 7 consistently applies new, powerful technologies<br />
together with internationally established industrial st<strong>and</strong>ards<br />
such as IEC, XML, PROFIBUS, Ethernet, TCP/IP, OPC,<br />
@aGlance, ISA 88 <strong>and</strong> ISA 95, just to mention a few.<br />
SIMATIC PCS 7’s openness covers all levels <strong>and</strong> applies as<br />
much to automation system <strong>and</strong> process peripherals as to operator<br />
<strong>and</strong> engineering systems, industrial communication networks<br />
or the SIMATIC IT framework as a link to information, coordination<br />
<strong>and</strong> planning tools for company management.<br />
However, this openness is not only characterized by the system<br />
architecture, horizontal/vertical integration <strong>and</strong> communication,<br />
but also by programming <strong>and</strong> data exchange interfaces for user<br />
programs as well as import/export functions for graphics, text<br />
<strong>and</strong> data, e.g. from the CAD/CAE world.<br />
SIMATIC PCS 7 can therefore also be combined with components<br />
from other vendors, <strong>and</strong> integrated in existing infrastructures.<br />
1/9
1/10<br />
Introduction<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
<strong>System</strong>-neutral<br />
components<br />
2/2 <strong>System</strong> documentation<br />
2/3 Administration<br />
2/4 Software Update Service<br />
2/5 ES/OS/BATCH/IT basic devices<br />
2/5 Introduction<br />
2/6 Basic hardware<br />
2/10 Multi-VGA graphic cards<br />
2/11 Operating devices/monitors<br />
2/12 Operating system<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
<strong>System</strong>-neutral components<br />
2 <strong>System</strong> documentation<br />
■ Overview<br />
Complete documentation for the SIMATIC PCS 7 process control<br />
system is available on CD-ROM. The documentation comes in<br />
3 languages (German/English/French) <strong>and</strong> includes all essential<br />
manuals: from system-wide documentation to individual descriptions<br />
of engineering tools, distributed I/Os, automation systems,<br />
operator systems <strong>and</strong> communication components. Getting<br />
Started items with sample projects are available by way of<br />
practical introduction.<br />
A separate programming guide for creating driver blocks is also<br />
available. This programming guide helps the advanced<br />
SIMATIC PCS 7 user to create system-conform driver blocks,<br />
which can be placed like st<strong>and</strong>ard components on system plans<br />
<strong>and</strong> automatically parameterized <strong>and</strong> configured in HW Config.<br />
In addition there is a multilingual S7 Manual Collection, which includes<br />
manuals for SIMATIC S7-200/300/400, SIMATIC C7, the<br />
LOGO! logic module, SIMATIC DP, SIMATIC PC, SIMATIC programming<br />
units, STEP 7, <strong>Engineering</strong> Software, Runtime Software,<br />
SIMATIC PCS 7, SIMATIC HMI <strong>and</strong> SIMATIC NET. Comprehensive<br />
documentation is thus available for all SIMATIC S7<br />
components used in context with SIMATIC PCS 7.<br />
The TELEPERM M Manual Collection is a bilingual (German <strong>and</strong><br />
English) collection of TELEPERM M manuals on CD-ROM. It replaces<br />
the complete documentation for the SIMATIC PCS 7 with<br />
all the relevant manuals for TELEPERM M migration.<br />
■ More information<br />
The "SIMATIC Technical Documentation Guide" on the Internet<br />
directs you straight to the technical documentation available for<br />
the various SIMATIC products <strong>and</strong> systems in the languages<br />
German, English, French, Italian <strong>and</strong> Spanish.<br />
Additional information is available in the Internet under:<br />
http://www.siemens.com/simatic-docu<br />
2/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC PCS 7<br />
Documentation CD<br />
SIMATIC PCS 7 documentation<br />
on CD-ROM, trilingual (German,<br />
English, French)<br />
Contents include:<br />
General documentation for<br />
SIMATIC PCS 7, e.g.<br />
- What’s new in PCS 7 V6.0<br />
- Outline description of SIMATIC<br />
PCS 7<br />
- Getting Started with PCS 7<br />
First Contact<br />
Part 1 – Basic Functions<br />
Part 2 – Rational <strong>Engineering</strong><br />
- ES Configuration Manual<br />
- OS Configuration Manual<br />
- Fault-Tolerant Process Control<br />
<strong>System</strong>s<br />
- PC Configuration <strong>and</strong> Authorization<br />
- 10 ms Time Stamp<br />
- Service Support <strong>and</strong> Diagnostics<br />
- PCS 7 Block Library<br />
Distributed I/Os<br />
- ET 200M<br />
- ET 200S<br />
- ET 200iS<br />
SIMATIC Operator <strong>System</strong> –<br />
Basic Process Control<br />
SIMATIC PDM<br />
SIMATIC <strong>Engineering</strong> Tools<br />
(STEP 7, CFC, SFC, S7-SCL,<br />
DOCPRO, BATCH, @PCS 7)<br />
Communication<br />
- S7-300 Communication<br />
- General Communication with<br />
SIMATIC<br />
- Bus Links<br />
- Couplers<br />
- SIMATIC NET Manuals<br />
SIMATIC Controls (<strong>Automation</strong><br />
<strong>System</strong>s)<br />
- S7-300, S7-400 Module Data<br />
- S7-300 Central Modules<br />
- S7-400H Fault-Tolerant <strong>System</strong>s<br />
- S7-400F/FH Failsafe <strong>System</strong>s<br />
6ES7 650-0XX06-8YX8 D)<br />
SIMATIC PCS 7 Programming<br />
Instructions for Creating Driver<br />
Blocks<br />
for SIMATIC PCS 7 V6.0 <strong>and</strong> V5.2,<br />
in Acrobat Reader Format (PDF)<br />
on CD-ROM, German/English<br />
SIMATIC S7 Manuals<br />
6ES7 653-1XD06-8YX8<br />
S7 Manual Collection<br />
Electronic manuals on CD, in<br />
5 languages (German, English,<br />
French, Italian, Spanish)<br />
6ES7 998-8XC01-8YE0 C)<br />
S7 Manual Collection - Maintenance<br />
Service for 1 Year<br />
Scope of supply: Current CD<br />
"S7 Manual Collection" <strong>and</strong> the<br />
three subsequent updates<br />
TELEPERM M Migration<br />
Manuals<br />
6ES7 998-8XC01-8YE2 C)<br />
TELEPERM M Manual Collection<br />
Electronic manuals on CD-ROM,<br />
bilingual (German, English)<br />
6DL5 900-8AX03-8YX8 C)<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1
■ Overview<br />
<strong>System</strong>-neutral components<br />
SIMATIC Electronic Signature<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Administration<br />
Central user management, access control <strong>and</strong> electronic<br />
signature<br />
The SIMATIC Electronic Signature ensures that operations cannot<br />
be performed until enabled by previously assigned Windows<br />
users/user groups. Users/user groups are assigned to the operations<br />
in the respective application. The SIMATIC Electronic Signature<br />
has to be installed on all clients/single stations of the plant<br />
SIMATIC Logon offers central user administration with security that access this application.<br />
<strong>and</strong> access control based on Windows 2000/XP <strong>and</strong> Windows At the moment this function is implemented as a system function<br />
2003 Server for the SIMATIC PCS 7 system components as well only on SIMATIC BATCH. However, the Electronic Signature can<br />
as non-SIMATIC components connected through an interface. It be used on any products in the specific applications.<br />
can be used to fulfill the validation requirements of 21 CFR<br />
Part 11. An electronic signature function can also be used in ■ Selection <strong>and</strong> Ordering Data Order No.<br />
conjunction with SIMATIC Logon.<br />
SIMATIC Logon Admin Tool 6ES7 658-7AX21-2YB5 C)<br />
The optional Chipcard Reader can be used for access control in Floating license for 1 user<br />
addition to the keyboard. It is also possible, however, to connect<br />
other logon devices with their corresponding drivers, e.g. a Fingerprint<br />
Mouse.<br />
<strong>Engineering</strong> software on CD-ROM<br />
(German, English, French, Spanish,<br />
Italian) <strong>and</strong> authorization diskette<br />
■ Function<br />
SIMATIC Logon Service<br />
Single license for 1 installation<br />
6ES7 658-7BX21-2YA0 C)<br />
SIMATIC Logon Admin Tool<br />
Runtime software on CD-ROM<br />
(German, English, French, Span-<br />
Using the SIMATIC Logon Admin Tool it is possible to assign the<br />
roles defined in the SIMATIC PCS 7 applications (e.g. <strong>Automation</strong><br />
License Manager <strong>and</strong> SIMATIC BATCH) to the Windows users/user<br />
groups. Administrators with the necessary Windows administrator<br />
privileges can also use the SIMATIC Logon Admin<br />
Tool to edit Windows users <strong>and</strong> user groups.<br />
ish, Italian) <strong>and</strong> authorization diskette<br />
SIMATIC Electronic Signature<br />
Single license for 1 installation<br />
Runtime software on CD-ROM<br />
(German, English, French, Spanish,<br />
Italian) <strong>and</strong> authorization dis-<br />
6ES7 658-7CX21-2YB0 C)<br />
The SIMATIC Logon Admin Tool is required once per plant (floatketteing<br />
license).<br />
Option<br />
SIMATIC Logon Service<br />
Chipcard reader<br />
Chipcard reader as desktop ver-<br />
6ES7 652-0XX01-1XC0<br />
The login dialog of the SIMATIC Logon Service is activated when<br />
an application is started which is managed by SIMATIC Logon.<br />
The user receives his specific privileges after making the login,<br />
password <strong>and</strong> domain entries. The SIMATIC Logon Service dialog<br />
for logoff, user change or password edit can be called in the<br />
applications.. The SIMATIC Logon Service is required on all clients/single<br />
stations that access applications for which SIMATIC<br />
sion, V.24 connection, PS/2 power<br />
supply with 1.8 m cable, instruction<br />
manual<br />
Chipcard<br />
Chipcard for chipcard reader;<br />
1 card required per user;<br />
package with 10 chipcards<br />
6ES7 652-0XX05-1XD1<br />
Logon is used for access protection.<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
■ Options<br />
Access security by means of chipcard reader<br />
A chipcard reader can be used to check a person’s authorization<br />
to access <strong>and</strong> operate a single station or a client. This method of<br />
access security uses the chipcard as a "key" to the operator terminals.<br />
Operations are only allowed when the card is actually inserted<br />
in the reader.<br />
The unmistakable identification of access rights is required in<br />
particular for plants which have to meet validation requirements.<br />
The chipcard reader is compliant with EN 55022 Class B <strong>and</strong><br />
EN 50082-1 st<strong>and</strong>ards.<br />
The reader is connected to a serial interface (COM1 or COM2)<br />
of the operator station.<br />
2/3<br />
2
<strong>System</strong>-neutral components<br />
2 Software Update Service<br />
■ Overview<br />
<strong>Siemens</strong> offers a SIMATIC PCS 7 Software Update Service. At a<br />
charge this subscription will automatically provide you with all<br />
ServicePacks issued within a year for the SIMATIC PCS 7 software<br />
products listed in the confirmation of order / software product<br />
certificate. Delivery is to the address entered in the order.<br />
The subscription is automatically extended for a further year unless<br />
canceled no later than 3 months prior to expiration.<br />
2/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC PCS 7 Software<br />
Update Service<br />
Subscription for 1 year with automatic<br />
extension; Requirements:<br />
current software version<br />
6ES7 658-4XX00-0YL0 D)<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1
■ Overview<br />
For engineering systems (ES), operator systems (OS) <strong>and</strong><br />
SIMATIC BATCH <strong>and</strong> SIMATIC Route Control we provide a range<br />
of modern, powerful basic devices that can also be used for<br />
connecting SIMATIC PCS 7 to the IT world. These basic devices<br />
can be exp<strong>and</strong>ed for system-specific purposes, are already optimized<br />
for use as single stations, clients or servers, <strong>and</strong> come<br />
equipped with the corresponding multi-lingual version of the operating<br />
systems Microsoft Windows 2000 (German, English,<br />
French, Italian <strong>and</strong> Spanish).<br />
The basic hardware (basic PC unit) can be combined with the<br />
color monitors recommended for SIMATIC PCS 7 in the catalog<br />
"PC-based <strong>Automation</strong>" to suit the operating environment <strong>and</strong><br />
the customer’s requirements.<br />
The system test confirms that the system software of the<br />
SIMATIC PCS 7 process control system can be run on the basic<br />
hardware offered in this catalog. <strong>Siemens</strong> guarantees the compatibility<br />
of hardware <strong>and</strong> software for system configurations<br />
based on components in this catalog.<br />
The use of basic software that is not offered in this catalog is at<br />
the user’s own risk <strong>and</strong> does not qualify for free support in the<br />
event of any compatibility problems.<br />
<strong>System</strong>-neutral components<br />
ES/OS/BATCH/IT basic devices<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
Minimum features of basic devices for ES, OS <strong>and</strong><br />
SIMATIC BATCH<br />
Programming device or personal computer with:<br />
- Pentium 4 processor or higher<br />
- min. 512 Mbyte RAM<br />
- min. 40 Gbyte hard disk memory<br />
Recommended features:<br />
- Programming device or personal computer with:<br />
- Pentium 4 processor with 2 GHz <strong>and</strong> higher<br />
- 1 Gbyte RAM für server/single stations, 512 Mbyte for clients<br />
- min. 60 Gbyte hard disk memory<br />
graphics card <strong>and</strong> monitor with 1280 x 1024 resolution<br />
(min. 1024 x 768)<br />
2/5<br />
2
<strong>System</strong>-neutral components<br />
ES/OS/BATCH/IT basic devices<br />
2 Basic hardware<br />
■ Overview<br />
The basic devices available for engineering systems, operator<br />
systems, SIMATIC BATCH <strong>and</strong> SIMATIC Route Control are<br />
based on a SIMATIC Rack PC in 19“ design, which is certified<br />
with the CE marking for use in industrial <strong>and</strong> office environments.<br />
This industrial PC meets the specific requirements of the process<br />
instrumentation <strong>and</strong> control system, <strong>and</strong> has a powerful innovative<br />
Intel PC architecture. Its service-friendly all-metal housing<br />
is mechanically robust, electromagnetically resistant, <strong>and</strong><br />
specially protected from dust by filters <strong>and</strong> pressurized cooling.<br />
Reliable 24-hour continuous operation at ambient temperatures<br />
between 5 <strong>and</strong> 40°C is made possible by the use of high-grade<br />
components with high MTBF values <strong>and</strong> monitoring functions for<br />
the inner housing temperature, fan <strong>and</strong> program execution.<br />
Specially optimized versions of the st<strong>and</strong>ard device are available<br />
for operation as single stations, servers or clients. The operating<br />
system <strong>and</strong> SIMATIC PCS 7 software are delivered in<br />
preinstalled form.<br />
Single stations <strong>and</strong> servers can be connected in two ways to the<br />
Industrial Ethernet bus:<br />
through a CP 1613 communications processor for communication<br />
with max. 64 automation systems (incl. redundant systems)<br />
or<br />
through a simple LAN card (Basic Communication Ethernet for<br />
communication with max. 8 non-redundant automation systems).<br />
A FastEthernet RJ45 port is already on board in all basic devices<br />
<strong>and</strong> can be used for connecting to an OS LAN (terminal bus).<br />
2/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Design<br />
The SIMATIC Rack PC, used as the basic device for engineering<br />
systems, operator systems, SIMATIC BATCH <strong>and</strong> SIMATIC<br />
Route Control, can be installed in both a vertical <strong>and</strong> a horizontal<br />
arrangement. It has a robust <strong>and</strong> service-friendly, flush-mounting<br />
metal housing for 19" racks (4 HE) <strong>and</strong> comes with the following<br />
features:<br />
Pentium 4 motherboard with future-oriented Intel architecture<br />
based on an Intel 865G chip set<br />
Powerful AGP graphics with Dynamic Video Memory, sound<br />
(Line In, Line Out, Mic.) <strong>and</strong> FastEthernet RJ45 port integrated<br />
on board<br />
Expansion reserves provided by a total of 6 PCI slots<br />
6 slots for drives:<br />
- 3x 5.25“ slots on the front (1 occupied by DVD-ROM on client<br />
<strong>and</strong> server or by DVD±RW on single station);<br />
- 2x 3.5" slots on the inside (occupied by 1 hard disk on the<br />
client, <strong>and</strong> 2 hard disks on the server <strong>and</strong> single station)<br />
Enhanced system availability through RAID 1 with 2 EIDE hard<br />
disks on the server <strong>and</strong> single station<br />
Second serial interface for server available (COM 2)<br />
4 USB 2.0 interfaces on the back<br />
High electromagnetic compatibility (CE-certified for industrial<br />
<strong>and</strong> office environments)<br />
Dust protection by means of pressurized ventilation in conjunction<br />
with a front fan <strong>and</strong> a dust filter<br />
PC front complies with IP30 degree of protection when the<br />
front door is closed<br />
Front door can be locked to prevent unauthorized access to<br />
removable media, control elements <strong>and</strong> interfaces located at<br />
the front<br />
Easy <strong>and</strong> fast installation <strong>and</strong> maintenance of PC components:<br />
access to the front drives through a hinged front door;<br />
only 3 screws to open the device<br />
3 LED indicators on the front of the PC visualize the operating<br />
status: Power (activated), HD (access to hard disk), Status<br />
(monitoring the fan / temperature)<br />
Prepared for easy mounting with telescopic rails<br />
Easy to remove fixing bracket with h<strong>and</strong>les<br />
Card hold-down device to secure PC modules during transportation<br />
<strong>and</strong> to protect them from vibration <strong>and</strong> shock<br />
Power supply unit with temperature-controlled fan<br />
Power connector lock for the power supply cable<br />
The operating system <strong>and</strong> SIMATIC PCS 7 software are preinstalled<br />
on the basic devices. A restore DVD is supplied for<br />
quickly restoring the original status if required.
<strong>System</strong>-neutral components<br />
ES/OS/BATCH/IT basic devices<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Basic hardware<br />
■ Technical specifications<br />
Interface modules/interfaces<br />
Basic hardware for single stations, servers <strong>and</strong> clients<br />
OS-LAN interface module 10/100/1000 Mbit/s (RJ45<br />
on board)<br />
Packaging 19" rack, 4 HE, for horizontal <strong>and</strong><br />
vertical installation, prepared for<br />
easy mounting with telescopic<br />
Plant bus interface module (single<br />
station/server)<br />
rails,<br />
IL 40 S V2 BCE FastEthernet RJ45 (PCI card)<br />
19" fixing bracket fixture with h<strong>and</strong>le,<br />
easy to remove<br />
IL 40 S V2 IE CP 1613 communications processor<br />
with licence<br />
CPU<br />
Interfaces<br />
Processor base<br />
Processor<br />
Front Side Bus (FSB)<br />
Second Level Cache<br />
mPGA478<br />
Intel Pentium 4, 2.8 GHz <strong>and</strong><br />
higher<br />
800 MHz<br />
USB<br />
Serial<br />
4 x at rear (high current),<br />
Hi-Speed USB 2.0<br />
Server: 1 x COM1 <strong>and</strong> 1 x COM2<br />
(each V.24)<br />
512 Kbyte<br />
Single station/client: 1 x COM1<br />
Main memory<br />
(V.24)<br />
Type Dual/Single Channel DDR 400 Parallel 1 x LPT1 (25-pin, EPP <strong>and</strong> ECP)<br />
SDRAM (PC 3200)<br />
Audio 1 x Line In; 1 x Line Out;<br />
Maximum configuration 4 memory bases in total (exp<strong>and</strong>-<br />
1 x Micro In<br />
able to 4 Gbyte)<br />
VGA 1 x<br />
St<strong>and</strong>ard configuration Single station/server: 1 Gbyte (2 x<br />
512 Mbyte)<br />
Keyboard 1 x PS/2<br />
Client: 512 Mbyte (2 x 256 Mbyte)<br />
Mouse 1 x PS/2<br />
Motherboard slots 6 x PCI (long), 1 x AGP 8x<br />
Monitoring functions<br />
Slots for drives<br />
Temperature Overshooting of the permissible<br />
operating temperature<br />
On the front 1 x 3.5“ (occupied by diskette<br />
drive)<br />
Fan Speed monitoring<br />
3 x 5.25“ (1 occupied by DVD-<br />
ROM on client <strong>and</strong> server or by<br />
DVD±RW on single station)<br />
Watchdog Monitoring the program flow<br />
(monitoring time can be parameterized<br />
per software)<br />
On the inside 2 x 3.5“ (2 occupied by HDD on<br />
server/single station; 1 occupied<br />
by HDD on client)<br />
Front LEDs Power (PC activated)<br />
HD (access to hard disk)<br />
Status (monitoring the fan / tem-<br />
Hard disk memory<br />
perature)<br />
Single station/server EIDE-RAID 1 (mirror) with two<br />
Ambient conditions<br />
120 Gbyte hard disks, 7200 rpm Degree of protection according to IP20;<br />
Client 80 Gbyte EIDE hard disk,<br />
EN 60529<br />
front IP30 (with closed front door)<br />
7200 rpm<br />
Protection class Protection class I compliant with<br />
Interchangeable drives Diskette drive<br />
IEC 61140<br />
Single station: DVD writer<br />
(DVD±RW), 16/8/4x (DVD media),<br />
48/24/48x (CD media), incl.<br />
Ambient temperature during operation<br />
5...40 °C for full expansion<br />
Note: Restrictions in use of<br />
DVD-ROM/CD-RW or DVD±RW<br />
burning software<br />
Humidity 5...80% at 25 °C (no condensa-<br />
Server/Client: DVD-ROM (16x<br />
tion)<br />
48x)<br />
Vibration during operation compli- 20...200 Hz: 2 m/s2 (approx.<br />
Graphics card 2D/3D graphics controller on ant with IEC 60068-2-6<br />
0.2 g)<br />
board, integrated in Intel 865G<br />
Note: Restrictions in use of<br />
chip set, on AGP bus with<br />
DVD-ROM/CD-RW or DVD±RW<br />
Dynamic Video Memory, 1600 x<br />
<strong>and</strong> interchangeable frames<br />
1200 pixel at 100 Hz image<br />
refresh rate <strong>and</strong> 64 k colors<br />
Shock load during operation compliant<br />
with IEC 60068-2-27<br />
9.8 m/s2, 20 ms (approx. 1.0 g)<br />
Note: Restrictions in use of<br />
Mouse Optical mouse<br />
DVD-ROM/CD-RW or DVD±RW<br />
Power supply<br />
Operating system<br />
300 W 120/230 V AC, 50/60 Hz,<br />
autorange<br />
<strong>and</strong> interchangeable frames<br />
Single station/client Microsoft Windows 2000 Professional<br />
MUI, preinstalled <strong>and</strong> on<br />
restore DVD,<br />
switch-selectable: German,<br />
English, French, Italian, Spanish<br />
Server Microsoft Windows 2000 Professional<br />
MUI, incl. 5 CAL (Client<br />
Access Licences), preinstalled<br />
<strong>and</strong> on restore DVD,<br />
switch-selectable: German,<br />
English, French, Italian, Spanish<br />
2/7<br />
2
2<br />
<strong>System</strong>-neutral components<br />
ES/OS/BATCH/IT basic devices<br />
Basic hardware<br />
Electromagnetic compatibility (EMC)<br />
Emitted interference EN 55022 Class B, FCC Class A<br />
Immunity to conducted interference ± 2 kV (IEC 61000-4-4, burst)<br />
on the supply lines<br />
± 1 kV (IEC 61000-4-5, surge<br />
symm.)<br />
± 2 kV (IEC 61000-4-5, surge<br />
unsymm.)<br />
Immunity to interference on signal ± 1 kV (IEC 61000-4-4, burst,<br />
lines<br />
length 30 m)<br />
± 2 kV (IEC 61000-4-5, surge<br />
unsymm., length > 30 m)<br />
Immunity to static discharge ± 4 kV, contact discharge<br />
(IEC 61000-4-2)<br />
± 8 kV, air discharge<br />
(IEC 61000-4-2)<br />
Immunity to high-frequency immis- 10 V/m 80% AM; 80 MHz to<br />
sion<br />
1 GHz (IEC 61000-4-3);<br />
10 V/m 50% ED; 900 MHz <strong>and</strong><br />
1.89 GHz (IEC 61000-4-3)<br />
10 V, 9 kHz to 80 MHz<br />
(IEC 61000-4-6)<br />
Immunity to magnetic fields 30 A/m, 50/60 Hz (IEC 61000-4-8)<br />
Approvals<br />
Safety directives IEC 60950-1; UL 60950; CSA<br />
Approvals UL 60950, cULus<br />
CE marking Use in the office <strong>and</strong> industrial<br />
sectors<br />
Emitted intereference: EN 61000-<br />
6-3<br />
Immunity to interference:<br />
EN 61000-6-2<br />
Dimensions <strong>and</strong> weights<br />
Overall dimensions in mm<br />
430 x 177 x 444<br />
(WxHxD)<br />
Weight approx. 19 kg<br />
2/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Accessories<br />
Keyboards<br />
The PCS 7 basic devices for ES/OS/BATCH/IT are supplied with<br />
a keyboard. The TK 200 keyboard with PS/2 connection is available<br />
as an additional <strong>and</strong> expansion component. It is particularly<br />
well suited for process operation with SIMATIC PCS 7 <strong>and</strong><br />
comes with German or international key assignment.<br />
Image & Partition Creator<br />
"SIMATIC PC/PG Image & Partition Creator" is available as an optional<br />
utility software package for creating regular backups of a<br />
hard disk’s contents <strong>and</strong> for quickly restoring a saved software<br />
status. Existing software installations are easily duplicated on<br />
devices with the same features <strong>and</strong> the same purpose. It is<br />
therefore easier <strong>and</strong> faster to carry out plant expansions <strong>and</strong> to<br />
completely replace a basic device during servicing. The tool can<br />
also be used to create, change <strong>and</strong> delete hard disk partitions.<br />
SIMATIC PC/PG Image & Partition Creator supports:<br />
the saving of hard disk images on a second hard disk, an internal<br />
CD-RW/DVD±RW or an external hard disk drive connected<br />
by USB, <strong>and</strong> the restoring of existing images on the<br />
hard disk<br />
the menu-prompted creation of a LAN connection to a server<br />
drive or to a PC that is directly connected by crosslink cable
■ Selection <strong>and</strong> Ordering Data<br />
Single station<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Video Memory, DVD±RW IDE,<br />
optical mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
Order No.<br />
PCS 7 ES/OS IL 40 S V2 BCE<br />
Connection to plant bus through<br />
Basic Communication Ethernet<br />
(BCE) with FastEthernet RJ45<br />
network card (PCI card)<br />
6ES7 650-0GC06-0YX0 D)<br />
PCS 7 ES/OS IL 40 S V2 IE<br />
Connection to plant bus through<br />
Industrial Ethernet with CP 1613<br />
communications processor<br />
Server<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Video Memory, DVD-ROM IDE,<br />
optical mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Server MUI (German,<br />
English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
6ES7 650-0GC16-0YX0 D)<br />
PCS 7 OS Server IL 40 S V2<br />
BCE<br />
Connection to plant bus through<br />
Basic Communication Ethernet<br />
(BCE) with FastEthernet RJ45<br />
network card (PCI card)<br />
6ES7 650-0GE06-0YX0 D)<br />
PCS 7 OS Server IL 40 S V2 IE<br />
Connection to plant bus through<br />
Industrial Ethernet with CP 1613<br />
communications processor<br />
Client<br />
6ES7 650-0GE16-0YX0 D)<br />
PCS 7 OS Client IL 40 S V2<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
512 Mbyte RAM (2 x 256 Mbyte),<br />
sound, EIDE hard disk of<br />
80 Gbyte, graphics controller on<br />
board with Dynamic Video Memory,<br />
DVD-ROM IDE, optical<br />
mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
6ES7 650-0GD06-0YX0 D)<br />
<strong>System</strong>-neutral components<br />
ES/OS/BATCH/IT basic devices<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Basic hardware<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Additional <strong>and</strong> expansion components<br />
Utility software<br />
SIMATIC PC/PG Image & Partition<br />
Creator<br />
Software for creating hard disk<br />
images <strong>and</strong> for configurating hard<br />
disk partitions<br />
6ES7 648-6AA02-0YX0 B)<br />
Memory modules for exp<strong>and</strong>ing<br />
the main memory<br />
Memory expansion kit 512<br />
Mbyte (Dual Channel) for SI-<br />
MATIC Rack PC IL 40 S V2 (2 x<br />
256 Mbyte DDR SDRAM)<br />
Memory expansion kit 1 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x<br />
512 Mbyte DDR SDRAM)<br />
Memory expansion kit 2 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x 1 Gbyte<br />
DDR SDRAM)<br />
6ES7 648-2AD30-0FB0 B)<br />
6ES7 648-2AD40-0FB0 B)<br />
6ES7 648-2AD50-0FB0 B)<br />
TK 200 keyboard (PS/2 connection)<br />
German key assignment 6GF6 710-1AA<br />
International key assignment 6GF6 710-1BA<br />
SIMATIC PC keyboard (USB<br />
connection)<br />
International key assignment 6ES7 648-0CB00-0YA0<br />
3-m power cable for Rack PC 1)<br />
For Great Britain 6ES7 900-0BA00-0XA0<br />
For Switzerl<strong>and</strong> 6ES7 900-0CA00-0XA0<br />
For USA 6ES7 900-0DA00-0XA0<br />
For Italy 6ES7 900-0EA00-0XA0<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
1) The PCS 7 systems are delivered as st<strong>and</strong>ard with a "European power<br />
cable". The country-specific versions listed above are required for some<br />
countries.<br />
2/9<br />
2
<strong>System</strong>-neutral components<br />
ES/OS/BATCH/IT basic devices<br />
2 Multi-VGA graphic cards<br />
■ Overview<br />
The ES/OS/BATCH/IT basic devices available for SIMATIC<br />
PCS 7 are supplied as st<strong>and</strong>ard with a graphics interface for<br />
controlling a process monitor. The Multi-VGA graphics cards<br />
"2 Screens" <strong>and</strong> "4 Screens" are available for multichannel operation<br />
with 2 or as many as 4 process monitors.<br />
With a special Multi-VGA graphics card, the visualization of a<br />
project/subproject during engineering or of a plant/unit in process<br />
mode can be shared among as many as 4 process monitors<br />
per operator terminal using various views. These<br />
project/plant sections can all be operated using just one keyboard<br />
<strong>and</strong> one mouse. The efficiency, user-friendliness <strong>and</strong> ergonomics<br />
of engineering <strong>and</strong> process control can thus be<br />
greatly improved compared to the single-channel mode of operation.<br />
■ Technical specifications<br />
Multi-VGA graphics cards<br />
Memory 32 Mbyte DDRAM per output<br />
Graphics card "2 Screens" 2 x 32 Mbyte<br />
Graphics card "4 Screens" 4 x 32 Mbyte<br />
Clock frequency 360 MHz integrated RAMDAC<br />
Max. analog resolution per channel 2048 x 1536 at 24 bpp <strong>and</strong> 85 Hz<br />
Max. digital resolution per channel<br />
Electromagnetic compatibility<br />
(EMC)<br />
1280 x 1024<br />
(1600 x 1200 is possible if supported<br />
by TFT/LCD display)<br />
Emitted interference EN 55022 Class B<br />
Immunity to interference EN 50082<br />
Slot assignment in operator station 1 PCI slot<br />
2/10<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Multi-VGA Graphics Card<br />
"2 Screens“<br />
for operating 2 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Dual graphics card, driver CD,<br />
manual, 1 dual DVI cable for<br />
2 digital outputs, 2 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE0 B)<br />
Multi-VGA Graphics Card<br />
"4 Screens“<br />
for operating 4 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Quad graphics card, driver CD,<br />
manual, 2 dual DVI cables for<br />
4 digital outputs, 4 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE1 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
Detailed technical data can be found in<br />
the catalog "PC-based <strong>Automation</strong>" or<br />
the Mall/CA 01 at "<strong>Automation</strong> systems - Monitors, printers <strong>and</strong><br />
input devices for industry"<br />
<strong>System</strong>-neutral components<br />
ES/OS/BATCH/IT basic devices<br />
Operating devices/monitors<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Operating devices<br />
Process Monitors<br />
A mouse <strong>and</strong> keyboard are the st<strong>and</strong>ard operating devices (see<br />
Industrial Monitors<br />
in "Basic hardware"). Additional operating devices such as a fin- LCD Color Monitor SCD 1898-I<br />
gerprint mouse, trackball, Ex PC operator control unit <strong>and</strong><br />
TS-Mobic <strong>and</strong> be found in the ST PCS 7.A Add-on Catalog .<br />
46 cm (18“) picture diagonal,<br />
desktop model, line frequency<br />
Process monitors<br />
30...97 kHz, degree of protection<br />
IP20, power supply unit 230 V AC<br />
Depending on the ambient conditions we recommend the<br />
1.8 m cable 6AV8 101-2DA00-0BA0<br />
SCD 1898-I (LCD color) or SCM 2196-I (CRT color) industrial<br />
monitors as well as the SCM 2197 (CRT color) office monitor, all<br />
from <strong>Siemens</strong>.<br />
5 m cable<br />
10 m cable<br />
6AV8 101-2DA00-0DA0<br />
6AV8 101-2DA00-0FA0<br />
The CRT monitors provide a top-quality picture throughout their 20 m cable 6AV8 101-2DA00-0JA0<br />
long service life.<br />
SCM 2196-I CRT Color Monitor 6GF6 100-1BA<br />
Outst<strong>and</strong>ing characteristics of the SCD 1898-I LCD monitor include:<br />
7 Long service life<br />
54 cm (21“) picture diameter,<br />
desktop model 115/230 V AC,<br />
line frequency up to 96 kHz,<br />
degree of protection IP30,<br />
7 Clear, high-contrast <strong>and</strong> flicker-free picture<br />
with video cable (Sub-D, BNC)<br />
7 Exact picture geometry<br />
7 Small space requirement <strong>and</strong> low weight<br />
7 Low energy consumption <strong>and</strong> heat development<br />
7 High resistance to shock <strong>and</strong> vibration<br />
7 High electromagnetic compatibility<br />
P95 Supporting Foot for<br />
SCM 2196-I<br />
Office Monitors<br />
SCM 2197 CRT Color Monitor<br />
54 cm (21“), picture diagonal<br />
degree of protection IP20, with<br />
6GF6 180-1AH<br />
6GF6 100-1PC<br />
7 No X-radiation<br />
power connection cable <strong>and</strong><br />
video cable with 15-pin/3-row<br />
Monitors suitable for installing in desks, 19" racks or switchgear<br />
cabinets can be found in:<br />
the catalog "PC-based <strong>Automation</strong>" or<br />
the A&D Mall/CA 01 at "<strong>Automation</strong> systems - Monitors, printers<br />
<strong>and</strong> input devices for industry"<br />
■ Technical specifications<br />
Sub-D connector<br />
Monitors SCD 1898-I SCM 2196-I SCM 2197<br />
Monitor 18.1“ (45 cm) 21“ (54 cm) CRT 21“ (54 cm) CRT<br />
TFT color monitor,<br />
1280 x 1024<br />
pixels<br />
color monitor color monitor<br />
Line frequency<br />
30..0.97 kHz 30..00.96 kHz 30..00.96 kHz<br />
Image refresh<br />
rate<br />
50..00.100 Hz 50..000.120 Hz 50..000.160 Hz<br />
Dimensions<br />
(WxHxD) in<br />
mm<br />
465 x 444 x 91 499 x 480 x 520 504 x 508 x 492<br />
Degree of protection<br />
IP20 IP30 IP20<br />
Weight approx. 10 kg approx. 30.5 kg approx. 26 kg<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/11<br />
2
<strong>System</strong>-neutral components<br />
ES/OS/BATCH/IT basic devices<br />
2 Operating system<br />
■ Overview<br />
Operating system upgrade<br />
When the SIMATIC PCS 7 is updated to Version 6.0, the NT workstation/server<br />
on PCs with the Windows NT operating system<br />
has to be upgraded to Windows 2000.<br />
The necessary upgrade packages can be ordered as follows:<br />
By fax: +49 821 804 3006<br />
By e-mail: dominikus.besserer@fujitsu-siemens.com<br />
<strong>Siemens</strong> Ordering <strong>System</strong> (Org ID: 13000054)<br />
2/12<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Upgrade from Windows NT<br />
Workstation to Windows 2000<br />
Professional operating system<br />
SB Windows 2000 Professional<br />
incl. SP4, German, pack of 3<br />
SB Windows 2000 Professional<br />
incl. SP4, German, pack of 1<br />
SB Windows 2000 Professional<br />
incl. SP4, English, pack of 3<br />
Operating system<br />
Windows 2000 Server<br />
SB Windows 2000 Server incl.<br />
SP4, German (for up to 5 clients)<br />
SB Windows 2000 Server incl.<br />
SP4, English (for up to 5 clients)<br />
5-client access license (CAL) for<br />
SB Windows 2000 Server, German<br />
5-client access license (CAL) for<br />
SB Windows 2000 Server, English<br />
MSO:B23-03883/KIT<br />
MSO:B23-03882/KIT<br />
MSO:B23-03877/KIT<br />
MSO:C11-03150/KIT<br />
MSO:C11-03148/KIT<br />
MSO:C78-00688/KIT<br />
MSO:C78-00686/KIT
SIMATIC PCS 7 BOX<br />
3/2 SIMATIC PCS 7 BOX<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
3<br />
SIMATIC PCS 7 BOX<br />
SIMATIC PCS 7 BOX<br />
■ Overview<br />
SIMATIC PCS 7 BOX extends the product spectrum of SIMATIC<br />
PCS 7 by adding a cost-effective entrance-level product that<br />
unites SIMATIC PCS 7 functionality for automation, operation, visualization<br />
<strong>and</strong> engineering in one compact PC system. In conjunction<br />
with the distributed I/Os on the PROFIBUS, SIMATIC<br />
PCS 7 BOX represents a complete SIMATIC PCS 7 process control<br />
system.<br />
■ Application<br />
SIMATIC PCS 7 BOX can be used just as readily for small applications<br />
in production or self-contained subprocesses (Package<br />
Units) as for the automation of a laboratory or test center. As a<br />
fully fledged member of the SIMATIC PCS 7 range, SIMATIC<br />
PCS 7 BOX works with the st<strong>and</strong>ard SIMATIC PCS 7 system software,<br />
is scalable <strong>and</strong> can be exp<strong>and</strong>ed without disruption of<br />
compatibility. The quantity framework is limited to<br />
2000 POs/64 K variables.<br />
SIMATIC PCS 7 BOX can be operated in st<strong>and</strong>-alone mode as<br />
well as in a plant network. Operation in a plant network is intended<br />
only as a single-station system; SIMATIC PCS 7 BOX is<br />
not suitable for server operation.<br />
A plant created with SIMATIC PCS 7 BOX can be exp<strong>and</strong>ed at<br />
any time with additional SIMATIC PCS 7 hardware <strong>and</strong> software<br />
components. And SIMATIC PCS 7 BOX can be integrated just a<br />
easily in existing SIMATIC PCS 7 plants.<br />
However, SIMATIC PCS 7 BOX has not yet been released for<br />
batch process automation with SIMATIC BATCH.<br />
3/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Design<br />
SIMATIC PCS 7 BOX in st<strong>and</strong>-alone operation<br />
SIMATIC PCS 7 BOX integrated in the SIMATIC PCS 7 plant network<br />
SIMATIC PCS 7 BOX is based on a Box PC 620 industrial PC with<br />
an installed CPU WinAC Slot 416 V3.4; this means that the often<br />
distributed PLS functionality for automation, operation, visualization<br />
<strong>and</strong> engineering can be brought together in a single system.<br />
SIMATIC PCS 7 BOX uses st<strong>and</strong>ard system software from SI-<br />
MATIC PCS 7 V6.0 Service Pack 3 or higher <strong>and</strong> is integrated in<br />
SIMATIC PCS 7 <strong>Engineering</strong> <strong>and</strong> in the PCS 7 Project Wizard.<br />
This ensures full compatibility with SIMATC PCS 7 V6.0.<br />
Using the CPU WinAC Slot 416 means that the automation program<br />
runs in the slot CPU fully independent of the industrial PC<br />
<strong>and</strong> the Windows operating system. The PC-independent power<br />
supply to the slot CPU is arranged through a separate power<br />
supply extension board. Software errors on the PC side have no<br />
effect on the slot CPU. Like voltage failures or rebooting the PC<br />
they have no impact on the execution of the automation program<br />
in the slot CPU.<br />
SIMATIC PCS 7 BOX can be configured by using either the engineering<br />
software integrated in the system or a central engineering<br />
system. OS modifications through the central engineering<br />
system are also possible online, but the online loading of OS<br />
modifications on the SIMATIC PCS 7 BOX is not yet possible.
SIMATIC PCS 7 BOX supports not only the distributed I/O devices<br />
of the ET 200 range with an extensive selection of cost-effective<br />
signal <strong>and</strong> function modules but also the connection of<br />
intelligent field/process devices on PROFIBUS PA. The process<br />
I/Os are connected through the two PROFIBUS DP ports of the<br />
slot CPU. As SIMATIC PDM can only access field devices on the<br />
PROFIBUS DP through the onboard communications processor<br />
CP 5611, an additional cross connection between the DP port<br />
<strong>and</strong> CP 5611 is required to use SIMATIC PDM . A plug required<br />
for this purpose is supplied with the SIMATIC PCS 7 BOX.<br />
Configuration modifications during operation (CiR) are not yet<br />
supported by the current CPU WinAC Slot 416. However, plans<br />
to include this functionality in future WinAC Slot CPUs are currently<br />
in the pipeline.<br />
In a plant network with other SIMATIC PCS 7 system components<br />
such as AS, OS, ES or BATCH <strong>and</strong> MES applications, bus<br />
communication is implemented through the Ethernet interface<br />
integrated in the SIMATIC PCS 7 BOX. An additional CP 1512 is<br />
required (see "Accessories") for connecting to the SIMATIC<br />
PCS 7 terminal bus (OS-LAN).<br />
SIMATIC PCS 7 BOX is available in the form of two product bundles:<br />
as a preinstalled SIMATIC PCS 7 complete system with AS, ES<br />
<strong>and</strong> OS functionality for up to 250 process objects (POs) / 8 K<br />
OS variables<br />
as a preinstalled SIMATIC PCS 7 runtime system with AS <strong>and</strong><br />
OS functionality for up to 250 process objects (POs) / 8 K OS<br />
variables<br />
These can be further exp<strong>and</strong>ed using the following add-on/expansion<br />
components (see also Chapter "ES/OS/Batch/IT basic<br />
devices" <strong>and</strong> the catalog "PC-based <strong>Automation</strong>"):<br />
SIMATIC PCS 7 Power Packs for up to 2,000 POs / 64 K OS<br />
variables<br />
SIMATIC PDM Package for PCS 7<br />
CP 1512 for connecting to the OS-LAN (SIMATIC PCS 7 terminal<br />
bus) of a SIMATIC PCS 7 plant network<br />
TK 200 st<strong>and</strong>ard keyboard<br />
Display <strong>and</strong> CRT monitors for office <strong>and</strong> industrial environments<br />
SITOP power supply 230 V AC / 24 V DC<br />
SITOP power DC-UPS module 15 A with RS 232 interface<br />
DC-UPS software for the further processing of signals sent<br />
from the DC-UPS module using the RS 232 interface on the PC<br />
(state visualization <strong>and</strong> the definition of reactions to different<br />
operating states of the DC-UPS module), can be used with<br />
Windows NT, 2000 <strong>and</strong> XP; freeware for downloading at<br />
http://www.siemens.com/sitop<br />
SITOP power battery module 24 V DC /20 A/7 Ah for DC-UPS<br />
module 15 A<br />
■ Technical specifications<br />
SIMATIC PCS 7 BOX<br />
SIMATIC PCS 7 BOX<br />
Industrial PC: SIMATIC Box PC 620<br />
CPU Intel Pentium III 1.26 GHz<br />
Main memory 1 Gbyte<br />
Second Level Cache 512 Kbyte<br />
Hard disk memory 80 Gbyte<br />
Diskette drive 1.44 Mbyte<br />
DVD-ROM/CD-RW Combo drive 8/8/24x<br />
Graphics UXGA LCD controller on AGP<br />
bus, 1280 x 1024 at 85 Hz<br />
Ethernet integrated Ethernet interface<br />
10/100 Mbit/s (RJ45)<br />
PROFIBUS DP 12 Mbit/s (floating, CP 5611-compatible)<br />
USB 2 terminals (high current)<br />
Expansions 1 CardBus slot for PCMCIA Typ III<br />
PC card<br />
Power supply 24 V DC<br />
Operating system Microsoft Windows 2000 Professional<br />
<strong>Automation</strong>: slot PLC module<br />
CPU WinAC Slot 416 V3.4<br />
Main memory 1.6 + 1.6 Mbyte (integrated)<br />
Loading memory 256 Kbyte<br />
Memory card 2 Mbyte RAM (installed)<br />
Processing times Binary comm<strong>and</strong>: 0.08 µs,<br />
IEEE floating point: 0.48 µs<br />
PROFIBUS DP PROFIBUS DP <strong>and</strong><br />
PROFIBUS DP/MPI interface<br />
onboard<br />
Connectable distributed I/Os ET 200M, ET 200iS, ET 200S,<br />
PROFIBUS DP st<strong>and</strong>ard slaves,<br />
PROFIBUS PA devices (using<br />
DP/PA link or DP-PA coupler)<br />
Dimensions PCI plug-in card (3/4 long)<br />
Power supply Power supply extension board<br />
independent of PC;<br />
external power supply 24 V DC<br />
<strong>and</strong> battery buffer<br />
Operation <strong>and</strong> visualization<br />
Software PCS 7 OS Software Single Station<br />
V6.0 (preinstalled)<br />
Licenses 250 POs/RT 8K variables<br />
(extendable to 2000 POs/RT 64K<br />
per PowerPack)<br />
<strong>Engineering</strong><br />
Software PCS 7 <strong>Engineering</strong> Software V6.0<br />
(preinstalled)<br />
Licenses AS/OS for 250 POs/RC 8K<br />
(extendable to 2000 POs/RC 64K<br />
per Power Pack)<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
3/3<br />
3
3<br />
SIMATIC PCS 7 BOX<br />
SIMATIC PCS 7 BOX<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC PCS 7 BOX<br />
Complete system (ES, OS <strong>and</strong><br />
AS), assembled <strong>and</strong> preinstalled,<br />
comprising:<br />
SIMATIC Box PC 620, 24 V DC,<br />
with WinAC Slot 416<br />
Memory card 2 Mbyte<br />
WinAC power supply extension<br />
board<br />
Backup battery<br />
Mouse<br />
PCS 7 <strong>Engineering</strong> Software<br />
V6.0 for AS/OS, 250 POs/RC 8K,<br />
trilingual (German, English,<br />
French)<br />
PCS 7 Library Blocks V6.0, Runtime<br />
License<br />
trilingual (German, English,<br />
French)<br />
6ES7 650-2HA06-0YX0 G)<br />
SIMATIC PCS 7 BOX<br />
Runtime system (OS <strong>and</strong> AS),<br />
assembled <strong>and</strong> preinstalled,<br />
comprising:<br />
SIMATIC Box PC 620, 24 V DC,<br />
with WinAC Slot 416<br />
Memory card 2 Mbyte<br />
WinAC power supply extension<br />
board<br />
Backup battery<br />
Mouse<br />
PCS 7 OS Software Single Station<br />
V6.0, 250 POs/RT 8K,<br />
trilingual (German, English,<br />
French)<br />
PCS 7 Library Blocks V6.0, Runtime<br />
License<br />
trilingual (German, English,<br />
French)<br />
Additional <strong>and</strong> Expansion Components<br />
SIMATIC PCS 7 Power Packs<br />
6ES7 650-2HB06-0YX0 G)<br />
PCS 7 <strong>Engineering</strong> Power Pack<br />
AS/OS<br />
for exp<strong>and</strong>ing the engineering<br />
software for AS/OS<br />
from 250 POs/RC 8 K to<br />
2,000 POs/RC 64 K<br />
Type of delivery: Certificate of license<br />
<strong>and</strong> authorization diskette<br />
6ES7 658-5AB06-0YD0<br />
PCS 7 OS Software Single Station<br />
Power Pack V6.0<br />
for exp<strong>and</strong>ing the OS Software<br />
Single Station<br />
from 250 POs/RC 8 K to<br />
2,000 POs/RC 64 K<br />
Type of delivery: Certificate of license<br />
<strong>and</strong> authorization diskette<br />
6ES7 658-2AB06-0YD0<br />
3/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data<br />
SIMATIC PDM<br />
Order No.<br />
PDM Starter Package V5.2 for<br />
SIMATIC PCS 7<br />
Preferred version for<br />
SIMATIC PCS 7, in 5 languages<br />
(German, English, French, Italian<br />
<strong>and</strong> Spanish), with:<br />
Basic software for SIMATIC PDM<br />
(incl. communication through<br />
PROFIBUS DP/PA, HART modem<br />
<strong>and</strong> RS 232)<br />
Integration in STEP 7 / PCS 7<br />
Routing through S7-400<br />
128 TAGs<br />
SIMATIC PDM documentation<br />
TAG options in form of Power<br />
Packs <strong>and</strong> supplementary software,<br />
see the chapter "ES Software<br />
SIMATIC PDM", section<br />
"PDM Package for PCS 7"<br />
6ES7 658-3PX05-0YC0 C)<br />
Connection to OS-LAN<br />
(SIMATIC PCS 7 terminal bus)<br />
CP 1512<br />
6GK1 151-2AA00<br />
PC card for CardBus slot, for connecting<br />
the SIMATIC PCS 7 BOX<br />
to Industrial Ethernet<br />
(10/100 Mbit/s), incl. RJ45 connection<br />
TK 200 keyboard (PS/2 connection)<br />
German key assignment 6GF6 710-1AA<br />
International key assignment 6GF6 710-1BA<br />
SIMATIC PC keyboard<br />
(USB connection)<br />
International key assignment 6ES7 648-0CB00-0YA0<br />
Power supply 230 V AC /<br />
24 V DC<br />
Power supply SITOP power 10 6EP1 334-2AA00<br />
stabilized load power supply, industry<br />
version,<br />
input: 120/230 V AC, output:<br />
24 V DC/10 A<br />
SITOP power DC-UPS module<br />
24 V DC/15 A 1)<br />
6EP 1931-2EC31<br />
with RS 232 interface <strong>and</strong><br />
charging unit for 24 V lead-acid<br />
battery<br />
input: 24 V DC/16 A, output 24 V<br />
DC/15 A<br />
SITOP power battery module 6EP1 935-6ME21<br />
24 V DC /20 A/7 Ah<br />
for DC-UPS module 15 A<br />
1) Add-on DC-UPS software<br />
(can be used with Windows<br />
NT, 2000 <strong>and</strong> XP) for further<br />
processing of signals sent<br />
from the DC-UPS module<br />
using the RS 232 interface<br />
on the PC; avaialable as<br />
freeware for downloading at<br />
http://www.siemens.de/sitop<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
G) Subject to export regulations: AL: N, ECCN: 5D002ENC3
<strong>Engineering</strong> <strong>System</strong><br />
4/2 Introduction<br />
4/3 ES hardware<br />
4/4 ES software<br />
4/4 Introduction<br />
4/5 <strong>Engineering</strong> st<strong>and</strong>ard software<br />
4/8 <strong>Engineering</strong> H systems<br />
4/8 Version cross checker<br />
4/9 Import/export assistant<br />
4/10 <strong>Engineering</strong> Process Safety<br />
4/10 Introduction<br />
4/11 <strong>Engineering</strong> F/FH systems<br />
4/12 SIMATIC safety matrix<br />
4/14 SIMATIC Route Control<br />
4/14 SIMATIC Route Control<br />
<strong>Engineering</strong><br />
4/15 ES software SIMATIC PDM<br />
4/15 Introduction<br />
4/17 SIMATIC PDM package for PCS 7<br />
4/18 SIMATIC PDM st<strong>and</strong>-alone version<br />
4/20 Supplementary ES software<br />
4/20 Controller optimization<br />
4/20 Simulation with S7-PLCSIM<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
4<br />
<strong>Engineering</strong> system<br />
Introduction<br />
■ Overview<br />
The SIMATIC PCS 7 <strong>Engineering</strong> <strong>System</strong> contains tools which<br />
are compatible with all <strong>Siemens</strong> system components <strong>and</strong> can be<br />
used for:<br />
Hardware <strong>and</strong> field devices<br />
Communication networks<br />
Continuous <strong>and</strong> sequential process operations<br />
Operation <strong>and</strong> monitoring strategies<br />
SIMATIC BATCH <strong>and</strong> SIMATIC Route Control.<br />
These combine the engineering of st<strong>and</strong>ard automation <strong>and</strong> the<br />
configuration of consistent safety functions for safe, fault-tolerant<br />
<strong>and</strong> high-availability process applications.<br />
Technologists as well as process <strong>and</strong> production engineers can<br />
plan <strong>and</strong> configure in the environment they are familiar with by<br />
utilizing the <strong>Engineering</strong> Toolset designed for technological<br />
needs <strong>and</strong> the predefined blocks <strong>and</strong> plans.<br />
4/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Function<br />
Typical automation components such as motors, valves <strong>and</strong> PID<br />
controllers are already saved as st<strong>and</strong>ardized software objects<br />
(measuring point types) in a control engineering library <strong>and</strong><br />
need only be integrated in the process operations <strong>and</strong> graphically<br />
connected. This is easy <strong>and</strong> quick to accomplish even by<br />
technologists without any programming experience. When image<br />
objects are connected, the associated OS variables are<br />
saved (together with the associated blocks where applicable) in<br />
the block list.<br />
The uniform data base for the engineering systems ensures that<br />
data which has been entered once is available system-wide.<br />
All project modifications associated with the automation systems,<br />
the operator systems <strong>and</strong> SIMATIC BATCH can be compiled<br />
<strong>and</strong> loaded in one step. The engineering system automatically<br />
ensures the correct sequence. A central dialog displays<br />
<strong>and</strong> controls the operation.<br />
Short turnaround times result in short waiting times for the commissioning<br />
engineer <strong>and</strong> have a positive impact on the commissioning<br />
costs. Changes to the configuration can be loaded online<br />
into the system components.<br />
The engineering system supports the implementation of large<br />
projects <strong>and</strong> the related processing of bulk data by providing<br />
appropriate functions such as:<br />
Plant hierarchy (plant view)<br />
Project library for measuring point types as well as the import<br />
<strong>and</strong> export of measuring points (process object view)<br />
Multi-project engineering<br />
Branch & merge<br />
Extended rename<br />
Version cross-checker<br />
Import/export assistant<br />
SFC type
■ Overview<br />
The central engineering system of the SIMATIC PCS 7 process<br />
control system is based on the same hardware as the OS single<br />
station of the operator system. This is characterized by powerful<br />
PC technology that can be used together with the Windows 2000<br />
operating system in the office as well as industrial environments<br />
<strong>and</strong> provides an optimum basis for engineering. For more userfriendliness,<br />
the operating range can be extended by connecting<br />
up as many as 4 process monitors through a special<br />
Multi-VGA graphics card.<br />
ES/OS single station<br />
The ES/OS single station is available as the st<strong>and</strong>ard item of<br />
hardware for engineering stations. It is based on the SIMATIC<br />
Rack PC IL 40 S for installation in 19“ rack systems. Two<br />
versions are available <strong>and</strong> differ in the way they communicate<br />
with the plant bus:<br />
PCS 7 ES/OS IL 40 S V2 BCE<br />
Communication through Basic Communication Ethernet<br />
(BCE) for max. 8 stations<br />
PCS 7 ES/OS IL 40 S V2 IE<br />
Communication through CP 1613<br />
A FastEthernet RJ45 port is already on board <strong>and</strong> can be used<br />
for connecting to an OS LAN (terminal bus).<br />
The ES/OS single station is delivered complete with the Windows<br />
2000 Professional MUI <strong>and</strong> a mouse. The keyboard <strong>and</strong> monitor<br />
have to be ordered separately.<br />
Options/expansions<br />
A Multi-VGA card can be added to the engineering system. It enables<br />
the connection of 2 or 4 monitors per operator terminal.<br />
■ Technical specifications<br />
Detailed technical data for single stations are provided in table<br />
form in the chapter "ES/OS/BATCH/IT basic devices".<br />
<strong>Engineering</strong> system<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
Monitors, refer to chapter "ES/OS/BATCH/IT basic devices“<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
ES hardware<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Basic hardware for ES/OS Single Station, SIMATIC PC in rack<br />
of 19“ design, Pentium 4 with 2.8 GHz <strong>and</strong> more, 1 Gbyte<br />
RAM (2 x 512 Mbyte), sound, EIDE-RAID 1 with 2 hard disks of<br />
120 Gbyte, graphics controller on board with Dynamic Video<br />
Memory, DVD±RW IDE, optical mouse,<br />
FastEthernet RJ45 on board for connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong> printer,<br />
Windows 2000 Professional MUI (German, English, French,<br />
Italian, Spanish);<br />
SIMATIC PCS 7 preinstalled <strong>and</strong> on restore DVD<br />
PCS 7 ES/OS IL 40 S V2 BCE<br />
Connection to system bus<br />
through Basic Communication<br />
Ethernet (BCE) with FastEthernet<br />
RJ45 network card (PCI card)<br />
6ES7 650-0GC06-0YX0 D)<br />
PCS 7 ES/OS IL 40 S V2 IE<br />
Connection to system bus through<br />
Industrial Ethernet with CP 1613<br />
communications processor<br />
6ES7 650-0GC16-0YX0 D)<br />
Additional <strong>and</strong> expansion components<br />
Utility software<br />
SIMATIC PC/PG Image & Partition<br />
Creator<br />
Software for creating hard disk<br />
images <strong>and</strong> for configurating hard<br />
disk partitions<br />
6ES7 648-6AA02-0YX0 B)<br />
Memory modules for exp<strong>and</strong>ing<br />
the main memory<br />
Memory expansion kit 512<br />
Mbyte (Dual Channel) for<br />
SIMATIC Rack PC IL 40 S V2<br />
(2 x 256 Mbyte DDR SDRAM)<br />
Memory expansion kit 1 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x<br />
512 Mbyte DDR SDRAM)<br />
Memory expansion kit 2 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x 1 Gbyte<br />
DDR SDRAM)<br />
6ES7 648-2AD30-0FB0 B)<br />
6ES7 648-2AD40-0FB0 B)<br />
6ES7 648-2AD50-0FB0 B)<br />
TK 200 keyboard (PS/2 connection)<br />
German key assignment 6GF6 710-1AA<br />
International key assignment<br />
SIMATIC PC keyboard (USB<br />
connection)<br />
6GF6 710-1BA<br />
International key assignment 6ES7 648-0CB00-0YA0<br />
Multi-VGA Graphics Card<br />
"2 Screens“<br />
for operating 2 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Dual graphics card, driver CD,<br />
manual, 1 dual DVI cable for<br />
2 digital outputs, 2 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE0 B)<br />
Multi-VGA Graphics Card<br />
"4 Screens“<br />
for operating 4 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Quad graphics card, driver CD,<br />
manual, 2 dual DVI cables for<br />
4 digital outputs, 4 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE1 B)<br />
4/3<br />
4
4<br />
<strong>Engineering</strong> system<br />
ES software<br />
Introduction<br />
■ Overview<br />
■ Integration<br />
The functionality of the engineering system is largely covered by The ES software can be run on the ES hardware offered in this<br />
the st<strong>and</strong>ard engineering software. The following software op- catalog <strong>and</strong> has been tested with it. <strong>Siemens</strong> guarantees the<br />
tions are offered in addition for special functions:<br />
compatibility of hardware <strong>and</strong> software for system configurations<br />
for engineering systems with st<strong>and</strong>ard engineering software based on components in this catalog.<br />
SIMATIC PCS 7 V6.0 up to Service Pack 2 (already integrated<br />
in ServicePack 3 <strong>and</strong> higher): PCS 7 Option Package (S7-<br />
400H <strong>System</strong>s) for the engineering of automation systems with<br />
H architecture (H/F/FH systems)<br />
Version cross checker<br />
Import/export assistant<br />
Should you use basic hardware other than that offered in this catalog,<br />
please note the minimum requirements quoted in the chapter<br />
"ES/OS/BATCH/IT basic devices".<br />
If you configure your own SIMATIC PCS 7 engineering system<br />
using other/own hardware components, you carry full responsibility<br />
<strong>and</strong> will not receive any free support in the event of com-<br />
<strong>Engineering</strong> Process Safety for engineering of fail-safe syspatibility problems.<br />
tems, incl. SIMATIC Safety Matrix engineering tool<br />
Despite comprehensive tests it cannot be ruled out that the func-<br />
SIMATIC Route Control engineering<br />
tion of a SIMATIC PCS 7 system may be disturbed or impaired<br />
SIMATIC PDM Process Device Manager<br />
PCS 7 PID-Tuner for controller optimization<br />
S7-PLCSIM for the functional testing of CFC/SFC programs<br />
by additional non-system software, i.e. software not explicitly released<br />
for SIMATIC PCS 7.<br />
Therefore, the use of non-system software in the SIMATIC PCS 7<br />
environment is your responsibility. You have no claims for free<br />
support in the event of compatibility problems.<br />
4/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
■ Overview<br />
The st<strong>and</strong>ard engineering software provides the basic functionality<br />
for configuration of SIMATIC PCS 7 system components<br />
(automation systems, process I/Os, operator systems <strong>and</strong> SI-<br />
MATIC BATCH).<br />
It is available in packages of various size to match the number<br />
of configurable process objects (250, 2,000, 3,000, 5,000 or unlimited/8,500<br />
POs). The number of configurable process objects<br />
can be subsequently increased at any time by means of engineering<br />
PowerPacks.<br />
The engineering software is available in various versions to suit<br />
different requirements:<br />
only for automation systems (AS)<br />
only for operator systems (OS)<br />
for automation systems <strong>and</strong> operator systems (AS/OS)<br />
The engineering software for automation systems <strong>and</strong> operator<br />
systems is available in each case with a 10-day restricted licence<br />
as an economical solution for short-term projects.<br />
■ Function<br />
Hardware configuration in the SIMATIC manager with HW Config<br />
Essential tools of the st<strong>and</strong>ard engineering software <strong>and</strong> their<br />
functions:<br />
SIMATIC Manager<br />
The SIMATIC Manager is the integration platform for the engineering<br />
tools <strong>and</strong> configuration interface for all engineering<br />
tasks of the SIMATIC PCS 7 process control system. All aspects<br />
of the SIMATIC PCS 7 project are managed, archived <strong>and</strong> documented<br />
here. The SIMATIC Manager provides tools for configuring<br />
the automation systems, the I/Os <strong>and</strong> the communication<br />
networks, <strong>and</strong> allows selection of the required hardware from an<br />
electronic catalog.<br />
The various tasks for creating a plant project are supported by<br />
three different views within SIMATIC Manager:<br />
The component view for the configuration of hardware, such<br />
as automation systems, bus components or process I/Os<br />
The plant view for hierarchical structuring of the plant<br />
The process object view as the central development environment<br />
for all aspects of measuring points/process objects<br />
Plant view (plant hierarchy)<br />
The plant view is used to structure <strong>and</strong> display a project in accordance<br />
with technological aspects. A technologically oriented<br />
project structure enables the technologist to find his bearings<br />
quickly. The OS areas <strong>and</strong> the image hierarchy can also be derived<br />
from this type of hierarchy <strong>and</strong> it also forms the basis for<br />
the plant-oriented identification of process objects.<br />
<strong>Engineering</strong> system<br />
ES software<br />
<strong>Engineering</strong> st<strong>and</strong>ard software<br />
Plant unit overviews, in which all operable <strong>and</strong> observable CFC<br />
blocks are positioned <strong>and</strong> connected, can be generated automatically.<br />
Process object view<br />
The process object view of the SIMATIC Manager permits a universal<br />
view of the measuring point. It shows the technological hierarchy<br />
of the plant (presented in tree form) in combination with<br />
a tabular view of all aspects of the measuring point/process object<br />
(general data, parameters, signals, messages, image objects<br />
<strong>and</strong> measured value archives).<br />
All objects in the marked branch of the hierarchy are displayed<br />
in the table so that they can be directly processed with userfriendly<br />
edit, filter, replace, import <strong>and</strong> export functions.<br />
Examples of editable OS st<strong>and</strong>ard displays (faceplates) from the PCS 7<br />
Library<br />
Libraries containing process control applications<br />
Preconfigured <strong>and</strong> tested blocks, faceplates <strong>and</strong> symbols are<br />
organized in libraries <strong>and</strong> form the basic elements for the<br />
graphic configuration of automation solutions. The use of these<br />
library elements plays a major role in minimizing the engineering<br />
input <strong>and</strong> project costs.<br />
The comprehensive range of blocks includes simple logic <strong>and</strong><br />
driver blocks, technological blocks with integral alarming <strong>and</strong><br />
HMI features such as PID controllers, motors or valves, <strong>and</strong> also<br />
blocks for the integration of PROFIBUS field devices according<br />
to PROFIBUS PA Profile 3.0 (incl. st<strong>and</strong>ardized evaluation of the<br />
process value status).<br />
Documentation on the libraries for process control applications<br />
can be found on the SIMATIC PCS 7 Documentation CD (see<br />
Documentation).<br />
Multi-project engineering<br />
Multi-project engineering permits division of a large complex<br />
project into several subprojects in accordance with technological<br />
criteria in order to allow several teams to work on the project<br />
in parallel. To achieve this, a host "Multi-project" is defined in the<br />
SIMATIC Manager. Individual (sub)projects can be inserted into<br />
or removed from a multi-project at any time. Similarly, projects<br />
can be merged or divided (Branch & Merge).<br />
The (sub)projects belonging to a multi-project are all saved on a<br />
central server <strong>and</strong> can be sent to a local engineering station for<br />
editing. The engineering performance is then not affected by<br />
network access.<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
4/5<br />
4
4<br />
<strong>Engineering</strong> system<br />
ES software<br />
<strong>Engineering</strong> st<strong>and</strong>ard software<br />
Branch & Merge<br />
Branch & Merge capability is provided in conjunction with multiproject<br />
engineering <strong>and</strong> supports the effective dividing <strong>and</strong><br />
merging of projects. Charts or plant units can be copied into another<br />
project <strong>and</strong> edited there.<br />
Charts with the same name in the master project are overwritten<br />
during Branch & Merge. Interconnections which are not specific<br />
to a project, typically for interlocking, become text interconnections<br />
when branched. When merging, these text interconnections<br />
– including those entered by the user – can be closed by<br />
pressing a key.<br />
Sequential function chart<br />
Sequential function chart (SFC)<br />
SFC is used for the graphical configuration of sequence control<br />
systems for non-continuous production operations. Each SFC<br />
plan contains inputs <strong>and</strong> outputs for the control function <strong>and</strong> for<br />
status data. SFCs can be directly positioned in a CFC <strong>and</strong> interconnected.<br />
The required CFC block connections are selected<br />
by simple operations <strong>and</strong> connected to the steps or transitions<br />
of the step chains.<br />
An ISA S88-conform status manager enables the configuration<br />
of up to 8 separate sequence chains for special treatments<br />
within a single SFC, e.g. for states such as HOLDING or<br />
ABORTING, for SAFE STATE or for different operating modes.<br />
SFC configuration is supported by user-friendly editing functions<br />
<strong>and</strong> powerful test <strong>and</strong> IBS functions.<br />
4/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Continuous function chart<br />
Continuous function chart (CFC)<br />
CFC is the tool for graphical configuration of continuous automation<br />
functions. Preengineered function blocks can be positioned,<br />
configured <strong>and</strong> interconnected within CFCs using powerful autorouting<br />
<strong>and</strong> the integral configuration of HMI messages. When<br />
creating a new CFC, a new runtime group with the same name<br />
as the chart is created. All the blocks that are subsequently entered<br />
in the chart are automatically added to this runtime group.<br />
The order of the run sequence can be optimized during compilation.<br />
An algorithm first determines the optimal order of the<br />
blocks <strong>and</strong> then the order of the run-time groups.<br />
SFC type<br />
An SFC type can be placed, parameterized <strong>and</strong> interconnected<br />
as an instance in a CFC just like a normal function block. It can<br />
therefore be reused, <strong>and</strong> a change to the master causes all instances<br />
to be automatically updated accordingly.<br />
Automatic interconnection of blocks<br />
The function "Generate module driver" can be used to automatically<br />
generate <strong>and</strong> place diagnostics blocks for the I/O components<br />
of the S7-400 automation system, the ET 200M, ET 200iS<br />
<strong>and</strong> ET 200S distributed I/O systems, <strong>and</strong> for PROFIBUS field<br />
devices according to the PROFIBUS PA Profile 3.0 <strong>and</strong> field devices<br />
with HART communication. The blocks are interconnected<br />
by a wizard on the basis of the symbolic addresses.<br />
Graphics designer <strong>and</strong> faceplate designer<br />
The project data for the engineering of the operator systems are<br />
organized using SIMATIC Manager. All the data relevant to operation<br />
<strong>and</strong> monitoring of a control element, such as messages<br />
<strong>and</strong> HMI variables, are generated automatically during definition<br />
of the automation function. A powerful graphics designer is<br />
available for the generation of process displays.<br />
Customer-specific faceplates can be created in addition to the<br />
st<strong>and</strong>ard faceplates for operation <strong>and</strong> monitoring of control elements<br />
or parts of the plant. With the faceplate designer it is easy<br />
<strong>and</strong> quick to generate such customer-specific faceplates.<br />
DOCPRO<br />
DOCPRO generates plant documentation for SIMATIC PCS 7<br />
projects in accordance with defined st<strong>and</strong>ards, as well as a circuit<br />
manual in which special requirements can be entered.
■ Selection <strong>and</strong> Ordering Data<br />
PCS 7 <strong>Engineering</strong> Software<br />
Single license<br />
trilingual (German, English,<br />
French)<br />
Electronic documentation on<br />
PCS 7 Toolset CDs <strong>and</strong> PCS 7<br />
Documentation CD<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
Pack 3 for Microsoft Windows<br />
2000 (in 5 languages), Microsoft<br />
Internet Explorer, Microsoft SQL<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
Order No.<br />
AS, for 250 POs (process objects)<br />
6ES7 658-1AA06-0YA0 D)<br />
AS, for 2,000 POs 6ES7 658-1AB06-0YA0 D)<br />
AS, for 3,000 POs 6ES7 658-1AC06-0YA0 D)<br />
AS, for 5,000 POs 6ES7 658-1AD06-0YA0 D)<br />
AS, POs unlimited 6ES7 658-1AE06-0YA0 D)<br />
AS, POs unlimited, 10 days 6ES7 658-1AE06-3YA0 D)<br />
OS, for 250 POs/RC 8K 6ES7 658-2DA06-0YA0 D)<br />
OS, for 2,000 POs/RC 64K 6ES7 658-2DB06-0YA0 D)<br />
OS, for 3,000 POs/RC 100K 6ES7 658-2DC06-0YA0 D)<br />
OS, for 5,000 POs/RC 150K 6ES7 658-2DD06-0YA0 D)<br />
OS, for 8,500 POs/RC 256K 6ES7 658-2DE06-0YA0 D)<br />
OS, for 8,500 POs/RC 256K,<br />
10 days<br />
6ES7 658-2DE06-3YA0 D)<br />
AS/OS, for 250 POs/RC 8K 6ES7 658-5AA06-0YA0 D)<br />
AS/OS, for 2,000 POs/RC 64K 6ES7 658-5AB06-0YA0 D)<br />
AS/OS, for 3,000 POs/RC 100K 6ES7 658-5AC06-0YA0 D)<br />
AS/OS, for 5,000 POs/RC 150K 6ES7 658-5AD06-0YA0 D)<br />
AS/OS, POs unlimited/RC 256K<br />
PCS 7 <strong>Engineering</strong><br />
PowerPack AS<br />
for extending the <strong>Engineering</strong><br />
Software for AS<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
6ES7 658-5AE06-0YA0 D)<br />
from 250 POs to 2,000 POs 6ES7 658-1AB06-0YD0<br />
from 2,000 POs to 3,000 POs 6ES7 658-1AC06-0YD0<br />
from 3,000 POs to 5,000 POs 6ES7 658-1AD06-0YD0<br />
from 5,000 POs to POs unlimited<br />
PCS 7 <strong>Engineering</strong><br />
PowerPack OS<br />
for extending the <strong>Engineering</strong><br />
Software for OS<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
6ES7 658-1AE06-0YD0<br />
from 250 POs/RC 8K to<br />
2,000 POs/RC 64K<br />
6ES7 658-2DB06-0YD0<br />
from 2,000 POs/RC 64K to<br />
3,000 POs/RC 100K<br />
6ES7 658-2DC06-0YD0<br />
from 3,000 POs/RC 100K to<br />
5,000 POs/RC 150K<br />
6ES7 658-2DD06-0YD0<br />
from 5,000 POs/RC 150K to<br />
8,500 POs/RC 256K<br />
6ES7 658-2DE06-0YD0<br />
<strong>Engineering</strong> system<br />
ES software<br />
<strong>Engineering</strong> st<strong>and</strong>ard software<br />
■ Selection <strong>and</strong> Ordering Data<br />
PCS 7 <strong>Engineering</strong> PowerPack<br />
AS/OS<br />
for extending the <strong>Engineering</strong><br />
Software for AS/OS<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
Order No.<br />
from 250 POs/RC 8K to<br />
2,000 POs/RC 64K<br />
6ES7 658-5AB06-0YD0<br />
from 2,000 POs/RC 64K to<br />
3,000 POs/RC 100K<br />
6ES7 658-5AC06-0YD0<br />
from 3,000 POs/RC 100K to<br />
5,000 POs/RC 150K<br />
6ES7 658-5AD06-0YD0<br />
from 5,000 POs/RC 150K to<br />
POs unlimited/RC 256K<br />
<strong>Engineering</strong> Software Upgrade<br />
from V5.x to V6.0<br />
Electronic documentation on<br />
PCS 7 Toolset CDs <strong>and</strong> PCS 7<br />
Documentation CD<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
Pack 3 for Microsoft Windows<br />
2000 (in 5 languages), Microsoft<br />
Internet Explorer, Microsoft SQL<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
Can be exp<strong>and</strong>ed with PCS 7<br />
<strong>Engineering</strong> Power Packs<br />
Upgrade PCS 7 Starter Package<br />
6ES7 658-5AE06-0YD0<br />
AS/OS upgrade, for<br />
250 POs/RC 8K<br />
ES Software <strong>Engineering</strong> upgrade<br />
6ES7 658-5AA06-0YE0 D)<br />
AS upgrade for 3,000 POs 6ES7 658-1AC06-0YE0 D)<br />
AS upgrade for POs unlimited<br />
OS Software <strong>Engineering</strong><br />
upgrade<br />
6ES7 658-1AE06-0YE0 D)<br />
OS upgrade for<br />
2,000 POs/RC 64K<br />
6ES7 658-2DB06-0YE0 D)<br />
OS upgrade for<br />
5,000 POs/RC 150K<br />
6ES7 658-2DD06-0YE0 D)<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
4/7<br />
4
4<br />
<strong>Engineering</strong> system<br />
ES software<br />
<strong>Engineering</strong> H systems<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
In the case of engineering systems with st<strong>and</strong>ard engineering S7-400H V5.2 Option Package 6ES7 833-2AC01-0YB0<br />
software SIMATIC PCS 7 V6.0 up to Service Pack 2 you must in- For STEP 7 <strong>and</strong> SIMATIC PCS 7<br />
stall the S7-400H option package in order to be able to configure<br />
automation systems with H architecture (H/F/FH systems). With<br />
Service Pack 3 <strong>and</strong> higher, the functionality of the S7-400H op-<br />
Note: Only for engineering systems<br />
with st<strong>and</strong>ard engineering<br />
software SIMATIC PCS 7 V6.0 up<br />
tion package is already integrated in the st<strong>and</strong>ard engineering to Service Pack 2<br />
software.<br />
Type of delivery:<br />
The F-Tool engineering tool (S7 F <strong>System</strong>s) is required in addition<br />
for F/FH systems.<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
Version Cross Checker<br />
■ Overview<br />
The version cross-checker tool determines the differences between<br />
various versions of a project by:<br />
Comparison of CFCs/SFCs, block types, signals <strong>and</strong> sequences<br />
in order to determine what is new, what has been deleted,<br />
<strong>and</strong> what has been changed<br />
Graphic display of comparison results in a combination of tree<br />
<strong>and</strong> tabular format<br />
Color-coded identification of objects <strong>and</strong> attribute values<br />
4/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PCS 7 Version Cross Checker 6ES7 658-1CX06-2YA0<br />
V6.0<br />
Single license<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
electronic documentation as<br />
online help integrated in the software<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette
■ Overview<br />
The import/export assistant is a large plant engineering tool for<br />
replicating common configuration elements, e.g. based on st<strong>and</strong>ardized<br />
types of control element. It can significantly shorten the<br />
time required for configuration by allowing users to import plant<br />
data which have already been configured (such as control element<br />
lists or charts from the CAD/CAE world) directly into the engineering<br />
system <strong>and</strong> automatically generating the corresponding<br />
user program. Existing PCS 7 projects can be both exported<br />
<strong>and</strong> reimported.<br />
<strong>Engineering</strong> system<br />
ES software<br />
Import/export assistant<br />
■ Benefits<br />
The import/export wizard offers the following benefits:<br />
Importing of pre-existing plant layout data, such as control element<br />
lists from the higher-level CAD/CAE world<br />
- No multiple inputs, minimized configuration errors<br />
- Simple h<strong>and</strong>ling, easy-to-use graphic environment<br />
Automatic generation of control elements based on the imported<br />
control element lists <strong>and</strong> typicals<br />
- Generation of technological hierarchy<br />
- Charts of the individual control elements<br />
- Drastic reduction of time, <strong>and</strong> avoidance of errors through<br />
automatic/reproducible generation<br />
Automatic derivation of the OS display hierarchy, automatic interconnecting<br />
of blocks <strong>and</strong> placing in displays<br />
- Considerable reduction of time <strong>and</strong> costs<br />
Commissioning the individual control elements with the userfriendly<br />
CFC <strong>and</strong> SFC graphic tools<br />
Exporting of parameters optimized during commissioning<br />
back to the CAD/CAE world<br />
- Consistent data in the higher-level planning tools<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PCS 7 Import/Export Assistant 6ES7 658-1DX06-2YB0<br />
V6.0<br />
Single license<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
Efficient bulk engineering using the import/export assistant license <strong>and</strong> authorization diskette<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
4/9<br />
4
4<br />
<strong>Engineering</strong> system<br />
<strong>Engineering</strong> Process Safety<br />
Introduction<br />
■ Overview<br />
Today’s process industry is often characterized by complex<br />
technological sequences with high safety dem<strong>and</strong>s, in which<br />
any failures <strong>and</strong> errors in process automation could have fatal<br />
consequences for man, machine, plants or the environment.<br />
This is where Process Safety comes into its own. The implemented<br />
safety engineering must reliably detect both errors in the<br />
process <strong>and</strong> internal errors, <strong>and</strong> automatically place the<br />
plant/application in a safe state in the event of a fault.<br />
With SIMATIC Safety Integrated, SIMATIC PCS 7 combines st<strong>and</strong>ard<br />
automation <strong>and</strong> safety engineering in an innovative overall<br />
system, which offers consistent safety engineering for reliable,<br />
failsafe, high-availability applications in the process industry:<br />
AS 414F/FH <strong>and</strong> AS 417F/FH automation systems<br />
PROFIBUS communication with PROFIsafe profile<br />
Distributed I/Os ET 200M <strong>and</strong> ET 200S with special failsafe<br />
modules<br />
Convenient process visualization, incl. safety-oriented fault indications<br />
over the operator system<br />
<strong>Engineering</strong> system with software package S7 F <strong>System</strong>s,<br />
CFC <strong>and</strong> SIMATIC Safety Matrix<br />
4/10<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
The SIMATIC PCS 7 engineering system offers you a consistent<br />
engineering tool for st<strong>and</strong>ard <strong>and</strong> safety applications. Continuous<br />
Function Chart (CFC) <strong>and</strong> S7 F <strong>System</strong>s allows the simple,<br />
efficient <strong>and</strong> cost-effective configuration of safety functions for<br />
failsafe I/Os modules <strong>and</strong> AS 414F/FH <strong>and</strong> AS 417F/FH. The<br />
SIMATIC Safety Matrix offers even more advantages. The convenient<br />
configuration tool automatically creates complex failsafe<br />
programs on the basis of a cause & effect matrix, with which it is<br />
possible to assign exactly defined reactions (effect) to events<br />
ocurring in the course of a process (cause).
■ Overview<br />
The S7 F <strong>System</strong>s <strong>Engineering</strong> Tool, which is integrated in the<br />
SIMATIC Manager, can be used to configure an F system (F/FH).<br />
This tool enables<br />
parameterization of the CPU <strong>and</strong> F signal modules <strong>and</strong><br />
generation of failsafe applications in the CFC.<br />
Predefined, TÜV-approved blocks are available for this purpose.<br />
The failsafe blocks relieve the user of having to perform the diverse<br />
programming tasks for the detection of errors <strong>and</strong> reaction<br />
to errors.<br />
The application program may contain failsafe (F) <strong>and</strong> non-failsafe<br />
st<strong>and</strong>ard programs (S), where strict separation of F <strong>and</strong> S<br />
program components together with data exchange by means of<br />
special conversion blocks prevent conflicts.<br />
S7 F <strong>System</strong>s supports the acceptance testing <strong>and</strong> comparison<br />
of F programs using a checksum that enables every minor<br />
change to be detected. This checksum is recorded during the<br />
TÜV acceptance test. A password prevents access to non-authorized<br />
persons.<br />
<strong>Engineering</strong> system<br />
<strong>Engineering</strong> Process Safety<br />
<strong>Engineering</strong> F/FH systems<br />
An S7 F Configuration Pack is required for the engineering when<br />
using the failsafe I/Os SM 326F/336F (AI, DI, DO) as st<strong>and</strong>ard<br />
I/Os (without F functionality). This is a component of the F programming<br />
tool S7 F <strong>System</strong>s V5.2 <strong>and</strong> can also be downloaded<br />
from the Internet (as part of product support provided by <strong>Automation</strong><br />
<strong>and</strong> <strong>Drives</strong> Service & Support: S7 F Configuration Pack<br />
V5.3).<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
S7 F <strong>System</strong>s V5.2<br />
6ES7 833-1CC00-0YX0<br />
F program software <strong>and</strong> function<br />
block library, single license<br />
Bilingual (German, English)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette;software <strong>and</strong> electronic<br />
documentation on CD<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
4/11<br />
4
4<br />
<strong>Engineering</strong> system<br />
<strong>Engineering</strong> Process Safety<br />
SIMATIC safety matrix<br />
■ Overview<br />
■ Design<br />
With the Safety Matrix, we offer an innovative configuration tool In the context of SIMATIC PCS 7, the following individual prod-<br />
for processes that require safety reactions to defined states. The ucts are available for the SIMATIC Safety Matrix:<br />
Safety Matrix is based on the proven principle of a cause & effect<br />
matrix with which it is possible to assign exactly defined reactions<br />
(effect) to events ocurring in the course of a process<br />
(cause). This is an integral part of the risk analysis of a plant. The<br />
specification of the safety program also corresponds to the input<br />
parameters for the safety matrix. Using these parameters, the<br />
Safety Matrix automatically generates failsafe CFC programs for<br />
SIMATIC PCS 7.<br />
Compared to conventional programming, safety logic can thus<br />
be configured significantly faster <strong>and</strong> with considerably less<br />
cost/input. Configurators do not require any special programming<br />
expertise <strong>and</strong> can concentrate fully on the safety requirements<br />
of their plants. If required, several matrices can also be interlinked.<br />
SIMATIC Safety Matrix Tool<br />
for the configuration of safety functions on the PCS 7 <strong>Engineering</strong><br />
<strong>System</strong><br />
SIMATIC Safety Matrix Editor<br />
for creating <strong>and</strong> checking the Safety Matrix logic in an external<br />
computer, independent of the engineering system; (can also<br />
be optionally used as an add-on to SIMATIC Safety Matrix<br />
Tool)<br />
SIMATIC Safety Matrix Viewer for SIMATIC PCS 7<br />
for the operation <strong>and</strong> monitoring Safety Matrix using the SI-<br />
MATIC PCS 7 operator system (for order date, please also refer<br />
to the section "OS Software" in the Chapter "Operator <strong>System</strong>")<br />
■ Benefits<br />
<strong>System</strong> requirements<br />
Hardware require- Software requirements<br />
The advantages of Safety Matrix at a glance:<br />
7 Configuration of safety functions (logic) using the proven<br />
cause & effect method – i.e. on the basis of process events<br />
<strong>and</strong> process reactions<br />
ments<br />
SIMATIC Safety Matrix SIMATIC PCS 7<br />
Tool<br />
AS 414H or<br />
AS 417H<br />
PCS 7 V6.0, SP2 or<br />
higher,<br />
S7 F <strong>System</strong>s V5.2 , HF 2<br />
or higher with S7 F-Lib<br />
7 Automatic generation of the safety-oriented SIMATIC PCS 7<br />
V1.2<br />
program<br />
SIMATIC Safety Matrix<br />
Windows 2000 Profes-<br />
7 Minimization of sources of error due to easy <strong>and</strong> clearly presented<br />
configuration<br />
Editor<br />
sional, SP2 or higher or<br />
Windows XP Professional<br />
7 Automatic creation of documentation after safety checks<br />
7 Shortened configuration times <strong>and</strong> no need for special programming<br />
skills<br />
7 Automatic generation of visualization <strong>and</strong> convenient display<br />
SIMATIC Safety Matrix SIMATIC PCS 7<br />
Viewer<br />
AS 414H or<br />
AS 417H<br />
PCS 7-OS V6.0, SP2 or<br />
higher<br />
of the Safety Matrix on the SIMATIC PCS 7 operator station The SIMATIC Safety Matrix Editor has the added benefit that the<br />
7 Automatic management of project versions of the program<br />
7 User-friendly tracking of changes<br />
Safety Matrix can also be created, processed <strong>and</strong> checked outside<br />
the SIMATIC PCS 7 engineering system. The SIMATIC<br />
Safety Matrix Editor can be used on any computer with Windows<br />
7 Easy modification of safety functions <strong>and</strong> simple adaptation of 2000 Professional, SP2 or higher or Windows XP Professional.<br />
the specification in test mode, as well as bypass, reset <strong>and</strong> However, generating the failsafe CFC program <strong>and</strong> compiling<br />
override functions.<br />
<strong>and</strong> loading it into the automation system is only possible using<br />
the SIMATIC engineering system with SIMATIC Safety Matrix<br />
Tool.<br />
4/12<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
■ Function<br />
Safety Matrix: "Intersections" define the linking of "cause" <strong>and</strong> "effect"<br />
Configuration of analog or digital "causes" <strong>and</strong> digital "effects"<br />
The matrix table is similar to a conventional spreadsheet. In the<br />
horizontal lines, the user first enters possible process events (inputs)<br />
<strong>and</strong> configures the type <strong>and</strong> number of inputs, possible<br />
delays, interlockings <strong>and</strong> logical operations. The user also defines<br />
here if <strong>and</strong> which faults can be tolerated. After configuring<br />
the causes, the effects, i.e. the reactions (outputs) to a specific<br />
event are entered in the vertical columns. The interlinking of<br />
causes <strong>and</strong> effects is then implemented by simply clicking the<br />
cell at the intersection of row <strong>and</strong> column. This opens a window<br />
in which the user can select the type of link.<br />
<strong>Engineering</strong> system<br />
<strong>Engineering</strong> Process Safety<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
SIMATIC safety matrix<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC Safety Matrix Tool<br />
Creation, configuration, compilation,<br />
loading <strong>and</strong> online monitoring<br />
of the Safety Matrix in a<br />
SIMATIC PCS 7 environment<br />
Bilingual (German, English)<br />
single license for 1 installation,<br />
type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette<br />
for Safety Matrix Tool <strong>and</strong> Safety<br />
Matrix Viewer; software <strong>and</strong> electronic<br />
documentation on CD<br />
6ES7 833-1SM00-0YA5 C)<br />
SIMATIC Safety Matrix Editor<br />
Creation <strong>and</strong> checking of the<br />
Safety Matrix logic on an external<br />
computer without a SIMATIC<br />
PCS 7/ STEP 7 environment<br />
Bilingual (German, English)<br />
single license for 1 installation,<br />
type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette;<br />
software <strong>and</strong> electronic<br />
documentation on CD<br />
6ES7 833-1SM40-0YA5 C)<br />
SIMATIC Safety Matrix Viewer<br />
for SIMATIC PCS 7<br />
Operation <strong>and</strong> monitoring of the<br />
Safety Matrix in a SIMATIC PCS 7<br />
environment with several operator<br />
control levels<br />
Bilingual (German, English)<br />
single license for 1 installation,<br />
type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette;<br />
software <strong>and</strong> electronic<br />
documentation on CD<br />
6ES7 833-1SM60-0YA5 C)<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
4/13<br />
4
4<br />
<strong>Engineering</strong> system<br />
SIMATIC Route Control<br />
SIMATIC Route Control <strong>Engineering</strong><br />
■ Overview<br />
Route Control <strong>Engineering</strong> Tool<br />
Once the RC-relevant basic data of a PCS 7 project have been<br />
adopted in a Route Control project, the next step is to configure<br />
the RC-specific objects with the Route Control <strong>Engineering</strong> Tool:<br />
Partial Routes:<br />
Dividing the transport routes into partial routes helps to increase<br />
flexibility <strong>and</strong> to minimize the amount of configuration<br />
work through grouping. Relevant partial route parameters: "bidirectional"<br />
<strong>and</strong> "priority" (when searching for a route, the lowest<br />
total of partial route priorities is decisive for the overall<br />
route)<br />
Locations:<br />
The beginning <strong>and</strong> end of each partial route - <strong>and</strong> hence the<br />
source <strong>and</strong> destination of a material transport - are marked by<br />
locations. The locations are also parameters for requesting a<br />
material transport (source, destination, intermediate locations/via).<br />
Interconnections:<br />
The RC elements are incorporated in a partial route <strong>and</strong> thus<br />
"interconnected" with it. As a result, the RC elements acquire<br />
additional properties depending on their type (e.g. "close<br />
valve" in base position). These properties can be edited in<br />
configuration windows.<br />
The configuration of Route Control builds on the basic configuration<br />
of the SIMATIC PCS 7 process control system using<br />
blocks from the PCS 7 St<strong>and</strong>ard Library. Technological elements<br />
of relevance for Route Control (RC elements) are adapted in the<br />
CFC Editor using uniform interface blocks from the Route Control<br />
Library. This means that existing plants are also easy to upgrade<br />
with SIMATIC Route Control.<br />
Detailed information, see the chapter "SIMATIC Route Control".<br />
Function Catalogs:<br />
The partial routes can be assigned to certain function catalogs,<br />
e.g. "Cleaning" or "Product Transport", according to technological<br />
<strong>and</strong> product-specific aspects. When searching for<br />
routes, function catalogs allow you to limit the results to the<br />
type of material transport.<br />
Function Steps/Sequence Functions<br />
Each function catalog includes as many as 32 configurable<br />
■ Function<br />
The SIMATIC Route Control <strong>Engineering</strong> program package with<br />
the following configuration components is available in addition to<br />
the basic tools of the SIMATIC PCS 7 <strong>Engineering</strong> <strong>System</strong> for<br />
configuring Route Control applications:<br />
technological sequence functions, e.g. base position of the<br />
control elements, open transport valves, open source valve,<br />
switch on pump. Together with the RC elements interconnected<br />
in the partial routes, the sequence functions determine<br />
the sequence of the material transport.<br />
Special configuration functions make it easier to perform repetitive<br />
routine <strong>and</strong> extend the range of options for controlling mate-<br />
Route Control Library<br />
rial transports, e.g.:<br />
The Route Control Library contains blocks for RC configuration,<br />
blocks for creating transport routes, <strong>and</strong> interface blocks for<br />
RC elements: control (actuator) elements, sensor elements, pa-<br />
Exporting configuration data in the form of CSV files to<br />
Microsoft Excel, copying <strong>and</strong> editing the data there, <strong>and</strong> then<br />
reimporting the files into Route Control<br />
rameter (RC setpoint) elements <strong>and</strong> connection elements (material<br />
data related to a partial route). It is made available in the catalog<br />
of the CFC Editor.<br />
Controlling the joint use of partial routes by configurable function<br />
IDs<br />
Checking material compatibilities <strong>and</strong> interlocking partial<br />
Route Control Wizard<br />
routes in case of incompatible material sequences based on<br />
the material ID saved in the connection element of the partial<br />
The Route Control Wizard is the interface between the RC con- route<br />
figuration <strong>and</strong> the SIMATIC PCS 7 basic configuration. The wizard,<br />
which can be called up from the SIMATIC Manager menu,<br />
Connecting to the route block in runtime the dynamic (exter-<br />
receives the RC-specific configuration data of the SIMATIC<br />
nal) setpoint values arriving from the process (e.g. weighed<br />
PCS 7 project for importing into the Route Control <strong>Engineering</strong>.<br />
quantity)<br />
In doing so it carries out a plausibility check, defines the AS-OS ■ Selection <strong>and</strong> Ordering Data Order No.<br />
<strong>and</strong> AS-AS communication connections <strong>and</strong> configures the<br />
RC server signals.<br />
SIMATIC Route Control <strong>Engineering</strong><br />
V6.0<br />
Single license for 1 installation, trilingual<br />
(German, English, French)<br />
Software <strong>and</strong> electronic documentation<br />
on the CD SIMATIC<br />
Route Control V6.0<br />
Type of delivery:<br />
CD SIMATIC Route Control V6.0,<br />
certificate of license <strong>and</strong> authorization<br />
diskette<br />
6ES7 658-7DX06-0YA0 D)<br />
4/14<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1
■ Overview<br />
Configuration options with SIMATIC PDM<br />
SIMATIC PDM (Process Device Manager) is a universal, vendorindependent<br />
tool for the configuration, parameterization, commissioning,<br />
diagnosis <strong>and</strong> servicing of intelligent field devices<br />
(sensors <strong>and</strong> actuators) <strong>and</strong> field components (remote I/Os,<br />
multiplexers, control-room devices, compact controllers), which<br />
in the following sections will be referred to simply as devices. Using<br />
one software, SIMATIC PDM enables the processing of more<br />
than 1,000 devices from <strong>Siemens</strong> <strong>and</strong> over 100 vendors worldwide<br />
on one homogeneous user interface.<br />
With respect to device integration, SIMATIC PDM is the most<br />
powerful device manager available on the world market. Devices<br />
which previously were not supported can be easily integrated<br />
in SIMATIC PDM at any time by importing their device descriptions<br />
(EDD). This provides security for your investment <strong>and</strong><br />
saves you investment costs, training expenses <strong>and</strong> consequential<br />
costs.<br />
Parameters <strong>and</strong> functions for all supported devices are displayed<br />
in a consistent <strong>and</strong> uniform fashion independent of their<br />
communications interface.<br />
■ Design<br />
<strong>Engineering</strong> system<br />
ES software SIMATIC PDM<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
Product Versions<br />
SIMATIC PDM is available in two product versions:<br />
as the SIMATIC PDM Package for SIMATIC PCS 7/S7, fully integrated<br />
in the central engineering system of SIMATIC PCS 7<br />
or in STEP 7, or<br />
as the SIMATIC PDM St<strong>and</strong>-alone, on a mobile computer (Microsoft<br />
Windows 95, 98, ME, NT, 2000 or XP Professional) on<br />
PROFIBUS or with direct connection to the device.<br />
Customer-oriented product structure<br />
SIMATIC PDM is optimally adapted to the customer’s needs <strong>and</strong><br />
structured to enable the customer to put together his very own<br />
product with the functionality actually required. Which product<br />
components he selects depends on whether SIMATIC PDM is<br />
operated in the SIMATIC PCS 7 context or in st<strong>and</strong>-alone mode.<br />
Depending on the number of devices integrated in a project<br />
or diagnosed in the lifelist, SIMATIC PDM is infinitely scalable<br />
from 4 TAGs (st<strong>and</strong>-alone version) or 128 TAGs, through<br />
128/512/1.024/2.048 TAGs, to an unlimited number of TAGs.<br />
Every device (e.g. transmitter, positioner etc.) corresponds to<br />
one TAG, <strong>and</strong> the number of TAGs within a project is monitored<br />
by SIMATIC PDM.<br />
4/15<br />
4
4<br />
<strong>Engineering</strong> system<br />
ES software SIMATIC PDM<br />
Introduction<br />
SIMATIC PDM St<strong>and</strong>-alone SIMATIC PDM Package for<br />
Communication<br />
SIMATIC PCS 7 / S7<br />
SIMATIC PDM supports several communication protocols <strong>and</strong><br />
SIMATIC PDM Basic Software incl. SIMATIC PDM Starter Package<br />
4TAGs<br />
PCS 7 incl. 128 TAGs<br />
components for communicating with devices that have the following<br />
interfaces:<br />
Option: Integration in STEP 7/<br />
PROFIBUS DP/PA interface<br />
PCS 7<br />
Option: Routing through S7-400<br />
HART interface<br />
Modbus interface<br />
Option: Communication through<br />
st<strong>and</strong>ard HART multiplexer<br />
Option: Communication through<br />
st<strong>and</strong>ard HART multiplexer<br />
Special interface from <strong>Siemens</strong><br />
TAG options:<br />
TAG options:<br />
Routing<br />
128<br />
512<br />
From the central engineering system of the SIMATIC PCS 7 pro-<br />
512<br />
1.024<br />
cess control system it is possible with SIMATIC PDM to reach ev-<br />
1.024<br />
2.048<br />
unlimited<br />
2.048<br />
unlimited<br />
ery EDD-parameterizable device in the field plant-wide through<br />
the various bus systems <strong>and</strong> remote I/Os. SIMATIC PDM can<br />
thus perform the following from a central position:<br />
read diagnosis information from the devices,<br />
■ Function<br />
modify device settings,<br />
adjust <strong>and</strong> calibrate devices,<br />
Core functions<br />
monitor process values,<br />
Adjustment <strong>and</strong> modification of device parameters<br />
create simulation values or<br />
Comparing (e.g. project <strong>and</strong> device data)<br />
reparameterize devices.<br />
Plausibility testing of data input<br />
Device identification <strong>and</strong> testing<br />
■ Integration<br />
Device status indication with operating modes, alarms <strong>and</strong><br />
states<br />
Device Integration<br />
Device identification <strong>and</strong> testing<br />
Simulation<br />
SIMATIC PDM supports all devices which are defined by means<br />
of the Electronic Device Description (EDD). Based on EN 50391<br />
<strong>and</strong> IEC 61804, EDD is the most widely used st<strong>and</strong>ardized tech-<br />
Diagnosis<br />
nology for device integration. It is also a directive of the estab-<br />
Management (e.g. networks <strong>and</strong> PCs)<br />
Commissioning functions, e.g. measuring circuit tests of device<br />
data<br />
Export/import<br />
Device replacement (lifecycle management)<br />
lished organizations for PROFIBUS (PNO: PROFIBUS-Nutzerorganisation)<br />
<strong>and</strong> HART (HCF: HART Communication Foundation).<br />
In SIMATIC PDM the devices are integrated directly by means of<br />
their EDD or the current HCF catalog. In the EDD the device is<br />
described in terms of its functions <strong>and</strong> construction using the<br />
Electronic Device Description Language (EDDL) specified by<br />
Saving of user operations (audit trail)<br />
PNO. SIMATIC PDM automatically creates its graphical user in-<br />
Graphic presentations of echo envelope curves, trend display,<br />
valve diagnosis results etc.<br />
terface with the specific device information using this description.<br />
Support of system management<br />
The current SIMATIC PDM device catalog covers more than<br />
1,000 devices from over 100 manufacturers worldwide. Further-<br />
SIMATIC PDM supports the operative system management in more, the devices of all manufacturers can be integrated at any<br />
particular through:<br />
time by simply importing their EDD into the SIMATIC PDM. It is<br />
Uniform presentation <strong>and</strong> operation of devices<br />
Indicators for preventive maintenance <strong>and</strong> servicing<br />
thus possible to keep the device range up to date at all times<br />
<strong>and</strong> to add to the number of manufacturers <strong>and</strong> devices supported<br />
by SIMATIC PDM. If you would like to use any devices<br />
Detection of changes in the project <strong>and</strong> device<br />
which cannot be found in the SIMATIC PDM device catalog, we<br />
Increasing the operational reliability<br />
will be glad to help you integrate them.<br />
Reducing the investment, operating <strong>and</strong> maintenance costs Contact addresses<br />
User interface<br />
The operator interface of SIMATIC PDM satisfies the requirements<br />
of the directives VDI/VDE GMA 2187 <strong>and</strong> IEC 65/349/CD.<br />
<strong>Siemens</strong> AG, <strong>Automation</strong> <strong>and</strong> <strong>Drives</strong>,<br />
Technical Support<br />
Europe<br />
Even complex devices with several hundred parameters can<br />
thus be represented clearly <strong>and</strong> processed quickly. Using<br />
SIMATIC PDM it is very easy to navigate in highly complex stations<br />
such as remote I/Os <strong>and</strong> even connected field devices.<br />
Several views are available to the user to help him with his tasks:<br />
Hardware project view<br />
Process device network view (preferably for st<strong>and</strong>-alone application)<br />
Process device plant view as TAG-related view, also with dis-<br />
Tel.: +49 180 50 50 222<br />
Fax: +49 180 50 50 223<br />
E-mail: adsupport@siemens.com<br />
Asia/Pacific<br />
Tel.: +86 1064 719 990<br />
Fax: +86 1064 747 474<br />
E-mail: adsupport.asia@siemens.com<br />
America<br />
play of diagnosis information<br />
Tel.: +1 423 262 2522<br />
Parameter view for parameterizing the field devices<br />
Lifelist view for commissioning <strong>and</strong> service<br />
Fax: +1 423 262 2289<br />
E-mail: simatic.hotline@sea.siemens.com<br />
4/16<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
<strong>Engineering</strong> system<br />
ES software SIMATIC PDM<br />
SIMATIC PDM package for PCS 7<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC PDM Starter Package<br />
V5.2 for SIMATIC PCS 7<br />
Preferred version for<br />
SIMATIC PCS 7, in 5 languages<br />
(German, English, French, Italian<br />
<strong>and</strong> Spanish), with<br />
Basic software for SIMATIC PDM<br />
(incl. communication through<br />
PROFIBUS DP/PA, HART modem<br />
<strong>and</strong> RS 232)<br />
Integration in STEP 7 / PCS 7<br />
Routing through S7-400<br />
128 TAGs<br />
SIMATIC PDM documentation<br />
SIMATIC PDM TAG options<br />
6ES7 658-3PX05-0YC0 C)<br />
Parameter view of SIMATIC PDM with curve <strong>and</strong> online display<br />
Power Pack<br />
The SIMATIC PDM package for PCS 7 is integrated in the engineering<br />
system of SIMATIC PCS 7 as a tool for the configuration,<br />
From 128 TAGs to 512 TAGs<br />
From 512 TAGs to 1024 TAGs<br />
6ES7 658-3XB05-2XD5<br />
6ES7 658-3XC05-2XD5<br />
parameterization, commissioning, diagnostics <strong>and</strong> servicing of<br />
intelligent process devices. Using a SIMATIC PDM Starter Package<br />
PCS 7, the latter can be custom-configured with the option<br />
"Communication through St<strong>and</strong>ard HART Multiplexers" <strong>and</strong> ad-<br />
From 1024 TAGs to 2048 TAGs<br />
From 2048 TAGs to TAGs unlimited<br />
6ES7 658-3XD05-2XD5<br />
6ES7 658-3XH05-2XD5<br />
ditional TAG options.<br />
Supplementary Software<br />
■ Design<br />
Communication through st<strong>and</strong>ard<br />
HART multiplexer<br />
6ES7 658-3EX00-2XD0<br />
SIMATIC PDM Starter Package PCS 7<br />
This is a SIMATIC PDM bundle for projects with up to 128 TAGs,<br />
which is optimized for integration in the central engineering system<br />
of SIMATIC PCS 7 or in STEP 7. In addition to the "SIMATIC<br />
PDM Basic Software" it already contains the options "Integration<br />
in 1 language (English)<br />
Demo Software<br />
SIMATIC PDM Demo V5.2<br />
In 5 languages (German, English,<br />
French, Italian <strong>and</strong> Spanish)<br />
6ES7 658-3GX05-0YC8 C)<br />
in STEP 7/PCS 7" <strong>and</strong> "Routing through S7-400" (for details of Update<br />
these software components see the section "SIMATIC PDM<br />
St<strong>and</strong>-alone Version").<br />
SIMATIC PDM Update from V5.1<br />
to V5.2<br />
6ES7 658-3AX05-0YC3 C)<br />
SIMATIC PDM Option<br />
in 5 languages (German, English,<br />
Communication through St<strong>and</strong>ard HART Multiplexer<br />
French, Italian <strong>and</strong> Spanish),<br />
works on basic software, all com-<br />
This option enables SIMATIC PDM to use the HART OPC server binations of the supplementary<br />
for communicating with HART field devices through HART multiplexers.<br />
software <strong>and</strong> the PDM starter<br />
package<br />
TAG options<br />
With TAG options it is possible to increase the number of project<br />
TAGs already integrated in the SIMATIC PDM Basic Software. Licenses<br />
for 512, 1,024, 2,048 <strong>and</strong> unlimited TAGs are available.<br />
One TAG corresponds to one SIMATIC PDM object, which represents<br />
individual field devices or components within a project,<br />
e.g. measuring devices, positioners, switching devices or remote<br />
I/Os. TAGs are also relevant for diagnosis with the lifelist of<br />
SIMATIC PDM. In this case, TAGs are considered to be all recognized<br />
devices with diagnostics capability, whose detailed diagnosis<br />
is effected through the device description (EDD).<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
4/17<br />
4
4<br />
<strong>Engineering</strong> system<br />
ES software SIMATIC PDM<br />
SIMATIC PDM st<strong>and</strong>-alone version<br />
■ Overview<br />
PDM Lifelist with status <strong>and</strong> diagnostics display<br />
SIMATIC PDM can be operated as a st<strong>and</strong>-alone version on a<br />
PC/PG/notebook independently of SIMATIC PCS 7.<br />
■ Design<br />
The product structure is designed to enable you to put together<br />
the SIMATIC PDM individually in accordance with the functionality<br />
you actually need:<br />
SIMATIC PDM Basic Software<br />
This is the basic block with all the functions required for operating<br />
<strong>and</strong> parameterizing the devices <strong>and</strong> with the communication<br />
routes enabled for PROFIBUS DP/PA, HART communication<br />
(Modem, RS 232 <strong>and</strong> PROFIBUS) <strong>and</strong> Modbus. The SIMATIC<br />
PDM Basic Software can manage projects with as many as<br />
4 TAGs <strong>and</strong> provided the system requirements are met it can be<br />
used for st<strong>and</strong>-alone operation on any computers (PCs/notebooks)<br />
with local connection to bus segments or direct connection<br />
to the device.<br />
SIMATIC PDM Option Integration in STEP 7/PCS 7<br />
This option is required for using SIMATIC PDM within a SIMATIC<br />
S7 or SIMATIC PCS 7 project with local connection to the<br />
PROFIBUS. SIMATIC PDM can thus be started directly from the<br />
hardware project (HW-Config).<br />
SIMATIC PDM Option Routing through S7-400<br />
This option is required as an add-on to the option "Integration in<br />
STEP7/PCS 7" when SIMATIC PDM is to be used in a central engineering<br />
system for SIMATIC S7/PCS 7 with Ethernet bus link to<br />
the automation systems for the plant-wide configuration, parameterization,<br />
commissioning <strong>and</strong> diagnosis of the devices in the<br />
field.<br />
4/18<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
SIMATIC PDM Option Communication through St<strong>and</strong>ard<br />
HART Multiplexer<br />
This option enables SIMATIC PDM to use the HART OPC server<br />
for communicating with HART field devices through HART multiplexers.<br />
TAG options<br />
With TAG options it is possible to increase the number of project<br />
TAGs already integrated in the SIMATIC PDM Basic Software. Licenses<br />
for 128, 512, 1,024, 2,048 <strong>and</strong> unlimited TAGs are available.<br />
One TAG corresponds to one SIMATIC PDM object, which<br />
represents individual field devices or components within a<br />
project, e.g. measuring devices, positioners, switching devices<br />
or remote I/Os. TAGs are also relevant for diagnosis with the lifelist<br />
of SIMATIC PDM. In this case, TAGs are considered to be all<br />
recognized devices with diagnostics capability, whose detailed<br />
diagnosis is effected through the device description (EDD).<br />
■ Technical specifications<br />
Requirements for st<strong>and</strong>-alone operation<br />
Hardware PG/PC/notebook with processor<br />
in accordance with the operating<br />
system requirements<br />
256 Mbyte main memory <strong>and</strong><br />
higher<br />
210 Mbyte free memory on hard<br />
disk <strong>and</strong> higher<br />
Operating system (alternative) Microsoft Windows 95c<br />
Microsoft Windows 98 SE<br />
Microsoft Windows ME<br />
Microsoft Windows NT 4.0 Workstation<br />
with SP6a or higher<br />
Microsoft Windows 2000 Professional<br />
with SP1 or higher<br />
Microsoft Windows XP Professional<br />
with SP1 or higher<br />
More software components<br />
SIMATIC PDM without STEP 7 SIMATIC Manager V5.2 (included<br />
on SIMATIC PDM CD)<br />
SIMATIC PDM integrated in STEP 7 V5.0 or higher with Ser-<br />
STEP 7<br />
vice Pack 4 or higher, to be<br />
ordered separately
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC PDM Basic Software<br />
V5.2<br />
Basic software for the operation<br />
<strong>and</strong> parameterization of process<br />
devices <strong>and</strong> components, in<br />
5 languages (German, English,<br />
French, Italian <strong>and</strong> Spanish), incl.<br />
communication through HART<br />
modem,<br />
communication through RS 232,<br />
communication through<br />
PROFIBUS DP/PA<br />
4 TAGs<br />
SIMATIC PDM documentation<br />
Supplementary Software<br />
Extensions to SIMATIC PDM basic<br />
software<br />
6ES7 658-3AX05-0YC0 C)<br />
Integration in STEP 7 /<br />
SIMATIC PCS 7<br />
is only required if it is intended to<br />
use the integration of SIMATIC<br />
PDM in HW Config<br />
in 5 languages (German, English,<br />
French, Italian <strong>and</strong> Spanish)<br />
6ES7 658-3BX00-2XD0<br />
Routing through S7-400<br />
In 5 languages (German, English,<br />
French, Italian <strong>and</strong> Spanish)<br />
6ES7 658-3CX00-2XD0<br />
Communication through st<strong>and</strong>ard<br />
HART multiplexer<br />
in 1 language (English)<br />
SIMATIC PDM TAG options<br />
6ES7 658-3EX00-2XD0<br />
Up to 128 TAGs 6ES7 658-3XA00-2XD0<br />
Up to 512 TAGs 6ES7 658-3XB00-2XD0 C)<br />
Up to 1,024 TAGs 6ES7 658-3XC00-2XD0<br />
Up to 2,048 TAGs<br />
Power Packs<br />
6ES7 658-3XD00-2XD0<br />
- From 128 TAGs to 512 TAGs 6ES7 658-3XB05-2XD5<br />
- From 512 TAGs to 1024 TAGs 6ES7 658-3XC05-2XD5<br />
- From 1024 TAGs to 2048 TAGs 6ES7 658-3XD05-2XD5<br />
- From 2048 TAGs to TAGs unlimited<br />
6ES7 658-3XH05-2XD5<br />
<strong>Engineering</strong> system<br />
ES software SIMATIC PDM<br />
SIMATIC PDM st<strong>and</strong>-alone version<br />
■ Selection <strong>and</strong> Ordering Data<br />
Demo Software<br />
Order No.<br />
SIMATIC PDM Demo Version<br />
V5.2<br />
In 5 languages (German, English,<br />
French, Italian <strong>and</strong> Spanish)<br />
Update<br />
6ES7 658-3GX05-0YC8 C)<br />
SIMATIC PDM Update from V5.1<br />
to V5.2<br />
in 5 languages (German, English,<br />
French, Italian <strong>and</strong> Spanish),<br />
works on all combinations of supplementary<br />
software <strong>and</strong> options<br />
6ES7 658-3AX05-0YC3 C)<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
4/19<br />
4
4<br />
<strong>Engineering</strong> system<br />
Supplementary ES software<br />
Controller optimization<br />
■ Overview<br />
The PCS 7 PID-Tuner can be used for the CTRL_PID <strong>and</strong><br />
CTRL_S software controllers. With the PCS 7 PID-Tuner function<br />
integrated in the CFC it is possible to determine the optimum<br />
control parameters for the PID, PI <strong>and</strong> P controllers of a loop in<br />
defined steps.<br />
Simulation with S7-PLCSIM<br />
■ Overview<br />
Overview simulation software for SIMATIC PCS 7<br />
4/20<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
The tool can be used to optimize controlled systems with <strong>and</strong><br />
without an integral component. Optimization can be carried out<br />
in manual or automatic mode. The transient response of the controllers<br />
with the determined controller parameters can be<br />
checked by carrying out step changes. The derived parameters<br />
can be saved <strong>and</strong> recalled as required.<br />
During determination of the controller parameters, the typical<br />
controller values (actual value, setpoint, manipulated variable)<br />
can be recorded using a curve function.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PCS 7 PID Tuner<br />
6ES7 653-0SP06-2YB0<br />
single license<br />
Controller optimization; options<br />
package for CFC<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette;<br />
For further programs concerning controller optimization, see the catalog<br />
"Add Ons for the SIMATIC PCS 7 Process Control <strong>System</strong>“.<br />
Using the S7-PLCSIM simulation software, user programs created<br />
with CFC/SFC can be tested on a PG/PC, regardless of<br />
whether the target hardware is available. The detection <strong>and</strong><br />
elimination of errors is thus brought forward into an early phase<br />
of development. This results in faster commissioning, lower<br />
costs <strong>and</strong> better program quality.<br />
■ Function<br />
S7-PLCSIM simulates a SIMATIC S7 CPU with its associated process<br />
images. The program to be tested is loaded into the simulated<br />
S7 CPU in the same way as for a real CPU, <strong>and</strong> is executed<br />
there. S7-PLCSIM is fully integrated in STEP 7. Process values<br />
can be exchanged between S7-PLCSIM <strong>and</strong> other Windows applications<br />
through an interface.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
S7-PLCSIM<br />
Functional testing of programs<br />
which were created with<br />
CFC/SFC, on PC/PG<br />
in 5 languages (German, English,<br />
French, Spanish, Italian)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette;<br />
software <strong>and</strong> electronic documentation<br />
on CD<br />
Single license 6ES7 841-0CC03-0YE0<br />
Upgrade to V5 6ES7 841-0CC03-0YE4<br />
Software Update Service 6ES7 841-0CA01-0YX2<br />
For further programs concerning testing <strong>and</strong> simulation, see the catalog<br />
"Add Ons for the SIMATIC PCS 7 Process Control <strong>System</strong>“.
Operator <strong>System</strong><br />
5/2 Introduction<br />
5/4 OS hardware<br />
5/4 Introduction<br />
5/5 OS basic hardware<br />
5/7 Signal output<br />
5/8 OS software<br />
5/8 Introduction<br />
5/10 OS software for single station/<br />
server/client<br />
5/11 OS archiving<br />
5/12 StoragePlus<br />
5/13 SFC visualization<br />
5/13 SIMATIC Safety Matrix Viewer<br />
5/14 Connectivity Pack <strong>and</strong><br />
Client Access Licences<br />
5/15 Redundant operator systems<br />
5/15 OS redundancy<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
5<br />
Operator system<br />
Introduction<br />
■ Overview<br />
Operator interface of the OS process control system with freely positionable<br />
windows<br />
The operator system is the human-machine interface of the SI-<br />
MATIC PCS 7 process control system, <strong>and</strong> thus represents the<br />
user’s window into the process. It is extremely flexible, <strong>and</strong> can<br />
be easily adapted to different plant architectures <strong>and</strong> customer<br />
requirements.<br />
The basis is formed by perfectly coordinated operator stations<br />
for single-user systems <strong>and</strong> for multi-user systems with client/server<br />
architecture.<br />
The system software of the operator stations is available in different<br />
levels based on the number of process objects (PO) used:<br />
250, 2,000, 3,000 or 5,000 POs per OS single station<br />
250, 2,000, 3,000, 5,000 or 8,500 POs per OS server<br />
The number of POs can be increased at any time by means of<br />
PowerPacks to allow for higher requirements or system expansions.<br />
5/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Benefits<br />
7 Flexible, modular architecture with scalable hardware <strong>and</strong><br />
software components for single-user <strong>and</strong> multi-user systems<br />
7 High-performance operator stations based on st<strong>and</strong>ard<br />
PC technology with Microsoft Windows 2000 can be used in<br />
office or industrial environments<br />
7 Client/server multi-user systems with up to 12 OS servers/<br />
pairs of servers, each for 5,000 process objects <strong>and</strong> up to<br />
32 OS clients per server/pair of servers<br />
7 High-performance archive system based on Microsoft SQL<br />
server with cyclic archives <strong>and</strong> integral data backup, optionally<br />
with archive server<br />
7 OS health check for monitoring important server applications<br />
7 Online modifications without interrupting runtime operations,<br />
<strong>and</strong> online testing with selective loading of redundant servers<br />
7 Optimized AS/OS communication:<br />
AS reply cycle can be 500 ms, but with data transmission only<br />
after change of data; suppression of nuisance alarms<br />
7 User-friendly process control <strong>and</strong> higher operational reliability,<br />
also in conjunction with multi-screen technology<br />
7 Extended status display through the combination of status<br />
<strong>and</strong> analog values with alarm information<br />
7 Alarm priorities as additional attribute for filtering important<br />
messages<br />
7 Central user management, access control, electronic signature<br />
7 Sign-of-life system status monitoring for subordinate systems<br />
connected to the plant bus<br />
7 <strong>System</strong>-side time synchronization based on UTC (Universal<br />
Time Coordinated)
■ Technical specifications<br />
Definitions<br />
Process object<br />
(PO)<br />
A process object (PO) is a synonym for an operable<br />
<strong>and</strong> observable block with approx. 30 OS variables. It<br />
allows comparison of the quantity framework data of<br />
the engineering system with those of the operator system.<br />
OS Variable An OS variable is a required, defined main memory<br />
location for operating <strong>and</strong> monitoring with the operator<br />
system, which values are read to <strong>and</strong> from.<br />
Measuring<br />
point<br />
The measuring point identifies all the functional units<br />
<strong>and</strong> processing functions (e.g. TIRCAS+: temperature<br />
display, registration, control, alarm <strong>and</strong> switching point<br />
up) required for implementing an automation or process<br />
control task for a process variable (e.g. temperature,<br />
filling level). It has at least one process contact<br />
point <strong>and</strong> is also the point in the plant/process at which<br />
the automation becomes effective through information<br />
acceptance, processing our output actions. In<br />
SIMATIC PCS 7, measuring points are represented by<br />
CFC plans for the basic automation of a special process<br />
control task, e.g. level control - as well as matching<br />
faceplates <strong>and</strong> block symbols for operation <strong>and</strong><br />
monitoring over an operator system.<br />
The number of OS variables belonging to a measuring<br />
point depends on the type of measuring point, i.e. on<br />
the respective process control task. By definition, a<br />
measuring point comprises an average of 50 OS variables,<br />
whereby motors, valves, etc. require fewer <strong>and</strong><br />
controls <strong>and</strong> dosing rates require more variables.<br />
Process objects Measuring points OS Variables<br />
250 160 8,192 (8K)<br />
2.000 1.300 65,536 (64K)<br />
3.000 2.000 102,400 (100K)<br />
5.000 3.000 153,600 (150K)<br />
8.500 5.000 262,144 (256K)<br />
OS quantity framework<br />
Max. number of OS servers / pairs<br />
of servers<br />
Max. number of automation systems<br />
per OS server / pair of servers<br />
Max. number of OS clients<br />
in multi-client mode 1)<br />
(per multi-user system)<br />
Max. number of monitors per operator<br />
station in multi-channel operation<br />
Operator system<br />
1) If every OS client has access to all OS servers/pairs of servers<br />
12<br />
64<br />
32<br />
4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
Max. number of OS areas 64<br />
Number of faceplates per control 1 to 16 (adjustable)<br />
window<br />
Number of trends per trends win- 10<br />
dow<br />
Select time OS area display < 2 s<br />
(100 process symbols)<br />
Max. number of variables/process<br />
objects:<br />
per OS single station 150K / 5,000 POs<br />
per OS server 256K / 8,500 POs<br />
Max. number of configurable indi- 50.000<br />
cations per server<br />
Number of measuring points<br />
per OS single station approx. 3,000<br />
per OS server approx. 5,000<br />
per multi-user system approx. 60,000<br />
High-performance archive system<br />
(cyclic buffer), based on Microsoft<br />
SQL server, for:<br />
Process value archiving in the OS approx. 1,000/s<br />
server<br />
Process value archiving with ar- approx. 5,000/s<br />
chive server<br />
Indications (per server) Steady-state load approx. 10/s<br />
Message peak approx. 3,000 / 4 s<br />
Max. number of archive variables 80.000<br />
(with archive server)<br />
5/3<br />
5
5<br />
Operator system<br />
OS hardware<br />
Introduction<br />
■ Overview<br />
All operator stations are based on st<strong>and</strong>ard PC technology combined<br />
with the Microsoft Windows 2000 operating system. PCs<br />
are offered with different performance levels, which have been<br />
optimized for different functions such as OS single station,<br />
OS client or OS server. The use of st<strong>and</strong>ard components <strong>and</strong> interfaces<br />
from the PC world means that the operator stations are<br />
open for customer <strong>and</strong> sector-specific options <strong>and</strong> expansions.<br />
They can be used in harsh industrial environments as well as in<br />
the office. OS single stations <strong>and</strong> OS clients can be installed<br />
with Multi-VGA graphic cards to permit the process control of<br />
several different plant areas using up to 4 monitors.<br />
■ Design<br />
Single-user system (OS single station)<br />
In a single-user system architecture, all operation <strong>and</strong> monitoring<br />
functions for a complete project (plant/unit) are concentrated<br />
in one station. A FastEthernet RJ45 port is already on board <strong>and</strong><br />
can be used for connecting to an OS LAN (terminal bus). The OS<br />
single station can be connected to the Industrial Ethernet bus in<br />
two ways:<br />
through a CP 1613 communications processor (communication<br />
with max. 64 automation systems) or<br />
through a st<strong>and</strong>ard LAN card (Basic Communication Ethernet<br />
for communication with max. 8 automation systems).<br />
The OS single station can be operated on the plant bus in parallel<br />
with other single-user systems or with a multi-user system architecture.<br />
By using the WinCC/Redundancy program package<br />
it is also possible to operate two OS single stations with redundant<br />
architecture.<br />
Multi-user system with client/server architecture<br />
A multi-user system consists of operator terminals (OS clients),<br />
which receive data (project data, process values, archives,<br />
alarms <strong>and</strong> messages) from one or more OS servers through an<br />
OS LAN (Local Area Network). The OS LAN can share the transmission<br />
medium with the plant bus or it can be designed as a<br />
separate bus (Ethernet with TCP/IP).<br />
5/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
In this architecture, redundant OS servers may be set up to meet<br />
higher availability requirements (hot st<strong>and</strong>by). Critical applications<br />
running on the OS server are monitored by Health Check<br />
for software faults. If a fault is detected, switchover to the redundant<br />
system is triggered. Synchronization of the redundant O<br />
servers takes place automatically <strong>and</strong> at high speed.<br />
OS clients can access the data of not only one OS server/server<br />
pair, but from several OS servers/pairs of servers simultaneously<br />
(multi-client mode). This makes it possible to subdivide a plant<br />
into technological units <strong>and</strong> to distribute the data accordingly to<br />
several OS servers/pairs of servers. In addition to scalability, the<br />
advantage of distributed systems is the ability to decouple plant<br />
areas from each other, which results in higher availability.<br />
SIMATIC PCS 7 supports multi-user systems with up to<br />
12 OS servers or 12 redundant OS pairs of servers. In multi-client<br />
mode, OS clients can access data from one or more of the<br />
12 OS servers/pairs of servers in parallel (up to 32 OS clients simultaneously<br />
on all).<br />
The OS servers are designed in addition with client functions<br />
which permit them to access the data (archives, messages,<br />
tags, variables) from the other OS servers of in the multi-user<br />
system. This means that process graphics on one OS server can<br />
also be linked with variables on other OS servers (area-independent<br />
displays).<br />
Like the OS single stations, the OS servers can be connected to<br />
the Industrial Ethernet plant bus using a communications processor<br />
or a st<strong>and</strong>ard LAN card. A FastEthernet RJ45 port is already<br />
on board <strong>and</strong> can be used for connecting to an OS LAN<br />
(terminal bus).<br />
Additional Archive Server<br />
An operator system may be equipped with an additional, preferably<br />
redundant archive server for process values. Using such an<br />
archive server it is possible to archive approx. 5,000 process<br />
values/s. The archive server is a station on the OS LAN <strong>and</strong> is not<br />
connected to the plant bus. A FastEthernet RJ45 port is already<br />
on board <strong>and</strong> can be used for connecting to the OS LAN.
Operator system<br />
OS hardware<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
OS basic hardware<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The full range of basic hardware presented in the chapter OS Server<br />
"ES/OS/Batch/IT basic devices" is available for the configuration<br />
of operator systems. This basic hardware may be exp<strong>and</strong>ed with<br />
the following options, depending on the customer’s particular requirements<br />
<strong>and</strong> whether the hardware is used as OS single station,<br />
OS server, archive server or OS client:<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Hardware <strong>and</strong> software components for redundant operations<br />
Multi-VGA graphics card for connection of up to 4 monitors<br />
Video Memory, DVD-ROM IDE,<br />
mouse,<br />
FastEthernet RJ45 on board for<br />
Display <strong>and</strong> CRT monitors for office <strong>and</strong> industrial environments<br />
(see the chapter "ES/OS/Batch/IT basic devices")<br />
Signal module for acoustic <strong>and</strong> visual signalling of messages<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Server MUI (Ger-<br />
Chipcard reader for access security<br />
man, English, French, Italian,<br />
Spanish);<br />
SIMATIC PCS 7 preinstalled <strong>and</strong><br />
The archive server is only a station in the OS-LAN, <strong>and</strong> therefore<br />
available only in the st<strong>and</strong>ard version with BCE communication.<br />
on restore DVD<br />
PCS 7 OS Server IL 40 S V2<br />
BCE<br />
Connection to system bus<br />
through Basic Communication<br />
6ES7 650-0GE06-0YX0 D)<br />
Upgrading from BCE to CP 1613 communication<br />
OS single stations <strong>and</strong> OS servers with BCE communication can<br />
be subsequently upgraded for communication with CP 1613.<br />
Items required:<br />
Ethernet (BCE) with FastEthernet<br />
RJ45 network card (PCI card)<br />
PCS 7 OS Server IL 40 S V2 IE<br />
Connection to system bus<br />
through Industrial Ethernet with<br />
6ES7 650-0GE16-0YX0 D)<br />
CP 1613:<br />
PCI card for connecting to Industrial Ethernet<br />
CP 1613 communications processor<br />
S7-1613:<br />
Software for S7 communication for CP 1613<br />
Archive server<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
■ Technical specifications<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics con-<br />
Detailed technical data for single stations, clients <strong>and</strong> servers troller on board with Dynamic<br />
are provided in table form in the chapter "ES/OS/BATCH/IT basic Video Memory, DVD-ROM IDE,<br />
devices".<br />
mouse,<br />
FastEthernet RJ45 on board,<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Server MUI (Ger-<br />
OS Single Station<br />
man, English, French, Italian,<br />
SIMATIC PC in rack of 19“ design,<br />
Spanish);<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
SIMATIC PCS 7 preinstalled <strong>and</strong><br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
on restore DVD<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Video Memory, DVD±RW IDE,<br />
mouse,<br />
FastEthernet RJ45 on board for<br />
PCS 7 OS Server IL 40 S V2<br />
BCE<br />
With Basic Communication Ethernet<br />
(BCE) based on FastEthernet<br />
RJ45 network card (PCI card)<br />
6ES7 650-0GE06-0YX0 D)<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish);<br />
SIMATIC PCS 7 preinstalled <strong>and</strong><br />
on restore DVD<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
PCS 7 ES/OS IL 40 S V2 BCE<br />
Connection to system bus<br />
through Basic Communication<br />
Ethernet (BCE) with FastEthernet<br />
RJ45 network card (PCI card)<br />
6ES7 650-0GC06-0YX0 D)<br />
PCS 7 ES/OS IL 40 S V2 IE<br />
Connection to system bus<br />
through Industrial Ethernet with<br />
CP 1613 communications processor<br />
6ES7 650-0GC16-0YX0 D)<br />
5/5<br />
5
5<br />
Operator system<br />
OS hardware<br />
OS basic hardware<br />
■ Selection <strong>and</strong> Ordering Data<br />
OS Client<br />
Order No.<br />
PCS 7 OS Client IL 40 S V2<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
512 Mbyte RAM (2 x 256 Mbyte),<br />
sound, EIDE hard disk 80 of<br />
80 Gbyte, graphics controller on<br />
board with Dynamic Video Memory,<br />
DVD-ROM IDE, optical<br />
mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish);<br />
SIMATIC PCS 7 preinstalled <strong>and</strong><br />
on restore DVD<br />
Upgrade from BCE to CP 1613<br />
Communication<br />
6ES7 650-0GD06-0YX0 D)<br />
CP 1613<br />
PCI card for connection to Industrial<br />
Ethernet, with AUI/ITP <strong>and</strong><br />
RJ45 connections<br />
6GK1 161-3AA00<br />
S7-1613 for Industrial Ethernet<br />
S7 communication software for<br />
CP 1613,<br />
can be used with<br />
Windows 2000/XP<br />
Single license for 1 installation,<br />
runtime software, software <strong>and</strong><br />
electronic manual on CD-ROM,<br />
license key on diskette, Class A,<br />
bilingual (German/English)<br />
6GK1 716-1CB62-3AA0 D)<br />
5/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data<br />
Additional <strong>and</strong> expansion components<br />
Order No.<br />
Multi-VGA Graphics Card<br />
"2 Screens"<br />
for operating 2 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Dual graphics card, driver CD,<br />
manual, 1 dual DVI cable for<br />
2 digital outputs, 2 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE0 B)<br />
Multi-VGA Graphics Card<br />
"4 Screens"<br />
for operating 4 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Quad graphics card, driver CD,<br />
manual, 2 dual DVI cables for<br />
4 digital outputs, 4 adapters for<br />
VGA outputs<br />
Utility software<br />
SIMATIC PC/PG Image & Partition<br />
Creator<br />
Software for creating hard disk<br />
images <strong>and</strong> for configurating hard<br />
disk partitions<br />
Memory modules for exp<strong>and</strong>ing<br />
the main memory<br />
Memory expansion kit 512<br />
Mbyte (Dual Channel) for SI-<br />
MATIC Rack PC IL 40 S V2 (2 x<br />
256 Mbyte DDR SDRAM)<br />
Memory expansion kit 1 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x<br />
512 Mbyte DDR SDRAM)<br />
Memory expansion kit 2 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x 1 Gbyte<br />
DDR SDRAM)<br />
6ES7 652-0XX03-1XE1 B)<br />
6ES7 648-6AA02-0YX0 B)<br />
6ES7 648-2AD30-0FB0 B)<br />
6ES7 648-2AD40-0FB0 B)<br />
6ES7 648-2AD50-0FB0 B)<br />
TK 200 keyboard (PS/2 connection)<br />
German key assignment 6GF6 710-1AA<br />
International key assignment 6GF6 710-1BA<br />
SIMATIC PC keyboard (USB<br />
connection)<br />
International key assignment 6ES7 648-0CB00-0YA0<br />
3-m power cable for Rack PC 1)<br />
For Great Britain 6ES7 900-0BA00-0XA0<br />
For Switzerl<strong>and</strong> 6ES7 900-0CA00-0XA0<br />
For USA 6ES7 900-0DA00-0XA0<br />
For Italy 6ES7 900-0EA00-0XA0<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
1) The PCS 7 systems are delivered as st<strong>and</strong>ard with a "European power<br />
cable". The country-specific versions listed above are required for some<br />
countries.<br />
Monitors, see chapter "ES/OS/BATCH/IT basic devices“
■ Overview<br />
OS single station <strong>and</strong> OS client can be exp<strong>and</strong>ed with a signal<br />
module. This signal module can operate a horn <strong>and</strong> up to 3 different<br />
lamps or buzzer sounds symbolizing different signal<br />
classes. Together with a hardware timer (watchdog) the signal<br />
module is able to detect <strong>and</strong> signal the failure of an operator station.<br />
A hardware acknowledge key can also be connected.<br />
The signal module occupies one PCI slot in the operator station.<br />
Operator system<br />
OS hardware<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Signal output<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PCI Signal Module<br />
PCI card for installing in an operator<br />
station<br />
6DS1 916-8RR B)<br />
Connecting cable<br />
For connecting an external audio<br />
detector to a signal module<br />
3 m 6XV2 175-8AH30<br />
10 m 6XV2 175-8AN10<br />
32 m 6XV2 175-8AN32<br />
50 m 6XV2 175-8AN50<br />
5/7<br />
5
5<br />
Operator system<br />
OS software<br />
Introduction<br />
■ Overview<br />
■ Function<br />
OS basic hardware <strong>and</strong> OS software are structured by OS single<br />
station, OS server <strong>and</strong> OS client in compliance with the architecture<br />
of the operator system <strong>and</strong> are accordingly coordinated in<br />
this regard.<br />
The optional archive server for process values is based on the<br />
starter software for OS server 250 PO/RT 8K with 512 variables.<br />
The size of the archive can be exp<strong>and</strong>ed by means of additive<br />
Archive PowerPacks to 1,500, 5,000, 30,000 or 80,000 variables.<br />
User Interface<br />
The predefined user interface of the operator system has all the<br />
features typical of a control system. It is multilingual, clearly<br />
structured, ergonomic <strong>and</strong> easy to underst<strong>and</strong>. The operator<br />
can survey the process extremely easily, <strong>and</strong> rapidly navigate<br />
between different views of the plant. He is supported by a picture<br />
tree manager, which organizes the picture hierarchy according<br />
to user requirements <strong>and</strong> permits direct selection of<br />
All operator stations can be equipped in addition with SFC visu-<br />
subordinate areas.<br />
alization.<br />
Process displays <strong>and</strong> measuring points can also be called up by<br />
■ Application<br />
name. An online language selector permits the user to change<br />
the display language dynamically during runtime.<br />
The OS software can be run on the OS basic hardware offered in<br />
this catalog <strong>and</strong> has been tested with it. <strong>Siemens</strong> guarantees the<br />
compatibility of hardware <strong>and</strong> software for system configurations<br />
based on components in this catalog.<br />
A st<strong>and</strong>ard view <strong>and</strong> a server view are available for the technological<br />
representation of a plant, each with variously designed<br />
area overviews. Features provided in both views include:<br />
Message line for display of last message<br />
Should you use basic hardware other than that offered in this cat- Date, time <strong>and</strong> name of the operator<br />
alog, please note the minimum requirements quoted in the chap- Area overview with up to 36/49/64 areas (depending on resoter<br />
"ES/OS/BATCH/IT basic devices".<br />
lution of the process monitor)<br />
If you configure your own SIMATIC PCS 7 operator station<br />
(OS single station/ OS server/ OS client) using other/own hard-<br />
Working area for plant displays <strong>and</strong> movable windows for<br />
faceplates, historic trends, etc.<br />
ware components, you carry full responsibility <strong>and</strong> will not receive<br />
any free support in the event of compatibility problems.<br />
Despite comprehensive tests it cannot be ruled out that the function<br />
of a SIMATIC PCS 7 system may be disturbed or impaired<br />
by additional non-system software, i.e. software not explicitly released<br />
for SIMATIC PCS 7. For this reason, <strong>Siemens</strong> AG warns<br />
against installing non-system software on SIMATIC PCS 7 runtime<br />
systems, <strong>and</strong> does not provide a warranty in the event of any<br />
resulting damage.<br />
Furthermore, the use of non-system software in the SIMATIC<br />
PCS 7 environment is your responsibility. You have no claims for<br />
free support in the event of compatibility problems.<br />
<strong>System</strong> function keys<br />
In a special message view it is possible to switch between control<br />
message pages such as new list, old list, cleared alarm list,<br />
operator action list, control element list <strong>and</strong> message history list.<br />
Trends can be displayed as a full-size picture or as a window in<br />
the working area. Some trends/trend groups are predefined during<br />
plant configuration. The operator is also able, however, to<br />
compile his own trends while online <strong>and</strong> to select them by measuring<br />
point name.<br />
5/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
Messages / alarms<br />
Message priorities are issued as an additional attribute to the<br />
known signal classes in order to make it easier to assess large<br />
quantities of signals <strong>and</strong> to be better able to distinguish important<br />
messages from the less important.<br />
Active messages are signaled by group displays representing<br />
preconfigured views based on signal groups.<br />
The last message to have arrived - or the message with the highest<br />
priority when alarm priorities are utilized - is displayed at the<br />
top edge of the st<strong>and</strong>ard view. A predefined window with further<br />
messages can be called up with the "Extended message line“.<br />
The "Loop-in-alarm" <strong>and</strong> "Select display using measuring point"<br />
functions support the quick evaluation <strong>and</strong> resolution of faults.<br />
Using "Loop-in-alarm“, the operator can jump directly to the process<br />
display in which the fault has occurred, <strong>and</strong> can then call<br />
up the associated faceplate (loop display) through the measuring<br />
point.<br />
Flexible sound setting options support the audible annunciation<br />
of messages/alarms through a soundcard or by controlling external<br />
horns through a signal module.<br />
Operator system<br />
OS software<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
Central user management, access control <strong>and</strong> electronic<br />
signature<br />
(see the chapter "Administration")<br />
SIMATIC Logon offers central user administration with security<br />
<strong>and</strong> access control based on Windows 2000 for the SIMATIC<br />
PCS 7 system components as well as non-SIMATIC components<br />
connected through API. It can be used to fulfill the validation requirements<br />
of 21 CFR Part 11. An electronic signature function<br />
can also be used in conjunction with SIMATIC Logon.<br />
A chipcard reader can be used to provide an additional level of<br />
security for controlling access to the operator stations by checking<br />
the operator privileges stored on a chipcard.<br />
Sign-of-life monitoring<br />
With the "Sign-of-life monitoring function", the operator system is<br />
able to monitor the correct operation of all subordinate systems<br />
connected to the plant bus. A graphical plan configuration display<br />
shows the status of each monitored component.<br />
Time synchronization<br />
The operator system can implement time synchronization based<br />
on UTC (Universal Time Coordinated) (UTC), which is a st<strong>and</strong>ard<br />
feature within the SIMATIC PCS 7 process control system. This<br />
feature is especially beneficial for widely distributed plants<br />
present in different time zones, e.g. pipelines.<br />
Script languages<br />
Visual Basic <strong>and</strong> C are the scripting languages available for custom<br />
programming of OS applications.<br />
5/9<br />
5
5<br />
Operator system<br />
OS software<br />
OS software for single station/server/client<br />
■ Overview<br />
The OS software is adapted to the OS basic hardware (OS single<br />
station, OS server <strong>and</strong> OS client).<br />
The OS software for OS single stations <strong>and</strong> OS servers can be<br />
adapted to plants of various size by changing the number of process<br />
objects (PO). The number of POs can be increased at any<br />
time by adding more PowerPacks in order to allow for higher requirements<br />
of system expansions.<br />
The engineering of the SIMATIC PCS 7 process control system<br />
is usually concentrated in a separate engineering system. In the<br />
case of OS single stations used for small plants, engineering<br />
<strong>and</strong> operator functionality can be combined in one station, except<br />
in the case of redundant systems (engineering software,<br />
see the chapter "<strong>Engineering</strong> system").<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
OS Software Single Station V6.0<br />
Single license for 1 installation, trilingual<br />
(German/English/French)<br />
Electronic documentation on<br />
PCS 7 Toolset CDs <strong>and</strong> PCS 7<br />
Documentation CD<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
Pack 3 for Microsoft Windows<br />
2000 (in 5 languages), Microsoft<br />
Internet Explorer, Microsoft SQL<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
250 POs/RT 8K<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
1) A process object (PO) is a synonym for an operable <strong>and</strong> observable block<br />
with approx. 30 variables.<br />
2) The upgrades OS Software Single <strong>and</strong> OS Software Server support a<br />
high-performance archive system for up to 512 variables. For large<br />
archives this volume can be extended using add-on OS Archive V6.0<br />
Power Packs (see OS Archiving). This applies regardless of whether a<br />
central process value archive server is used or not.<br />
1) OS Software Server Power Pack<br />
V6.0<br />
For exp<strong>and</strong>ing the OS software<br />
for servers<br />
Single license for 1 Installation<br />
trilingual (German, English,<br />
French)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
from 250 POs/RT 8K to 2,000<br />
POs/RT 64K<br />
6ES7 658-2BB06-0YD0<br />
from 2,000 POs/RT 64K to 3,000 6ES7 658-2BC06-0YD0<br />
POs/RT 100K<br />
from 3,000 POs/RT 100K to<br />
5,000 POs/RT 150K<br />
6ES7 658-2BD06-0YD0<br />
from 5,000 POs/RT 150K to 6ES7 658-2BE06-0YD0<br />
8,500 POs/RT 256K<br />
OS Software Client V6.0<br />
Single license for 1 installation ,<br />
trilingual (German, English,<br />
French)<br />
Electronic documentation on PCS<br />
7 Toolset CDs <strong>and</strong> PCS 7 Documentation<br />
CD<br />
6ES7 658-2CX06-0YA0 D)<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
6ES7 658-2AA06-0YA0 D)<br />
Pack 3 for Microsoft Windows<br />
2000 (in 5 languages), Microsoft<br />
2,000 POs/RT 64K<br />
3,000 POs/RT 100K<br />
5,000 POs/RT 150K<br />
6ES7 658-2AB06-0YA0<br />
6ES7 658-2AC06-0YA0<br />
6ES7 658-2AD06-0YA0<br />
D)<br />
D)<br />
D)<br />
Internet Explorer, Microsoft SQL<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
Upgrade of operator software<br />
from V5.x to V6.0<br />
OS Software Single Station<br />
Single license for 1 installation ,<br />
Power Pack V6.0<br />
trilingual (German, English,<br />
For extending the OS software for<br />
French)<br />
a single station<br />
Electronic documentation on PCS<br />
Single license for 1 installation ,<br />
trilingual (German, English,<br />
7 Toolset CDs <strong>and</strong> PCS 7 Documentation<br />
CD<br />
French)<br />
Type of delivery:<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
Pack 3 for Microsoft Windows<br />
from 250 POs/RT 8K to<br />
6ES7 658-2AB06-0YD0<br />
2000 (in 5 languages), Microsoft<br />
2,000 POs/RT 64K<br />
Internet Explorer, Microsoft SQL<br />
from 2,000 POs/RT 64K to 6ES7 658-2AC06-0YD0<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
3,000 POs/RT 100K<br />
Upgrade of OS software for sin-<br />
from 3,000 POs/RT 100K to<br />
5,000 POs/RT 150K<br />
6ES7 658-2AD06-0YD0<br />
gle station with 2,000<br />
POs/RT 64K<br />
OS Software Server V6.0<br />
Single license for 1 installation ,<br />
trilingual (German, English,<br />
French)<br />
Electronic documentation on PCS<br />
7 Toolset CDs <strong>and</strong> PCS 7 Documentation<br />
CD<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
Pack 3 for Microsoft Windows<br />
2000 (in 5 languages), Microsoft<br />
Internet Explorer, Microsoft SQL<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
250 POs/RT 8K 6ES7 658-2BA06-0YA0 D)<br />
2,000 POs/RT 64K 6ES7 658-2BB06-0YA0 D)<br />
3,000 POs/RT 100K 6ES7 658-2BC06-0YA0 D)<br />
5,000 POs/RT 150K 6ES7 658-2BD06-0YA0 D)<br />
8,500 POs/RT 256K 6ES7 658-2BE06-0YA0 D)<br />
2)<br />
6ES7 658-2AB06-0YE0 D)<br />
Upgrade of OS software for single<br />
station with 5,000<br />
POs/RT 150K 2)<br />
Upgrade of OS software for<br />
server 2,000 POs/RT 64K<br />
6ES7 658-2AD06-0YE0 D)<br />
2)<br />
Upgrade of OS software for<br />
server 5,000 POs/RT 150K<br />
6ES7 658-2BB06-0YE0 D)<br />
2)<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
6ES7 658-2BD06-0YE0 D)<br />
Upgrade of OS software for client 6ES7 658-2CX06-0YE0 D)<br />
5/10<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
Operator system<br />
OS software<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
OS archiving<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
A high-performance archive system based on Microsoft SQL OS Software Server V6.0<br />
6ES7 658-2BA06-0YA0 D)<br />
server technology can be configured online to save process val- Single license for 1 installation ,<br />
ues <strong>and</strong> messages in cyclic archives, <strong>and</strong> has an integral ar- trilingual (German, English,<br />
chive backup function for exporting <strong>and</strong> storing old data. The French)<br />
high-performance archive system is usually designed for up to Up to 512 variables<br />
512 variables. The number of variables can be increased with<br />
the help of add-on OS Archive Power Packs.<br />
Electronic documentation on PCS<br />
7 Toolset CDs <strong>and</strong> PCS 7 Docu-<br />
A central process value archive server based on the hardware of<br />
the OS server can be configured in addition with the st<strong>and</strong>ard<br />
software for the OS server (250 POs/RT 8K) <strong>and</strong> add-on OS Archive<br />
Power Packs.<br />
mentation CD<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
Archive servers for process values are operated preferably as<br />
redundant systems.<br />
Pack 3 for Microsoft Windows<br />
2000 (in 5 languages), Microsoft<br />
Internet Explorer, Microsoft SQL<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
OS Archive V6.0 Power Pack<br />
Single license for 1 installation ,<br />
trilingual (German, English,<br />
French)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
from 512 to 1,500 variables 6ES7 658-2EA06-2YD0<br />
from 1,500 to 5,000 variables 6ES7 658-2EB06-2YD0<br />
from 5,000 to 30,000 variables 6ES7 658-2EC06-2YD0<br />
from 30,000 to 80,000 variables 6ES7 658-2ED06-2YD0<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
5/11<br />
5
5<br />
Operator system<br />
OS software<br />
StoragePlus<br />
■ Overview<br />
StoragePlus is a program package for the long-term archiving of<br />
measurement values, messages, reports <strong>and</strong> batch data of the<br />
SIMATIC PCS 7 V6.0 process control system. StoragePlus manages<br />
measurement values, messages <strong>and</strong> OS reports, which<br />
are swapped out of the OS archives, as well as batch data from<br />
SIMATIC BATCH in a central database. All these data can be visualized<br />
in graphic <strong>and</strong> clear manner using the Internet Explorer<br />
<strong>and</strong> be swapped out onto the storage media supported by the<br />
operating system.<br />
■ Application<br />
StoragePlus can be used for the long-term archiving of data from<br />
the SIMATIC PCS 7 V6.0 process control system. For this purpose<br />
StoragePlus has to be installed on a separate computer<br />
with Microsoft Windows 2000 (see "<strong>System</strong> Neutral Components",<br />
chapter "ES/OS/Batch/IT Basic Devices"), which is connected<br />
by OS-LAN/terminal bus to the OS <strong>and</strong> Batch Servers/<br />
single-station systems of the SIMATIC PCS 7 plant.<br />
StoragePlus manages the measurement values, messages <strong>and</strong><br />
OS reports which are swapped out of the OS archives, as well as<br />
batch data from SIMATIC BATCH, in a central database <strong>and</strong><br />
makes these data available independently of the PCS 7 runtime<br />
systems. All the data can be visualized in graphic <strong>and</strong> clear<br />
manner using the Internet Explorer. Data selection is supported<br />
by integrated filter functions. Messages <strong>and</strong> measurement values<br />
can be shown in table form, <strong>and</strong> measurement values also<br />
in graphic form. Tables of measurement values can be exported<br />
in CSV format for processing in other Windows applications, e.g.<br />
Microsoft Excel.<br />
The data managed by StoragePlus can be swapped out onto all<br />
the storage media supported by the operating system. This may<br />
require additional hardware <strong>and</strong> software, e.g. a DVD writer with<br />
suitable burning software.<br />
StoragePlus is able to read in data which were swapped out using<br />
Storage V5.2 <strong>and</strong> to convert the data into the SIMATIC PCS 7<br />
V6.0 data format.<br />
■ Function<br />
Archiving of messages, measurement values <strong>and</strong> reports of<br />
the SIMATIC PCS 7 V6.0 operator systems<br />
Archiving of batch data from SIMATIC BATCH V6.0<br />
Swapping out of all StoragePlus data onto external storage<br />
media<br />
Reading in of swapped-out StoragePlus data from external<br />
storage media<br />
Cataloging of all StoragePlus data<br />
Parameterizing of views (display windows <strong>and</strong> masks) incl. the<br />
selection criteria for displaying the data<br />
5/12<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Visualizing of messages in table form dependent on filter functions<br />
Displaying of measurement values in table or graphic form dependent<br />
on filter functions<br />
Exporting of measurement values in CSV format, e.g. to Microsoft<br />
Excel<br />
Visualizing a batch overview (selecting the detailed protocol<br />
of a batch from the batch overview is possible)<br />
Web-based presentation of data<br />
Access protection with user-specific rights<br />
Migration of messages <strong>and</strong> measurement values from Storage<br />
V5.2<br />
■ Technical specifications<br />
StoragePlus<br />
Long-term archiving Up to 4 OS servers/server pairs<br />
simultaneously<br />
Max. data input (number of archive 400 /s<br />
values) per OS server<br />
Max. data input (number of archive 1,600 /s<br />
values) over all OS servers<br />
Max. data volume input capacity 500 Mbyte<br />
per day<br />
Hardware requirements<br />
Main memory 512 Mbyte <strong>and</strong> higher, 1 Gbyte<br />
recommended<br />
Hard disk memory recommended<br />
Security EIDE-RAID 1 with 2 hard disks for<br />
60 Gbyte <strong>and</strong> higher<br />
Capacity 2 hard disks for 60 Gbyte <strong>and</strong><br />
higher for separating database<br />
<strong>and</strong> log files<br />
Software requirements<br />
Operating system / applications Microsoft Windows 2000 incl.<br />
ServicePack 4<br />
Microsoft Internet Explorer V6.0<br />
incl. ServicePack 1<br />
Microsoft Internet Information<br />
Services (IIS) <strong>and</strong> installed Message<br />
Queuing<br />
Software included in delivery of Microsoft SQL Server 2000 incl.<br />
SIMATIC PCS 7 for which no addi- ServicePack 3<br />
tional license has to be purchased<br />
OS Client SIMATIC PCS 7 V6.0<br />
in connection with StoragePlus<br />
incl. ServicePack 3<br />
SIMATIC BATCH Client Software<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
StoragePlus V1.0<br />
Software for the long-term<br />
archiving of data from the<br />
SIMATIC PCS 7 process control<br />
system<br />
Single license for 1 installation ,<br />
trilingual (German, English,<br />
French)<br />
Type of delivery:<br />
Electronic documentation (German,<br />
English) <strong>and</strong> software on<br />
CD-ROM, certificate of license<br />
<strong>and</strong> authorization diskette<br />
6ES7 652-0XC01-2YA0 C)<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S
■ Overview<br />
The SFC visualization function of the operator system enables<br />
the sequence controls configured with the SFC tool to be displayed<br />
<strong>and</strong> operated in the same way as on the engineering system.<br />
No additional configuration work is necessary. In an overview<br />
display it is possible, for example, to open step <strong>and</strong><br />
transition displays <strong>and</strong> to present step comments or dynamically<br />
supplied stepping conditions.<br />
■ Overview<br />
The SIMATIC Safety Matrix Viewer for SIMATIC PCS 7 serves the<br />
operation <strong>and</strong> monitoring of the SIMATIC Safety Matrix using the<br />
SIMATIC PCS 7 operator system.<br />
Hardware requirements: SIMATIC PCS 7 AS 414H or AS 417H<br />
Software requirements: PCS 7-OS V6.0, SP2 or higher<br />
For further details on the Safety Matrix, please refer to the section<br />
"ES Software – <strong>Engineering</strong> Process Safety" in the chapter<br />
"<strong>Engineering</strong> <strong>System</strong>".<br />
Operator system<br />
OS software<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
SFC visualization<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SFC Visualization V6.0<br />
6ES7 652-0XD06-2YB0<br />
For displaying <strong>and</strong> operating SFC<br />
sequence controls on an operator<br />
station<br />
Single license for 1 installation,<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette<br />
SFC Visualization Upgrade from 6ES7 652-0XD06-2YF0<br />
SIMATIC PCS 7 V5.x to V6.0<br />
Single license for 1 installation<br />
trilingual (German, English,<br />
French)<br />
(software on PCS 7 Toolset CDs,<br />
electronic documentation on<br />
PCS 7 Documentation CD)<br />
Type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette<br />
SIMATIC Safety Matrix Viewer<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC Safety Matrix Viewer<br />
for SIMATIC PCS 7<br />
Operation <strong>and</strong> monitoring of the<br />
Safety Matrix in a SIMATIC PCS 7<br />
environment with several operator<br />
control levels<br />
Bilingual (German, English)<br />
single license for 1 installation,<br />
type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette;<br />
software <strong>and</strong> electronic<br />
documentation on CD<br />
6ES7 833-1SM60-0YA5 C)<br />
5/13<br />
5
5<br />
Operator system<br />
OS software<br />
Connectivity Pack <strong>and</strong> Client Access Licences<br />
■ Overview<br />
St<strong>and</strong>ardized access of process data in the OS single stations/OS<br />
servers by higher-level information systems, office applications<br />
or user-oriented applications is supported by the<br />
PCS 7 operator system with a range of specifications <strong>and</strong> interfaces.<br />
Because the PCS 7 operator system is OPC-compliant, operator<br />
stations can act as OPC servers <strong>and</strong> be the data source for other<br />
applications. The OS single stations <strong>and</strong> OS servers already<br />
have an integral OPC Data Access Server for access to all online<br />
values that correspond to st<strong>and</strong>ards OPC Data Access 1.1<br />
<strong>and</strong> 2.0. Additional open interfaces are also available as an optional<br />
WinCC/Connectivity Pack for access to archive data <strong>and</strong><br />
indications of the operator system.<br />
5/14<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Function<br />
OPC HDA (Historical Data Access Server)<br />
As OPC HDA server, the PCS 7 operator station makes historical<br />
data from the WinCC archive system available to other applications.<br />
The OPC client, e.g. a reporting tool, can selectively request<br />
the required data by specifying the beginning <strong>and</strong> end of<br />
a time interval. A wide range of diverse unit functions, such as<br />
Variance, Mean Value or Integral, allow preprocessing by the<br />
HDA server, thus reducing the communication load.<br />
OPC A&E (Alarm & Events Server)<br />
As OPC A&E server, the PCS 7 operator station forwards WinCC<br />
indications, including all process-accompanying values, to subscribers<br />
at production <strong>and</strong> company management level, where<br />
they can of course also be acknowledged. Filter mechanisms<br />
<strong>and</strong> subscriptions ensure that only selected <strong>and</strong>/or changed<br />
data is transferred.<br />
OLE DB<br />
OLE DB offers easy to implement, st<strong>and</strong>ardized direct access to<br />
the archive data in the MS SQL server database of the operator<br />
system. It also provides access to all WinCC archive data with<br />
the relevant processaccompanying values, message <strong>and</strong> user<br />
texts.<br />
For further information, see catalog ST 80, section "WinCC/Connectivity<br />
Pack" in the chapter "SIMATIC WinCC options".<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
WinCC/Connectivity Pack<br />
Single license for 1 installation<br />
6AV6 371-1DR06-0AX0 C)<br />
■ Design<br />
WinCC/Client Access License<br />
for (office) computers (without<br />
6AV6 371-1ES06-0AX0 C)<br />
Components of the WinCC/Connectivity Pack that can be used<br />
with SIMATIC PCS 7:<br />
WinCC installation) that access<br />
archive <strong>and</strong> alarm data of an<br />
operator station (OS single sta-<br />
OPC HDA (Historical Data Access Server):<br />
tion/ OS server) using OPC HDA,<br />
Data server for historical data from the WinCC archive system<br />
OPC A&E (Alarm & Events Server):<br />
Data server for indications from the WinCC alarm system<br />
OLE-DB<br />
For direct access to the archive data stored in the MS SQL<br />
server database<br />
OPC A&E or OLE-DB<br />
Single license for 1 installation<br />
WinCC/Client Access License<br />
per processor<br />
for client access to archive <strong>and</strong><br />
alarm data of an operator station<br />
(OS single station/ OS server)<br />
6AV6 371-1ES06-0CX0 C)<br />
A WinCC/Connectivity Pack is required for each operator station<br />
(OS single station/OS server) that makes archive <strong>and</strong> alarm data<br />
available over this interface. With SIMATIC PCS 7, however, it is<br />
using OPC HDA, OPC A&E or<br />
OLE-DB<br />
License for any number of clients<br />
per processor<br />
common to use a mulit-client operating system, with<br />
WinCC/Connectivity Pack as the central OPC server. This collects<br />
the data from the OS servers <strong>and</strong> makes it available to OPC<br />
clients. In this case, only the OPC server requires a WinCC/Connectivity<br />
Pack.<br />
A WinCC/Client Access License is also required for each (office)<br />
computer (without WinCC installation) that accesses the archive<br />
<strong>and</strong> alarm data of an operator station (OS single station/<br />
OS server) using OPC HDA, OPC A&E or OLE-DB.<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S
■ Overview<br />
Redundancy for operator systems<br />
The following information should be observed if a redundant operator<br />
station is to be configured:<br />
The WinCC/Redundancy software is required for redundant<br />
OS single stations for alignment of the archives.<br />
An OS Software Redundant Server Pack is required to configure<br />
a redundant OS server.<br />
BCE communication with the FastEthernet card is generally<br />
sufficient even for redundant operator stations. Up to 8 automation<br />
systems can be connected per pair of servers.<br />
Communication using CP 1613 is only required in cases<br />
where<br />
- a subordinate fault-tolerant automation system is connected,<br />
or<br />
- the maximum number of 8 stations per OS is insufficient.<br />
Operator system<br />
Redundant operator systems<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
OS redundancy<br />
An operator station with CP 1613 is delivered with the S7-1613<br />
software. If a subordinate fault-tolerant automation system is<br />
to be connected, the S7-REDCONNECT software is required.<br />
In this case, the S7-REDCONNECT upgrade package must be<br />
ordered.<br />
If an operator station with BCE communication is to be upgraded<br />
for redundant operation with a subordinate fault-tolerant<br />
automation system, the S7-REDCONNECT software is required<br />
in addition to the CP 1613 communications processor.<br />
If the plant bus is to be designed as a redundant dual ring, two<br />
network cards must be installed per OS (2 x FastEthernet card<br />
or 2 x CP 1613).<br />
5/15<br />
5
5<br />
Operator system<br />
Redundant operator systems<br />
OS redundancy<br />
■ Selection <strong>and</strong> Ordering Data<br />
For the configuration of redundant<br />
OS single stations<br />
Order No.<br />
WinCC/Redundancy<br />
For alignment of archives following<br />
OS restart; single license for<br />
2 installations<br />
Installation required on each of<br />
the two redundant OS single stations<br />
6AV6 371-1CF06-0AX0 C)<br />
RS 232 connecting cable, 10 m 6ES7 902-1AC00-0AA0<br />
For the configuration of redundant<br />
OS servers<br />
OS Software Redundant Server<br />
Pack V6.0<br />
Single license for 2 installations,<br />
with OS software server <strong>and</strong><br />
WinCC/Redundancy as well as<br />
RS 232 connecting cable, 10 m<br />
250 POs/RT 8K 6ES7 652-3XA06-2YA0 D)<br />
2,000 POs/RT 64K 6ES7 652-3XB06-2YA0 D)<br />
3,000 POs/RT 100K 6ES7 652-3XC06-2YA0 D)<br />
5,000 POs/RT 150K 6ES7 652-3XD06-2YA0 D)<br />
8,500 POs/RT 256K<br />
Power Packs for PO expansion,<br />
see OS Software Server (2 Power<br />
Packs each required)<br />
WinCC Options V6 manual<br />
Contents: WinCC/User Archives,<br />
WinCC/Server <strong>and</strong><br />
WinCC/Redundancy<br />
6ES7 652-3XE06-2YA0 D)<br />
English 6AV6 392-1DA06-0AB0<br />
5/16<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data<br />
Upgrade package for OS single<br />
stations / OS servers with BCE<br />
for communication with faulttolerant<br />
AS<br />
Order No.<br />
CP 1613<br />
PCI card for connection to Industrial<br />
Ethernet, with AUI/ITP <strong>and</strong><br />
RJ45 connections<br />
6GK1 161-3AA00<br />
S7-REDCONNECT<br />
Software for failsafe S7 communication<br />
through redundant networks,<br />
for CP 1613, can be used<br />
with Windows 2000/XP,<br />
single license for 1 installation,<br />
runtime software, software <strong>and</strong><br />
electronic manual on CD-ROM,<br />
license key on diskette, Class A,<br />
bilingual (German/English)<br />
Upgrade package for OS single<br />
stations / OS servers with CP<br />
1613 for communication with<br />
fault-tolerant AS<br />
6GK1 716-0HB62-3AA0 D)<br />
Upgrade S7-REDCONNECT<br />
Software for expansion of<br />
S7-1613 to S7-REDCONNECT,<br />
can be used with<br />
Windows 2000/XP,<br />
single license for 1 installation,<br />
runtime software, software <strong>and</strong><br />
electronic manual on CD-ROM,<br />
license key on diskette, Class A,<br />
bilingual (German/English)<br />
6GK1 716-0HB62-3AA4 D)<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1
Batch automation<br />
6/2 SIMATIC BATCH<br />
6/2 Introduction<br />
6/3 SIMATIC BATCH hardware<br />
6/5 SIMATIC BATCH software<br />
6/5 Basic Package<br />
6/6 Batch Control Center<br />
6/6 Recipe <strong>System</strong><br />
6/7 Batch Planning<br />
6/7 Hierarchical Recipe<br />
6/8 ROP Library<br />
6/8 Separation Procedures/Formulas<br />
6/8 SIMATIC BATCH API<br />
6/8 Upgrade<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
6<br />
Batch automation<br />
SIMATIC BATCH<br />
Introduction<br />
■ Design<br />
SIMATIC BATCH is configured either as a single-user system or<br />
as a client/server system, <strong>and</strong> can be used in plants of any size<br />
due to its modular architecture <strong>and</strong> flexible scalability in 4 steps<br />
using 150, 600, 1800 <strong>and</strong> >1800 batch process objects (instances<br />
of plant units <strong>and</strong> equipment modules).<br />
A typical batch automation process is comprised of a batch<br />
server <strong>and</strong> several batch clients, which together process a plant<br />
project. The batch server can be configured with redundancy<br />
(hot st<strong>and</strong>by) in order to increase availability.<br />
2/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Integration<br />
SIMATIC BATCH is fully integrated in SIMATIC PCS 7. The plant<br />
data can be configured entirely using the engineering system.<br />
The engineering system passes on all data required for recipe<br />
creation to the batch server, making recipe processing possible<br />
separate from the engineering system. Changes to the configuration<br />
which are made on the engineering system are available<br />
to the batch server using an update function (online/offline).<br />
The hardware of the batch server can be separate from the<br />
OS servers. SIMATIC BATCH clients <strong>and</strong> OS clients can run on<br />
separate or common basic hardware. The PCS 7 operator systems<br />
relevant to the batch are made known to the batch server<br />
during configuration of the batch applications.<br />
SIMATIC BATCH communicates with the automation system<br />
through the PCS 7 operator systems. Operator instructions <strong>and</strong><br />
dialogs can also be integrated into the communication. These<br />
functions can be used to draw attention to necessary operator<br />
inputs, or to offer a facility for data input, e.g. for laboratory values.<br />
SIMATIC BATCH provides special st<strong>and</strong>ard faceplates for<br />
controlling <strong>and</strong> monitoring plant units <strong>and</strong> equipment modules.<br />
SFC instances derived from a SFC-type template are generally<br />
used as the interface to the subordinate automation level. The<br />
properties of the SFC-type, such as modes of operation, setpoints/actual<br />
values, instance parameters, times etc. can be defined<br />
through a properties dialog. However, it is also possible to<br />
use special batch interface blocks for communication with the<br />
processing programs in the automation systems, e.g. for plant<br />
expansions or when connecting non-SIMATIC systems.
■ Design<br />
The modularity <strong>and</strong> flexibility of SIMATIC BATCH are optimally<br />
supported by the hardware available. All the basic hardware<br />
from the chapter "ES/OS/BATCH/IT basic devices" can be used<br />
for SIMATIC BATCH.<br />
For small plants, SIMATIC BATCH can be installed together with<br />
the OS software on a single station system. The hardware for this<br />
OS/BATCH single station can be selected below or in the chapters<br />
"ES/OS/BATCH/IT basic devices" or "Operator system".<br />
Batch process automation typically has a distributed client/server<br />
configuration with one batch server <strong>and</strong> several batch<br />
clients, which together process a plant project. The batch server<br />
of such a configuration can be configured with redundancy (hot<br />
st<strong>and</strong>by) in order to increase availability.<br />
The batch server is only a station in the OS-LAN, <strong>and</strong> therefore<br />
available only in the st<strong>and</strong>ard version with BCE communication.<br />
A FastEthernet RJ45 port is already on board <strong>and</strong> can be used<br />
for connecting to the OS LAN.<br />
Batch automation<br />
SIMATIC BATCH<br />
SIMATIC BATCH hardware<br />
The batch server redundancy is supported by the SIMATIC<br />
BATCH basic package. As with OS redundancy we recommend<br />
you to connect the two redundant servers in addition through the<br />
COM interface using an RS 232 cable (see ordering data for accessories).<br />
Data transmission through this connection has a<br />
positive impact on system performance. No additional hardware<br />
<strong>and</strong> software components from the section "OS server redundancy"<br />
are required.<br />
Multi-VGA graphics card for connecting up to 4 monitors<br />
Display <strong>and</strong> CRT monitors for office <strong>and</strong> industry environments<br />
(see the chapter "ES/OS/BATCH/IT basic devices")<br />
The Multi-VGA graphics cards "2 Screens" <strong>and</strong> "4 Screens" are<br />
offered for multichannel operation of an OS/batch single station<br />
or a batch client with 2 up to 4 process monitors. Plant sections<br />
distributed over 2 or as many as 4 process monitors by means<br />
of a graphics card can be controlled using one keyboard <strong>and</strong><br />
one mouse. The Multi-VGA graphics cards are compliant with<br />
EN 55022 <strong>and</strong> EN 50082 st<strong>and</strong>ards. Each card occupies one<br />
PCI slot in the operator station.<br />
Note:<br />
All signals from SIMATIC BATCH are processed in the operator<br />
system’s signal system, hence there is no need for an additional<br />
signal module.<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/3<br />
6
6<br />
Batch automation<br />
SIMATIC BATCH<br />
SIMATIC BATCH hardware<br />
■ Selection <strong>and</strong> Ordering Data<br />
OS/Batch Single Station<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Video Memory, DVD±RW IDE,<br />
optical mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
Order No.<br />
PCS 7 ES/OS IL 40 S V2 BCE<br />
Connection to plant bus through<br />
Basic Communication Ethernet<br />
(BCE) with FastEthernet RJ45<br />
network card (PCI card)<br />
6ES7 650-0GC06-0YX0 D)<br />
PCS 7 ES/OS IL 40 S V2 IE<br />
Connection to plant bus through<br />
Industrial Ethernet with CP 1613<br />
communications processor<br />
Batch server<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Video Memory, DVD-ROM IDE,<br />
optical mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Server MUI (German,<br />
English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
6ES7 650-0GC16-0YX0 D)<br />
PCS 7 OS Server IL 40 S V2<br />
BCE<br />
Connection to plant bus through<br />
Basic Communication Ethernet<br />
(BCE) with FastEthernet RJ45<br />
network card (PCI card)<br />
Client<br />
6ES7 650-0GE06-0YX0 D)<br />
PCS 7 OS Client IL 40 S V2<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
512 Mbyte RAM (2 x 256 Mbyte),<br />
sound, EIDE hard disk of<br />
80 Gbyte, graphics controller on<br />
board with Dynamic Video Memory,<br />
DVD-ROM IDE, optical<br />
mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
6ES7 650-0GD06-0YX0 D)<br />
2/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data<br />
Additional <strong>and</strong> expansion components<br />
Utility software<br />
Order No.<br />
SIMATIC PC/PG Image & Partition<br />
Creator<br />
Software for creating hard disk<br />
images <strong>and</strong> for configurating hard<br />
disk partitions<br />
6ES7 648-6AA02-0YX0 B)<br />
Memory modules for exp<strong>and</strong>ing<br />
the main memory<br />
Memory expansion kit 512<br />
Mbyte (Dual Channel) for<br />
SIMATIC Rack PC IL 40 S V2<br />
(2 x 256 Mbyte DDR SDRAM)<br />
Memory expansion kit 1 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x<br />
512 Mbyte DDR SDRAM)<br />
Memory expansion kit 2 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x 1 Gbyte<br />
DDR SDRAM)<br />
6ES7 648-2AD30-0FB0 B)<br />
6ES7 648-2AD40-0FB0 B)<br />
6ES7 648-2AD50-0FB0 B)<br />
TK 200 keyboard (PS/2 connection)<br />
German key assignment 6GF6 710-1AA<br />
International key assignment<br />
SIMATIC PC keyboard (USB<br />
connection)<br />
6GF6 710-1BA<br />
International key assignment<br />
3-m power cable for Rack PC<br />
6ES7 648-0CB00-0YA0<br />
1)<br />
For Great Britain 6ES7 900-0BA00-0XA0<br />
For Switzerl<strong>and</strong> 6ES7 900-0CA00-0XA0<br />
For USA 6ES7 900-0DA00-0XA0<br />
For Italy 6ES7 900-0EA00-0XA0<br />
RS 232 connecting cable, 10 m<br />
For connecting the redundant<br />
batch servers through the COM<br />
interface<br />
6ES7 902-1AC00-0AA0<br />
Multi-VGA Graphics Card<br />
"2 Screens“<br />
for operating 2 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Dual graphics card, driver CD,<br />
manual, 1 dual DVI cable for<br />
2 digital outputs, 2 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE0 B)<br />
Multi-VGA Graphics Card<br />
"4 Screens“<br />
for operating 4 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Quad graphics card, driver CD,<br />
manual, 2 dual DVI cables for<br />
4 digital outputs, 4 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE1 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
1) The PCS 7 systems are delivered as st<strong>and</strong>ard with a "European power<br />
cable". The country-specific versions listed above are required for some<br />
countries.<br />
Monitors, refer to chapter "ES/OS/BATCH/IT basic devices“
Batch automation<br />
SIMATIC BATCH software<br />
SIMATIC BATCH software<br />
■ Overview<br />
■ Overview<br />
The basic software for all SIMATIC BATCH system configurations The basic package includes 150 batch POs (instances of plant<br />
is provided in the basic package consisting of 150 batch POs units <strong>and</strong> equipment modules), one BatchCC (batch control<br />
(instances of plant units <strong>and</strong> equipment modules), a BatchCC center) <strong>and</strong> one Recipe <strong>System</strong> (recipe editor). It enables a<br />
(batch control center) <strong>and</strong> a Recipe <strong>System</strong> (recipe editor). It small SIMATIC BATCH project to be implemented on the hard-<br />
provides everything needed to implement a small SIMATIC ware of a single station or on a client-server combination consist-<br />
BATCH project on the hardware of a single station or on a clienting of a batch client <strong>and</strong> a batch server.<br />
server configuration consisting of a batch client <strong>and</strong> a batch<br />
server.<br />
The capacity of the basic package can be extended by means<br />
of PO options <strong>and</strong> Power Packs to batches with 300, 600, 1,800<br />
The capacity of the basic package can be exp<strong>and</strong>ed by means or unlimited POs.<br />
of PO options <strong>and</strong> Power Packs as described in the section "Basic<br />
package". An appropriate number of BatchCC <strong>and</strong> Recipe ■ Selection <strong>and</strong> Ordering Data Order No.<br />
<strong>System</strong> option packages is needed to exp<strong>and</strong> the client/server<br />
configuration with additional batch clients. Option packages are<br />
available to exp<strong>and</strong> single stations, batch clients <strong>and</strong> batch<br />
servers in their functions as well.<br />
SIMATIC BATCH<br />
Basic Package V6.0<br />
(Batch PO 150)<br />
Option packages for single stations, batch servers <strong>and</strong> batch clients:<br />
Single station<br />
Batch<br />
server<br />
Batch client<br />
ROP Library X X<br />
Hierarchical Recipe X X<br />
Separation Procedures/Formulas<br />
SIMATIC BATCH API<br />
X<br />
X<br />
X<br />
X<br />
Batch Planning X X<br />
Batch Control Center X X<br />
Recipe <strong>System</strong> X X<br />
SIMATIC BATCH works closely with the operator system <strong>and</strong><br />
communicates through the operator system with the automation<br />
systems. For small plants, SIMATIC BATCH is therefore installed<br />
together with the OS software on a single station. The ordering<br />
data for the OS software can be found in the chapter "Operator<br />
system".<br />
Redundant SIMATIC BATCH systems cannot be installed on<br />
OS servers, only on separate BATCH servers.<br />
1)<br />
For single station <strong>and</strong> client-<br />
6ES7 657-0SA06-0YA0 D)<br />
server configuration<br />
Single license for 1 installation, trilingual<br />
(German, English, French)<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
Pack 3 for Microsoft Windows<br />
2000 (in 5 languages), Microsoft<br />
Internet Explorer <strong>and</strong><br />
PC Anywhere<br />
SIMATIC BATCH<br />
PO Option V6.0<br />
For expansion of the SIMATIC<br />
BATCH Basic Package<br />
Single license for 1 installation, trilingual<br />
(German, English, French)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
To batch with 300 POs<br />
To batch with 600 POs<br />
6ES7 657-0XE06-2YB0<br />
6ES7 657-0XB06-2YB0<br />
To batch with 1,800 POs 6ES7 657-0XC06-2YB0<br />
To batch with unlimited POs<br />
SIMATIC BATCH<br />
Power Pack V6.0<br />
For expansion of batch POs<br />
Single license for 1 installation, trilingual<br />
(German, English, French)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
6ES7 657-0XD06-2YB0<br />
From batch with 300 POs to<br />
batch with 600 POs<br />
6ES7 657-0XB06-2YD0<br />
From batch with 600 POs to<br />
batch with 1,800 POs<br />
6ES7 657-0XC06-2YD0<br />
From batch with 1,800 POs to<br />
batch with unlimited POs<br />
6ES7 657-0XD06-2YD0<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
1) Whereas process objects (PO) represent operable <strong>and</strong> observable blocks<br />
with approx. 30 variables, batch process objects (batch POs) represent<br />
instances of plant units <strong>and</strong> equipment modules.<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/5<br />
6
6<br />
Batch automation<br />
SIMATIC BATCH software<br />
Batch Control Center<br />
■ Overview<br />
The Batch Control Center (BatchCC) is the "comm<strong>and</strong> center“<br />
for monitoring <strong>and</strong> controlling batch processes with SIMATIC<br />
BATCH. Using BatchCC it is possible to manage all data relevant<br />
to SIMATIC BATCH through a graphical user interface.<br />
2/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Function<br />
BatchCC offers powerful functions for the following tasks:<br />
Reading in <strong>and</strong> updating the plant data of the basic automation<br />
Definition of user privileges for all functions, for clients, or for<br />
plant units of SIMATIC BATCH<br />
Definition of material names <strong>and</strong> codes<br />
Management of master recipes <strong>and</strong> starting the recipe editor<br />
in order to enter the recipe structure<br />
Management of libraries with recipe elements (library operations)<br />
Editing of formula categories <strong>and</strong> management of associated<br />
formulas (parameter sets)<br />
Creation of batches with master recipes<br />
Starting of batch processing <strong>and</strong> controlling of batches<br />
Monitoring <strong>and</strong> diagnostics of batch processing<br />
Recording <strong>and</strong> archiving of recipes <strong>and</strong> batch data<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC BATCH<br />
6ES7 657-0LX06-2YB0<br />
BatchCC V6.0<br />
Single license for 1 installation,<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette
■ Overview<br />
Note:<br />
The Recipe <strong>System</strong> option package is included once in the basic<br />
package.<br />
Batch automation<br />
SIMATIC BATCH software<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Recipe <strong>System</strong><br />
■ Function<br />
The recipe editor can be used to:<br />
Create new master recipes <strong>and</strong> library operations<br />
Modify existing master recipes <strong>and</strong> library operations<br />
(changes of structure or parameters)<br />
Document new master recipes <strong>and</strong> library operations<br />
Carry out plausibility tests<br />
Assign releases for testing or production of master recipes<br />
<strong>and</strong> library operations<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC BATCH<br />
6ES7 657-0AX06-2YB0<br />
Recipe <strong>System</strong> V6.0<br />
Single license for 1 installation,<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
The Recipe <strong>System</strong> option package presents itself to the user in electronic documentation on<br />
the form of a recipe editor. The recipe editor is a convenient tool PCS 7 Documentation CD<br />
for simple, intuitive creation <strong>and</strong> modification of master recipes<br />
Type of delivery: Certificate of<br />
<strong>and</strong> library operations. It has a graphical user interface, editing license <strong>and</strong> authorization diskette<br />
functions typical of those in Microsoft Windows for single <strong>and</strong><br />
group objects, <strong>and</strong> a structural syntax check function.<br />
The basis for recipe creation are the batch objects created from<br />
the batch plant configuration using the SIMATIC PCS 7 engineering<br />
system, e.g. plant units <strong>and</strong> technological functions. The<br />
batch recipe editor can be started individually, but can also be<br />
called from BatchCC.<br />
2/7<br />
6
6<br />
Batch automation<br />
SIMATIC BATCH software<br />
Batch Planning<br />
■ Overview<br />
The basic package enables the creation of individual production<br />
orders <strong>and</strong> batches. Far more planning functionality is offered by<br />
the additional Batch Planning option package. BatchCC can<br />
then be used to plan batches in advance for a large number of<br />
production orders.<br />
2/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Function<br />
The range of functions includes not only the planning but also<br />
the modification, canceling, deleting <strong>and</strong> releasing of batches.<br />
Dividing <strong>and</strong> saving batches for a production can be performed<br />
manually or, after specifying the number of batches <strong>and</strong> the production<br />
quantity, automatically. The following batch parameters<br />
can be selected <strong>and</strong> changed before the release order is given:<br />
Quantity to be prepared<br />
Starting mode (immediately, by operator input or time-controlled)<br />
Plant unit assignment<br />
Formula (parameter set)<br />
Run sequence (interlinking with the previous or next batch)<br />
Indication of batch runtime<br />
Batch planning <strong>and</strong> control are conveniently supported <strong>and</strong> simplified<br />
by special displays such as order category list, production<br />
order list, batch planning list, batch status list <strong>and</strong> batch results<br />
list.<br />
All batches <strong>and</strong> their plant unit assignments can be clearly presented<br />
by a combination of Gantt diagram <strong>and</strong> table. Conflicts<br />
of time or due to multiple assignment of plant units are marked<br />
by symbols. Time conflicts are easily eliminated by moving the<br />
affected batches in the Gantt diagram.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC BATCH<br />
6ES7 657-0BX06-2YB0<br />
Batch Planning V6.0<br />
Single license for 1 installation,<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette
■ Overview<br />
Hierarchical recipes according to ISA S88.01<br />
Batch automation<br />
SIMATIC BATCH software<br />
Hierarchical Recipe<br />
SIMATIC BATCH <strong>and</strong> SIMATIC PCS 7 form a functional unit that<br />
fully covers the models described in the ISA S88.01 st<strong>and</strong>ard.<br />
The hierarchical recipe structure is mapped on the plant module<br />
as follows:<br />
Recipe procedure for controlling the process or the production<br />
in a plant<br />
Partial recipe procedure for controlling a process step or a<br />
plant unit<br />
Recipe operation/function for the process engineering<br />
task/function on an equipment module<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC BATCH<br />
6ES7 657-0FX06-2YB0<br />
Hierarchical Recipe V6.0<br />
Single license for 1 installation,<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The management of recipe operations is conveniently supported<br />
by a user library (ROP library). Library recipe operations<br />
SIMATIC BATCH<br />
ROP Library V6.0<br />
6ES7 657-0GX06-2YB0<br />
can be inserted as a reference in recipe procedures <strong>and</strong> can Single license for 1 installation<br />
thus be modified from a central location. This reduces the requirements<br />
for engineering <strong>and</strong> validation. If the reference link is<br />
trilingual (German, English,<br />
French)<br />
broken, the recipe operation becomes a fixed component of the Software on PCS 7 Toolset CDs,<br />
recipe procedure, <strong>and</strong> is thus independent of further central<br />
modifications.<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
ROB Library<br />
2/9<br />
6
6<br />
Batch automation<br />
SIMATIC BATCH software<br />
Separation Procedures/Formulas<br />
■ Overview<br />
The flexibility achieved by recipes which are independent of<br />
plant units can be increased even further if the procedure <strong>and</strong><br />
parameter sets (formulas) are separated from one another. Various<br />
master recipes can be created by linking several formulas<br />
using a recipe procedure. This enables central modification of<br />
procedures. The formula structure is determined by the formula<br />
category defined by the user.<br />
SIMATIC BATCH API<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The SIMATIC BATCH API application programming interface is<br />
an open interface for custom expansions. It provides the user<br />
SIMATIC BATCH<br />
API V6.0<br />
6ES7 657-0MX06-2YB0<br />
with access to SIMATIC BATCH data <strong>and</strong> functions <strong>and</strong> enables Single license for 1 installation,<br />
the programming of special industry or project specific applications.<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs<br />
Type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette<br />
Upgrade<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Customers who are already using BATCH flexible V4.02 can up- SIMATIC BATCH Upgrade 6ES7 657-0XX06-0YE0 D)<br />
grade to SIMATIC BATCH V6.0. Recipes created with BATCH From BATCH flexible V4.02 to<br />
flexible V4.02 can be converted for use in SIMATIC BATCH V6.0. SIMATIC BATCH V6.0<br />
The interface blocks of BATCH flexible V4.02 can also be used<br />
in SIMATIC BATCH V6.0.<br />
Single license for 1 installation,<br />
trilingual (German, English,<br />
French)<br />
Electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette, PCS 7 Toolset CDs<br />
<strong>and</strong> additional CDs with Service<br />
Pack 3 for Microsoft Windows<br />
2000 (in 5 languages), Microsoft<br />
Internet Explorer, Microsoft SQL<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
2/10<br />
Quantity<br />
Temperature<br />
Time<br />
Salt<br />
Pepper<br />
Sugar<br />
Master Recipe 1<br />
Formula 1<br />
1000 kg<br />
90 °C<br />
10 min<br />
Yes<br />
No<br />
100 g<br />
Formula 2<br />
500 kg<br />
80 °C<br />
15 min<br />
Yes<br />
No<br />
150 g<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Formula 3<br />
900 kg<br />
95 °C<br />
12 min<br />
No<br />
Yes<br />
50 g<br />
Master Recipe 2 Master Recipe 3<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC BATCH<br />
6ES7 657-0HX06-2YB0<br />
Separation Procedures/Formulas<br />
V6.0<br />
Single license for 1 installation,<br />
trilingual (German, English,<br />
French)<br />
Software on PCS 7 Toolset CDs,<br />
electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1
SIMATIC Route Control<br />
7/2 Introduction<br />
7/3 Route Control Hardware<br />
7/5 Route Control Software<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
7<br />
SIMATIC Route Control<br />
Introduction<br />
■ Overview<br />
SIMATIC Route Control adds a tool for the configuration, control,<br />
monitoring <strong>and</strong> diagnostics of material transports in pipeline networks.<br />
It is not specialized on any particular industry.<br />
With SIMATIC Route Control, which can also be combined with<br />
SIMATIC BATCH, users of SIMATIC PCS 7 are capable of automating<br />
not only their production processes <strong>and</strong> associated<br />
warehouses but also the material transports linking both areas.<br />
SIMATIC Route Control can h<strong>and</strong>le complex networks as well as<br />
simple transport routes. In particular SIMATIC Route Control is<br />
predestined for plants with a multitude of complex route combinations<br />
or extensive tank farms such as are found above all in<br />
the chemical, petrochemical <strong>and</strong> food <strong>and</strong> drinks industries.<br />
Preferred applications:<br />
Plants in the medium <strong>and</strong> high capacity range with an extensive<br />
route/pipeline network<br />
Frequent conversions <strong>and</strong> extensions of the transport network<br />
incl.actuators <strong>and</strong> sensors<br />
Transport routes with high flexibility:<br />
- regularly changing materials<br />
- dynamic selection of the source <strong>and</strong> destination of the material<br />
transport (incl. reversing of direction on bidirectional<br />
transport routes)<br />
numerous simultaneous material transports<br />
plant projects in combination with SIMATIC BATCH<br />
7/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Integration<br />
SIMATIC Route Control is fully integrated in SIMATIC PCS 7 <strong>and</strong>,<br />
thanks to the modular architecture <strong>and</strong> 3-step scalability (up to<br />
30 / up to 100 / up to 300 simultaneous material transports), can<br />
be flexibly adapted to different sizes of plant.<br />
SIMATIC Route Control provides graded user authorizations for<br />
engineering, operating <strong>and</strong> maintenance personnel. These authorizations<br />
are integrated in the user administration with SI-<br />
MATIC Logon.<br />
The Route Control <strong>Engineering</strong> Tool, the Route Control Library<br />
<strong>and</strong> the Route Control Wizard are concentrated together with the<br />
other engineering tools of the SIMATIC PCS 7 process control<br />
system in a central engineering system. The configuration of<br />
Route Control builds on the basic configuration of the SIMATIC<br />
PCS 7 process control system using blocks from the PCS 7 St<strong>and</strong>ard<br />
Library. Technological elements of relevance for Route<br />
Control (RC elements) are adapted in the CFC Editor using uniform<br />
interface blocks from the Route Control Library. Even existing<br />
SIMATIC PCS 7 plants are therefore easy to exp<strong>and</strong> with<br />
SIMATIC Route Control.<br />
After the transport network is configured <strong>and</strong> the variants of a<br />
material transport tested, the Route Control configuration data<br />
are transferred to the Route Control Server where they can then<br />
be activated at a suitable time. Configuration changes are taken<br />
immediately into account in the determination of a suitable transport<br />
route after transfer from the Route Control <strong>Engineering</strong> Tool<br />
to the Route Control Server <strong>and</strong> subsequent activation through<br />
the Route Control Center (online loading).<br />
The Route Control Server (RC Server) supplies the Route Control<br />
Clients (Route Control Center) with the necessary data <strong>and</strong><br />
transfers their operations to the automation systems. When a<br />
material transport is requested through the Route Control Center<br />
(RCC), it is the job of the RC Server to dynamically compile a<br />
suitable transport route from the partial routes which were configured<br />
using a map of the automation systems on the basis of<br />
the selected parameters (source, destination <strong>and</strong> intermediate<br />
locations) <strong>and</strong> configured parameters (e.g. material or function<br />
IDs).<br />
In the process displays of the SIMATIC PCS 7 operator systems,<br />
each route block is represented by an RC block symbol <strong>and</strong> an<br />
RC faceplate. Through a route block’s RC block symbol it is possible<br />
to select its RC faceplate <strong>and</strong> through a route block’s RC<br />
faceplate it is possible to select its RCC view.
■ Design<br />
The modularity <strong>and</strong> flexibility of SIMATIC Route Control are optimally<br />
supported by the hardware available. All the basic hardware<br />
from the chapter "ES/OS/BATCH/IT basic devices" can be<br />
used for SIMATIC Route Control.<br />
For small plants, SIMATIC Route Control can be installed either<br />
alone or together with the OS software on a single station system.<br />
The hardware for this OS/RC single station can be selected<br />
below or in the chapters "ES/OS/BATCH/IT basic devices" or<br />
"Operator system".<br />
Distributed multiple-station systems with client/server architecture,<br />
exp<strong>and</strong>able with up to 32 clients per server, are typical for<br />
the automation of material transports with SIMATIC Route Control.<br />
Basically it is possible (except in redundant operation) to<br />
operate an RC Server, Batch Server <strong>and</strong> OS Server on shared<br />
basic hardware. However, availability will be higher <strong>and</strong> performance<br />
better if each component has its own server hardware.<br />
The availability of the RC Server can be further increased<br />
through redundant configuration of the server hardware. SI-<br />
MATIC PCS 7 supports multiple-station systems with up to<br />
12 servers/server pairs.<br />
The Route Control Client is represented by the Route Control<br />
Center (RCC). The RCC can be installed on an OS Client, a<br />
Batch Client or separate client hardware.<br />
RC servers <strong>and</strong> OS/RC single stations can be connected to the<br />
Industrial Ethernet plant bus using a communications processor<br />
or a st<strong>and</strong>ard LAN card.<br />
RC Server redundancy is supported by the SIMATIC Route Control<br />
Server program package. Unlike for OS serve redundancy,<br />
no additional hardware <strong>and</strong> software components are required.<br />
SIMATIC Route Control<br />
Route Control Hardware<br />
The basic hardware (PC basic unit) is exp<strong>and</strong>able according to<br />
the customer’s particular requirements <strong>and</strong> whether the hardware<br />
is used as RC Single Station, RC Server or Batch Client with<br />
the following options:<br />
Multi-VGA graphics card for connecting up to 4 monitors<br />
Display <strong>and</strong> CRT monitors for office <strong>and</strong> industry environments<br />
(see the chapter "ES/OS/BATCH/IT basic devices")<br />
The Multi-VGA graphics cards "2 Screens" <strong>and</strong> "4 Screens" are<br />
offered for multichannel operation of an OS/RC Single Station or<br />
a client with 2 up to 4 process monitors. Views distributed over 2<br />
or as many as 4 process monitors by means of a graphics card<br />
can be controlled using one keyboard <strong>and</strong> one mouse. The<br />
Multi-VGA graphics cards are compliant with EN 55022 <strong>and</strong><br />
EN 50082 st<strong>and</strong>ards. Each card occupies one PCI slot in the operator<br />
station.<br />
Note:<br />
All signals from SIMATIC Route Control are processed in the operator<br />
system’s signal system, hence there is no need for an additional<br />
signal module.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
OS/Route Control Single Station<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Video Memory, DVD±RW IDE,<br />
optical mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
PCS 7 ES/OS IL 40 S V2 BCE<br />
Connection to plant bus through<br />
Basic Communication Ethernet<br />
(BCE) with FastEthernet RJ45<br />
network card (PCI card)<br />
PCS 7 ES/OS IL 40 S V2 IE<br />
Connection to plant bus through<br />
Industrial Ethernet with CP 1613<br />
communications processor<br />
6ES7 650-0GC06-0YX0 D)<br />
6ES7 650-0GC16-0YX0 D)<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
7/3<br />
7
7<br />
SIMATIC Route Control<br />
Route Control Hardware<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Route Control Server<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Video Memory, DVD-ROM IDE,<br />
optical mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Server MUI (German,<br />
English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
PCS 7 OS Server IL 40 S V2<br />
BCE<br />
Connection to plant bus through<br />
Basic Communication Ethernet<br />
(BCE) with FastEthernet RJ45<br />
network card (PCI card)<br />
PCS 7 OS Server IL 40 S V2 IE<br />
Connection to plant bus through<br />
Industrial Ethernet with CP 1613<br />
communications processor<br />
Client<br />
PCS 7 OS Client IL 40 S V2<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
512 Mbyte RAM (2 x 256 Mbyte),<br />
sound, EIDE hard disk of<br />
80 Gbyte, graphics controller on<br />
board with Dynamic Video Memory,<br />
DVD-ROM IDE, optical<br />
mouse,<br />
FastEthernet RJ45 on board for<br />
connection to OS-LAN,<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish); SIMATIC PCS 7 preinstalled<br />
<strong>and</strong> on restore DVD<br />
7/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
6ES7 650-0GE06-0YX0 D)<br />
6ES7 650-0GE16-0YX0 D)<br />
6ES7 650-0GD06-0YX0 D)<br />
■ Selection <strong>and</strong> Ordering Data<br />
Additional <strong>and</strong> expansion components<br />
Utility software<br />
Order No.<br />
SIMATIC PC/PG Image & Partition<br />
Creator<br />
Software for creating hard disk<br />
images <strong>and</strong> for configurating hard<br />
disk partitions<br />
6ES7 648-6AA02-0YX0 B)<br />
Memory modules for exp<strong>and</strong>ing<br />
the main memory<br />
Memory expansion kit 512<br />
Mbyte (Dual Channel) for<br />
SIMATIC Rack PC IL 40 S V2<br />
(2 x 256 Mbyte DDR SDRAM)<br />
Memory expansion kit 1 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x<br />
512 Mbyte DDR SDRAM)<br />
Memory expansion kit 2 Gbyte<br />
(Dual Channel) for SIMATIC<br />
Rack PC IL 40 S V2 (2 x 1 Gbyte<br />
DDR SDRAM)<br />
6ES7 648-2AD30-0FB0 B)<br />
6ES7 648-2AD40-0FB0 B)<br />
6ES7 648-2AD50-0FB0 B)<br />
TK 200 keyboard (PS/2 connection)<br />
German key assignment 6GF6 710-1AA<br />
International key assignment<br />
SIMATIC PC keyboard (USB<br />
connection)<br />
6GF6 710-1BA<br />
International key assignment<br />
3-m power cable for Rack PC<br />
6ES7 648-0CB00-0YA0<br />
1)<br />
For Great Britain 6ES7 900-0BA00-0XA0<br />
For Switzerl<strong>and</strong> 6ES7 900-0CA00-0XA0<br />
For USA 6ES7 900-0DA00-0XA0<br />
For Italy 6ES7 900-0EA00-0XA0<br />
Multi-VGA Graphics Card<br />
"2 Screens“<br />
for operating 2 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Dual graphics card, driver CD,<br />
manual, 1 dual DVI cable for<br />
2 digital outputs, 2 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE0 B)<br />
Multi-VGA Graphics Card<br />
"4 Screens“<br />
for operating 4 process monitors<br />
on 1 station<br />
Type of delivery:<br />
Quad graphics card, driver CD,<br />
manual, 2 dual DVI cables for<br />
4 digital outputs, 4 adapters for<br />
VGA outputs<br />
6ES7 652-0XX03-1XE1 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
1) The PCS 7 systems are delivered as st<strong>and</strong>ard with a "European power<br />
cable". The country-specific versions listed above are required for some<br />
countries.<br />
Monitors, refer to chapter "ES/OS/BATCH/IT basic devices“
■ Overview<br />
Route Control Center<br />
The Route Control Software is structured such that SIMATIC<br />
Route Control can be flexibly adapted to different plant sizes <strong>and</strong><br />
architectures (single/multiple station systems):<br />
Route Control <strong>Engineering</strong> (component of the SIMATIC PCS 7<br />
<strong>Engineering</strong> <strong>System</strong>; see the section "ES Software" in the<br />
chapter "<strong>Engineering</strong> <strong>System</strong>")<br />
Route Control Server<br />
Route Control Center (RCC)<br />
SIMATIC Route Control works closely with the Operator <strong>System</strong>,<br />
hence where small plants are concerned it is possible for the<br />
Route Control Center <strong>and</strong> Route Control Server to be installed<br />
not only on their own but also together with the OS software on a<br />
single station. The ordering data for the OS software can be<br />
found in the chapter "Operator system".<br />
In the case of multiple-station systems it is also possible to operate<br />
the Route Control Server, Batch Server <strong>and</strong> OS Server on<br />
shared basic hardware. However, availability will be higher <strong>and</strong><br />
performance better if they are installed on separate server hardware.<br />
In any case it is impossible to combine a Route Control<br />
Server <strong>and</strong> an OS Server on redundant servers.<br />
The Route Control Server program package suitable for up to<br />
30 simultaneous material transports can be exp<strong>and</strong>ed by means<br />
of add-on Power Packs to meet higher requirements (up to<br />
100 or 300 simultaneous material transports).<br />
The Route Control Client is represented by the Route Control<br />
Center (RCC). The RCC can be installed on an OS Client, a<br />
Batch Client or separate client hardware.<br />
■ Function<br />
SIMATIC Route Control<br />
Route Control Software<br />
Route Control Server<br />
The Route Control Server supplies the RC Clients (RCC) with the<br />
necessary data <strong>and</strong> transfers their operations to the automation<br />
systems. When a material transport is requested through the<br />
RCC, it is the job of the RC Server to dynamically compile a suitable<br />
transport route from the partial routes which were configured<br />
using a map of the automation systems on the basis of the<br />
selected parameters (source, destination <strong>and</strong> intermediate locations)<br />
<strong>and</strong> with due account taken of other parameters (e.g.<br />
function catalogs, function IDs or material IDs) . Configuration<br />
changes can be taken immediately into account in the determination<br />
of a suitable transport route after transfer from the Route<br />
Control <strong>Engineering</strong> Tool to the Route Control Server <strong>and</strong> subsequent<br />
activation through the Route Control Center (online loading).<br />
Route Control Center (RCC)<br />
The RCC can be called either from the faceplate of a route block<br />
or from the start menu. It displays all of a material transport’s relevant<br />
route data <strong>and</strong> error information in several coordinated<br />
views<br />
Key functional features are:<br />
Overview of all RC elements <strong>and</strong> request details<br />
Operation of the selected material transport: Selection of operating<br />
mode: manual/automatic; request, start, stop, continue<br />
<strong>and</strong> end material transport in manual mode; set/change<br />
request parameters (locations: source, destination, intermediate<br />
locations) <strong>and</strong> general properties (function catalog, function<br />
ID, material ID <strong>and</strong> "ignore error") in manual mode; activate/deactivate<br />
sequence functions in manual mode<br />
Diagnostics of material transport request errors caused by<br />
locked RC elements, locked partial routes, inconsistent actuations<br />
or prohibited sequential material<br />
Diagnostics of currently running material transports: color <strong>and</strong><br />
text display of transport route status in the route view of the<br />
RCC; detailed analyses by evaluation of feedback signals<br />
from RC elements<br />
Server functions: Select RC Server, display RC Server status,<br />
update view (read in data again from the RC Server)<br />
Display of the operator who has logged on<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
7/5<br />
7
7<br />
SIMATIC Route Control<br />
Route Control Software<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC Route Control Server<br />
V6.0<br />
for up to 30 simultaneous material<br />
transports 1)<br />
6ES7 658-7FA06-0YB0<br />
For single station <strong>and</strong> clientserver<br />
configuration<br />
Single license for 1 installation, trilingual<br />
(German/English/French)<br />
Software <strong>and</strong> electronic documentation<br />
on CD SIMATIC Route<br />
Control V6.0 (delivered with<br />
SIMATIC Route Control <strong>Engineering</strong><br />
V6.0)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
SIMATIC Route Control Server<br />
Power Pack V6.0<br />
For expansion of the SIMATIC<br />
Route Control Server<br />
Single license for 1 installation, trilingual<br />
(German, English, French)<br />
Software <strong>and</strong> electronic documentation<br />
on CD SIMATIC Route<br />
Control V6.0 (delivered with<br />
SIMATIC Route Control <strong>Engineering</strong><br />
V6.0)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
For up to 100 simultaneous ma- 6ES7 658-7FB06-0YD0<br />
terial transports<br />
For up to 300 simultaneous ma- 6ES7 658-7FC06-0YD0<br />
terial transports<br />
7/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIMATIC Route Control Center<br />
V6.0<br />
Single license for 1 installation, trilingual<br />
(German, English, French)<br />
Software <strong>and</strong> electronic documentation<br />
on CD SIMATIC Route<br />
Control V6.0 (delivered with<br />
SIMATIC Route Control <strong>Engineering</strong><br />
V6.0)<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
6ES7 658-7EX06-0YB0<br />
SIMATIC Route Control <strong>Engineering</strong><br />
V6.0<br />
Single license for 1 installation, trilingual<br />
(German, English, French)<br />
Software <strong>and</strong> electronic documentation<br />
on the CD SIMATIC<br />
Route Control V6.0<br />
Type of delivery:<br />
CD SIMATIC Route Control V6.0,<br />
certificate of license <strong>and</strong> authorization<br />
diskette;<br />
6ES7 658-7DX06-0YA0 D)<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
Note :<br />
Detailed information on SIMATIC Route Control <strong>Engineering</strong> V6.0, see "ES<br />
Software" in the chapter "<strong>Engineering</strong> <strong>System</strong>".
IT world<br />
8/2 SIMATIC IT<br />
8/3 @PCS 7<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
8<br />
SIMATIC IT<br />
2/2<br />
IT world<br />
■ Overview<br />
■ Design<br />
SIMATIC IT Production Suite<br />
The SIMATIC IT Production Suite, consisting of the SIMATIC IT<br />
Framework <strong>and</strong> the SIMATIC IT Components, is <strong>Siemens</strong>’ practical<br />
implementation of the requirements of the internationally<br />
recognized MES st<strong>and</strong>ard ISA 95.<br />
7 SIMATIC IT Framework permits modeling of the physical plant<br />
<strong>and</strong> all manufacturing processes in line with the ISA 95 model.<br />
The core component of the SIMATIC IT Framework is the customer’s<br />
plant model which permits direct underst<strong>and</strong>ing of<br />
plant operation.<br />
7 SIMATIC IT Components offer fundamental <strong>and</strong> reliable MES<br />
functionality. Each component is designed for specific parts of<br />
the production process. As a whole, they cover the ISA 95<br />
st<strong>and</strong>ard production functions.<br />
The SIMATIC IT range is rounded off by products which can also<br />
be marketed as st<strong>and</strong>-alone programs independent of the SI-<br />
MATIC IT Production Suite:<br />
SIMATIC IT Historian<br />
Integration <strong>and</strong> synchronization of all business processes Plant Information Management <strong>System</strong> (PIM) for recording,<br />
using SIMATIC IT<br />
saving <strong>and</strong> analyzing process <strong>and</strong> production data<br />
Manufacturing Execution <strong>System</strong>s (MES) permit effective inte- SIMATIC IT Unilab<br />
gration of production processes <strong>and</strong> merch<strong>and</strong>ise management Laboratory Information Management <strong>System</strong> (LIMS)<br />
systems, <strong>and</strong> support the coordination of all resources <strong>and</strong> ap- SIMATIC IT Interspec<br />
plications relevant to manufacturing during all phases of produc- Specifications Management <strong>System</strong> (PLM) for product specition.fications<br />
Using SIMATIC IT – the Manufacturing Execution <strong>System</strong> from SIMATIC IT Framework can integrate components from other<br />
<strong>Siemens</strong> – customers are able to model their complete produc- vendors as well as existing applications such that they can be<br />
tion know-how, exactly define their flow of operations, <strong>and</strong> col- used in the same manner as SIMATIC IT Components.<br />
lect data in real-time from the Enterprise Resource Planning <strong>System</strong><br />
(ERP) <strong>and</strong> from the production department. Manufacturers<br />
can therefore control their plants much more effectively, <strong>and</strong> in- ■ More information<br />
crease their flexibility. As a result of faster <strong>and</strong> more appropriate<br />
You can obtain further information from:<br />
response to all production events, SIMATIC IT helps companies<br />
to reduce downtimes, waste <strong>and</strong> reworking, to optimize ware- Marketing Germany<br />
house stock, <strong>and</strong> to respond more rapidly to customer inquiries. Manfred Graeter<br />
E-mail: manfred.graeter@siemens.com<br />
■ Benefits<br />
European help line : +49 (0) 180 5050 111<br />
<strong>Siemens</strong> <strong>Automation</strong> <strong>and</strong> <strong>Drives</strong><br />
SIMATIC IT from <strong>Siemens</strong> offers decisive advantages. Firstly,<br />
<strong>Automation</strong> Solutions MES<br />
even complex business <strong>and</strong> production structures can be mod-<br />
Viale Cembrano, 11<br />
eled simply, <strong>and</strong> future modifications can also be efficiently inte-<br />
I-16148 Genoa, Italy<br />
grated. Secondly, the model developed for users – i.e. the map-<br />
Tel.: +39 010 3434-1<br />
ping of their business <strong>and</strong> production processes – remains<br />
Fax.: +39 010 383 115<br />
completely transparent, underst<strong>and</strong>able <strong>and</strong>, in particular, inde-<br />
E-mail: marketing.simatic-it@siemens.com<br />
pendent of the system which it controls. Thirdly, the model can<br />
therefore be used uniformly at all sites of a company: processes<br />
can be st<strong>and</strong>ardized throughout the company, <strong>and</strong> best practices<br />
utilized.<br />
Additional information is available in the Internet under:<br />
SIMATIC IT is uniform from modeling up to implementation, for<br />
the model itself executes <strong>and</strong> controls the subsequent MES application.<br />
This shortens the project duration, avoids implementation<br />
errors, provides documentation without gaps, <strong>and</strong> thus effectively<br />
protects the contributed know-how. In this manner,<br />
SIMATIC IT reduces the total cost of ownership of an MES imple-<br />
http://www.siemens.com/simatic-it<br />
mentation, <strong>and</strong> provides additional safeguarding of investments.<br />
Libraries can be used to save the plant <strong>and</strong> production models<br />
defined by SIMATIC IT Framework at any time for simple reuse<br />
in other projects. This significantly reduces introduction <strong>and</strong><br />
maintenance costs as well as the duration of a project.<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
■ Overview<br />
Company-wide availability of process data with @PCS 7<br />
@PCS 7 offers a simple, cost-effective solution for remote access<br />
to the process data that resides in the SIMATIC PCS 7 system.<br />
The data can be displayed <strong>and</strong> processed further on any<br />
computer with any operating system using the st<strong>and</strong>ard software<br />
package @aGlance – even through the intranet/Internet.<br />
@aGlance is integrated in an @PCS 7 server on every operator<br />
station of SIMATIC PCS 7 . To read the data, the target PC requires<br />
only a Web@aGlance package <strong>and</strong> a st<strong>and</strong>ard Web<br />
browser. For writing <strong>and</strong> communication with other @aGlance<br />
servers, the operator station must have a corresponding license.<br />
Upon integration of @aGlance/IT, the SIMATIC PCS 7 can communicate<br />
with a large number of software products for the plant<br />
management/company management level. @PCS 7 provides<br />
customers with access through the @aGlance interface to the<br />
PCS 7 operator system data, including the achieves <strong>and</strong> messages.<br />
An intelligent log-on procedure provides the @aGlance product<br />
range with plug <strong>and</strong> play interfacing while incorporating safety<br />
features. Security <strong>and</strong> access privileges are programmed using<br />
a powerful administration tool.<br />
A further advantage of the open architecture of the client/server<br />
technology is the ability to select the operating systems or applications<br />
on the server or at the client end of the @aGlance/IT software<br />
package. This also means that the implementation of<br />
@aGlance is independent of any existing hardware <strong>and</strong> software<br />
architecture. Hence there is no dependence on specific suppliers<br />
or systems, including those that already exist in the company<br />
<strong>and</strong> may be introduced in the future. The costs of a possible<br />
change of system can be avoided.<br />
■ Benefits<br />
@PCS 7 offers the following benefits:<br />
7 @PCS 7 makes process data available to the operational management<br />
/ company management levels on a client/server basis.<br />
7 @PCS 7 makes process data available throughout the company.<br />
The process data can be visualized, analyzed <strong>and</strong> processed<br />
further from each office desktop.<br />
7 @PCS 7 permits access to all data of the PCS 7 operator stations,<br />
e.g. to archived data.<br />
7 Any client/server application that has an @aGlance interface<br />
can be connected to @PCS 7.<br />
7 @PCS 7 is based on @aGlance technology; @aGlance has established<br />
itself as one of the de facto st<strong>and</strong>ards for interface<br />
software (Middleware) for Internet connections.<br />
7 Users can develop their own custom client/server applications<br />
based on the @aGlance product range.<br />
■ Design<br />
IT world<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
@PCS 7<br />
SIMATIC PCS 7 offers several different versions of @PCS 7:<br />
@PCS 7 Web Read Access<br />
is integrated in the OS software <strong>and</strong> offers reading Internet/Intranet<br />
access to OS data (process data, messages, archived<br />
data)<br />
@PCS 7 Web Write Access option package<br />
provides writing access in addition to reading access to<br />
OS data<br />
@PCS 7 Full Client Access option package<br />
enables communication with @aGlance/IT client applications,<br />
e.g. with the InfoPlus.21 information management system<br />
@PCS 7 Server To Server Communication option package<br />
enables communication with server applications of the<br />
@aGlance/IT server add-ons<br />
Notes:<br />
For @PCS 7 to be run with an OS single station, the software<br />
has to be installed on the computer in question. The clients of<br />
@PCS 7 can communicate with the server in both local <strong>and</strong> remote<br />
modes.<br />
@PCS 7 can be used together with WinCC outside the<br />
SIMATIC PCS 7 environment.<br />
If @PCS 7 is not installed on a SIMATIC PCS 7 operator station,<br />
WinCC is required in addition on the @PCS 7 computer.<br />
2/3<br />
8
8<br />
@PCS 7<br />
2/4<br />
IT world<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
@PCS 7 Web Write Access<br />
Single license for 1 installation, trilingual<br />
(German/English/French)<br />
Electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license, authorization diskette,<br />
PCS 7 Toolset CDs <strong>and</strong> additional<br />
CDs with Service Pack 3 for<br />
Microsoft Windows 2000 (in 5 languages),<br />
Microsoft Internet<br />
Explorer <strong>and</strong> PC Anywhere<br />
6ES7 658-0DX06-0YA0 C)<br />
@PCS 7 Full Client Access<br />
Single license for 1 installation, trilingual<br />
(German/English/French)<br />
Electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license, authorization diskette,<br />
PCS 7 Toolset CDs <strong>and</strong> additional<br />
CDs with Service Pack 3 for<br />
Microsoft Windows 2000 (in 5 languages),<br />
Microsoft Internet<br />
Explorer <strong>and</strong> PC Anywhere<br />
6ES7 658-0EX06-0YA0 C)<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
@PCS 7 Server to Server Communication<br />
Single license for 1 installation, trilingual<br />
(German/English/French)<br />
Electronic documentation on<br />
PCS 7 Documentation CD<br />
Type of delivery: Certificate of<br />
license, authorization diskette,<br />
PCS 7 Toolset CDs <strong>and</strong> additional<br />
CDs with Service Pack 3 for<br />
Microsoft Windows 2000 (in 5 languages),<br />
Microsoft Internet<br />
Explorer <strong>and</strong> PC Anywhere<br />
6ES7 658-0FX06-0YA0 C)<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S
Communication<br />
9/2 Introduction<br />
9/3 Industrial Ethernet<br />
9/3 Introduction<br />
9/4 Fast Ethernet<br />
9/7 FastConnect<br />
9/8 <strong>System</strong> Connection PCS 7 systems<br />
9/9 PROFIBUS<br />
9/9 Introduction<br />
PROFIBUS DP<br />
9/9 Introduction<br />
9/10 Electrical networks<br />
9/11 Fiber optic cable<br />
9/12 Plastic fiber optic cable<br />
9/13 AS connection<br />
9/14 Y-link<br />
PROFIBUS PA<br />
9/15 Introduction<br />
9/16 Basic components<br />
9/19 AS-Interface<br />
9/18 FastConnect/SpliTConnect<br />
9/19 Other communication<br />
9/20 EIB instabus<br />
9/21 Modbus<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
9<br />
Communication<br />
Introduction<br />
■ Overview<br />
Communication within SIMATIC PCS 7 utilizes the SIMATIC NET<br />
networking components. Based on proven worldwide st<strong>and</strong>ards,<br />
it provides a communication concept that guarantees reliable<br />
data transfer between all levels <strong>and</strong> locations within a<br />
plant.<br />
All SIMATIC NET products have been specially developed for industrial<br />
applications <strong>and</strong> are optimized for all industries <strong>and</strong><br />
plants.<br />
The network components meet high st<strong>and</strong>ards, especially in areas<br />
where the components are subject to external influences,<br />
such as:<br />
interfering electromagnetic fields,<br />
corrosive liquids <strong>and</strong> atmospheres,<br />
explosion hazards <strong>and</strong><br />
high levels of contamination <strong>and</strong>/or mechanical loads.<br />
The SIMATIC NET buses promote consistent, trouble-free communication<br />
between all system components:<br />
engineering <strong>and</strong> operator stations,<br />
automation systems, peripherals <strong>and</strong> field components.<br />
9/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Industrial Ethernet communication is typically used for the system<br />
bus. When integrated in small systems, it allows Ethernet<br />
functionality without a communications processor in the ES/OS.<br />
State-of-the-art Fast Ethernet technology is used with SIMATIC<br />
PCS 7 to meet high data throughput dem<strong>and</strong>s in medium <strong>and</strong><br />
large-sized plants, while providing all the advantages of a high<br />
communication speed of 100 Mbit/s, switching technology, <strong>and</strong><br />
the reliability of redundant optical rings.<br />
PROFIBUS DP/PA, which complies with the international st<strong>and</strong>ard<br />
IEC 61158, is used for the I/O bus <strong>and</strong> for field device connections,<br />
respectively. Both implementations allow the connection<br />
of bus-based field devices in potentially explosive areas.<br />
This enables production sectors to be equipped with absolutely<br />
uniform, consistent communication from all automation levels;<br />
from the field level up to the operations management level.
■ Overview<br />
Industrial Ethernet is used as the bus for the SIMATIC PCS 7 process<br />
control system. Industrial Ethernet is a powerful cell network<br />
based on the IEEE 802.3 st<strong>and</strong>ard.<br />
Note:<br />
Detailed information on Industrial Ethenet <strong>and</strong> the bus components<br />
can be found in the IK PI catalog, in the A&D Mall or in<br />
CA 01 at "Communication/Networks / SIMATIC NET communication<br />
systems".<br />
■ Benefits<br />
With a market share of over 80%, Ethernet is todays leading network<br />
for LAN applications worldwide. Thanks to its characteristics,<br />
Ethernet provides a number of significant benefits for the<br />
user:<br />
Fast commissioning through simple connections<br />
High availability because existing installations can be exp<strong>and</strong>ed<br />
without affecting their operation.<br />
Virtually unlimited communications capacity through scalability<br />
using switching technology<br />
Networking of different application domains, such as office<br />
<strong>and</strong> shopfloor.<br />
Company-wide communication through connection to WAN<br />
(wide area network), e.g. ISDN or Internet.<br />
Investment protection through ongoing compatible development<br />
SIMATIC NET offers major expansions of the Ethernet system for<br />
harsh industrial environments:<br />
Network components for use in these special environmental<br />
conditions<br />
Fast local assembly using the FastConnect cabling system<br />
with RJ45 technology<br />
Failsafe networks through high-speed redundancy<br />
Continuous monitoring of network components using a simple<br />
but effective signal concept<br />
■ Technical specifications<br />
Communication<br />
Industrial Ethernet<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
Plant bus / OS-LAN Industrial Ethernet<br />
Number of stations 1,023 per network segment<br />
(IEEE 802.3)<br />
Length of the network<br />
Local network Electrical: up to approx. 1.5 km<br />
Optical: up to approx. 150 km<br />
WAN Worldwide with TCP/IP<br />
Topology Line, tree, ring, star, redundant<br />
ring<br />
9/3<br />
9
9<br />
Communication<br />
Industrial Ethernet<br />
Fast Ethernet<br />
■ Overview<br />
The components used for the SIMATIC PCS 7 bus support modern<br />
Fast Ethernet technology.<br />
The advantages of Fast Ethernet are:<br />
High communication speed of 100 Mbit/s<br />
Switching technology<br />
Redundancy through optical rings<br />
The growing popularity of Fast Ethernet (100 Mbit/s) is owed to<br />
its great similarity with the well-known Ethernet. Data format <strong>and</strong><br />
access procedures are the same. Industrial twisted pair (ITP)<br />
<strong>and</strong> fiberoptic (FO) cables can be used <strong>and</strong> existing technology<br />
expertise can be leveraged. This reduces the costs, the work<br />
load <strong>and</strong> the learning effort associated with Fast Ethernet implementation.<br />
OSM optical switch modules from the SIMATIC NET range are a<br />
simple <strong>and</strong> cost-effective way of connecting existing plants or<br />
plant units with 10 Mbit/s Ethernet (triaxial cables, OLM, star<br />
hubs) to communication networks with 100 Mbit/s Fast Ethernet.<br />
OSM thus enables you to introduce 100 Mbit/s technology one<br />
step at a time.<br />
9/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Application<br />
Industrial Ethernet optical switch modules (OSM) enable the<br />
configuration of switched networks with 100Mbit/s in the control<br />
level area where high requirements are imposed on network<br />
availability <strong>and</strong> extensive diagnosis options are needed.<br />
With segmentation (splitting a network into subnetworks/segments)<br />
<strong>and</strong> connecting these segments to an Industrial Ethernet<br />
OSM, load separation <strong>and</strong> an increased performance can be<br />
achieved in existing networks.<br />
The redundancy manager integrated in the OSM allows the assembly<br />
of redundant optical Industrial Ethernet ring structures in<br />
switching technology with fast media redundancy (reconfiguration<br />
time max. 0.3 seconds). The data rate in the ring is<br />
100Mbit/s; up to 50 Industrial Ethernet OSMs per ring can be<br />
used.<br />
In addition to the 2 ring ports, Industrial Ethernet OSMs have<br />
other ports (optionally with RJ45, ITP or BFOC interface) to<br />
which both terminals <strong>and</strong> network segments can be connected.<br />
Selection support for the various product versions of OSM is provided<br />
by the table in the section "Technical data“.<br />
The Optical Media Converters (OMC) convert an electrical<br />
twisted pair interface into an optical interface. It is thus possible<br />
to connect a station with RJ45-TP interface to one of the 8 optical<br />
ports of an OSM BC08.<br />
The Industrial Ethernet Electrical Switch Modules (ESM) enable<br />
the design of electrical rings. The data rate in the ring is likewise<br />
100Mbit/s; up to 50ESMs per ring can be used. In addition to the<br />
2 ring ports, the ESMs have other ports to which both terminals<br />
<strong>and</strong> network segments can be connected.<br />
Optical <strong>and</strong> electrical transmission media<br />
FIBER OPTIC CABLE) is preferably used as optical transmission<br />
medium. The st<strong>and</strong>ard cables are suitable for overground installation<br />
in the outdoor <strong>and</strong> indoor area. They are available in fixed<br />
lengths, preassembled with 4 BFOC connectors.<br />
The data packages arriving from a bus station are only relayed<br />
to the port to which the receiver is connected. The redundant,<br />
optical ring topology enhances the reliability of a network; communication<br />
is maintained even if a fiberoptic cable breaks.<br />
The terminals are connected through industrial twisted pairs<br />
(ITPs). The preassembled ITP st<strong>and</strong>ard cable with Sub-D connectors<br />
is available for connection between stations <strong>and</strong> network<br />
components. Line lengths of up to 100 m can be achieved while<br />
saving on patch technology.<br />
The ITP st<strong>and</strong>ard cable 9/15 is equipped with a 9-pin <strong>and</strong> a<br />
15-pin connector. The cable is used for direct connection of terminals<br />
with ITP interface to Industrial Ethernet components with<br />
ITP interface.<br />
The ITP XP st<strong>and</strong>ard cable 9/9 is equipped with two 9-pin connectors.<br />
This cable is crossed for direct connection of two Industrial<br />
Ethernet network components with ITP interface.<br />
The ITP XP st<strong>and</strong>ard cable 15/15 is equipped with two 15-pin<br />
connectors. This cable is crossed for direct connection of two<br />
terminals with ITP interface.<br />
The Industrial Ethernet ITP connectors have Sub-D connectors<br />
made of metal <strong>and</strong> are available in two versions:<br />
9-pin connector with straight outgoing cable, for connection to<br />
OSM/ESM, OLM or ELM<br />
15-pin connector with variable outgoing cable, for connection<br />
to terminals with ITP interface<br />
Alternatively, the terminals can also be connected to twisted pair<br />
(TP cord) cables. Detailed information on TP cord cables can be<br />
found in the IK PI catalog, in the A&D Mall or in CA 01 at "Communication/Networks<br />
/ SIMATIC NET communication systems".
■ Technical specifications<br />
Selection support for product versions of OSM <strong>and</strong> ESM<br />
Type <strong>and</strong> number Preferentially for use<br />
of ports<br />
Sub-D (ITP)<br />
RJ45 (TP)<br />
Multimode DO<br />
1) TP cable inside a switchgear cabinet<br />
2) For cross-building connection of Fast Ethernet networks with OSM<br />
3) For design of an optical network, where TP cable (max. 6 m) are only<br />
used inside switchgear cabinets<br />
4) Connects a station with RJ45-TP interface to one of the 8 optical ports of<br />
an OSM BC08<br />
5) Inside buildings<br />
6) Inside switchrooms<br />
Singlemode FO<br />
with<br />
high<br />
EMC<br />
loading<br />
for<br />
plant<br />
bus<br />
for<br />
OS-<br />
LAN<br />
OSM TP22 –- 2 2 –- 1)<br />
OSM ITP62 (st<strong>and</strong>ard) 6 –- 2 –-<br />
OSM TP62 –- 6 2 –-<br />
OSM ITP62-LD 6 –- –- 2<br />
OSM ITP53 5 –- 3 –- 2) 2)<br />
OSM BC08 –- –- 8 –- 3) 3) 3)<br />
OMC TP11 –- 1 1 –- 4) 4) 4)<br />
ESM ITP80 8 –- –- –- 5)<br />
ESM TP40 –- 4 –- –- 6)<br />
ESM TP80 –- 8 –- –- 6)<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
OSM TP22 for<br />
6GK1 105-2AE00<br />
Industrial Ethernet<br />
Optical switch module with<br />
2 fiberoptic ports 100 Mbit/s,<br />
2 RJ45 ports 10/100 Mbit/s <strong>and</strong><br />
4 digital inputs; redundant<br />
DC 24 V supply <strong>and</strong> signal contact;<br />
with network management<br />
OSM ITP62 for<br />
6GK1 105-2AA10<br />
Industrial Ethernet<br />
Optical switch module with<br />
2 fiberoptic ports 100 Mbit/s,<br />
6 ITP ports 10/100 Mbit/s <strong>and</strong><br />
8 digital inputs; redundant<br />
DC 24 V supply <strong>and</strong> signal contact;<br />
with network management<br />
OSM TP62 for<br />
6GK1 105-2AB10<br />
Industrial Ethernet<br />
Optical switch module with<br />
2 fiberoptic ports 100 Mbit/s,<br />
6 RJ45 ports 10/100 Mbit/s <strong>and</strong><br />
8 digital inputs; redundant<br />
DC 24 V supply <strong>and</strong> signal contact;<br />
with network management<br />
OSM ITP62-LD for<br />
6GK1 105-2AC10<br />
Industrial Ethernet<br />
Optical switch module with<br />
2 fiberoptic ports 100 Mbit/s long<br />
distance (single-mode fiberoptic<br />
cable up to 26 km), 6 ITP ports<br />
10/100 Mbit/s <strong>and</strong> 8 digital inputs;<br />
redundant DC 24 V supply <strong>and</strong><br />
signal contact; with network management<br />
Communication<br />
Industrial Ethernet<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
OSM ITP53 for<br />
6GK1 105-2AD10<br />
Industrial Ethernet<br />
Optical switch module with<br />
3 fiberoptic ports 100 Mbit/s,<br />
5 ITP ports 10/100 Mbit/s <strong>and</strong><br />
8 digital inputs; redundant<br />
DC 24 V supply <strong>and</strong> signal contact;<br />
with network management,<br />
for cross-building connection of<br />
two Fast Ethernet networks with<br />
OSM<br />
Industrial Ethernet ESM TP40 6GK1 105-3AC00<br />
Electrical switch module with<br />
4 RJ45 ports 10/100 Mbit/s <strong>and</strong><br />
4 digital inputs; redundant<br />
DC 24 V supply <strong>and</strong> signal contact;<br />
with network management,<br />
preferably for OS-LAN<br />
Industrial Ethernet ESM ITP80 6GK1 105-3AA10<br />
Electrical switch module with<br />
8 ITP ports 10/100 Mbit/s <strong>and</strong><br />
8 digital inputs; redundant<br />
DC 24 V supply <strong>and</strong> signal contact;<br />
with network management,<br />
preferably for OS-LAN<br />
Industrial Ethernet ESM TP80 6GK1 105-3AB10<br />
Electrical switch module with<br />
8 RJ45 ports 10/100 Mbit/s <strong>and</strong><br />
8 digital inputs; redundant<br />
DC 24 V supply <strong>and</strong> signal contact;<br />
with network management,<br />
preferably for OS-LAN<br />
OSM BC08 for<br />
6GK1 105-4AA00<br />
Industrial Ethernet<br />
Optical switch module with<br />
8 fiberoptic ports 100 Mbit/s <strong>and</strong><br />
8 digital inputs; redundant<br />
DC 24 V supply <strong>and</strong> signal contact;<br />
with network management<br />
Industrial Ethernet OMC TP11 6GK1 100-2AB00<br />
Optical media converter RJ45 on<br />
multimode fiberoptic cable<br />
(BFOC) with 100 Mbit/s up to<br />
3km;<br />
redundant DC 24 V supply <strong>and</strong><br />
signal contact<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Fast Ethernet<br />
9/5<br />
9
9<br />
Communication<br />
Industrial Ethernet<br />
Fast Ethernet<br />
■ Selection <strong>and</strong> Ordering Data<br />
Optical transmission media<br />
FIBER OPTIC CABLE<br />
st<strong>and</strong>ard cable, splittable<br />
Preassembled with 4 BFOC connectors<br />
Preferred lengths<br />
Order No.<br />
1 m 6XV1 820-5BH10 B)<br />
5 m 6XV1 820-5BH50 B)<br />
10 m 6XV1 820-5BN10 B)<br />
20 m 6XV1 820-5BN20 B)<br />
50 m 6XV1 820-5BN50 B)<br />
BFOC Connector Set<br />
For FIBER OPTIC CABLE,<br />
20 st<strong>and</strong>ard cables<br />
Electrical transmission media<br />
ITP St<strong>and</strong>ard Cable for Industrial<br />
Ethernet<br />
Not preassembled, sold by the<br />
meter<br />
6GK1 901-0DA20-0AA0 B)<br />
2 x 2-core, without connectors<br />
For connection of a terminal; for<br />
self-assembly of connectors or for<br />
the connection between patch<br />
panel <strong>and</strong> socket<br />
ITP St<strong>and</strong>ard Cable 9/15<br />
ITP installation cable for direct<br />
connection of terminals with ITP<br />
interface to Industrial Ethernet<br />
network components<br />
with ITP interface; with a 9-pin<br />
<strong>and</strong> a 15-pin Sub-D plug<br />
6XV1 850-0AH10<br />
2 m 6XV1 850-0BH20<br />
5 m 6XV1 850-0BH50<br />
8 m 6XV1 850-0BH80<br />
12 m 6XV1 850-0BN12<br />
15 m 6XV1 850-0BN15<br />
20 m 6XV1 850-0BN20<br />
30 m 6XV1 850-0BN30<br />
40 m 6XV1 850-0BN40<br />
50 m 6XV1 850-0BN50<br />
60 m 6XV1 850-0BN60<br />
70 m 6XV1 850-0BN70<br />
80 m 6XV1 850-0BN80<br />
90 m 6XV1 850-0BN88<br />
100 m 6XV1 850-0BT10<br />
9/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
ITP XP St<strong>and</strong>ard Cable 9/9<br />
Crossed ITP installation cable for<br />
direct connection of two Industrial<br />
Ethernet network components<br />
with ITP interface;<br />
with two 9-pin Sub-D plugs<br />
2 m 6XV1 850-0CH20<br />
5 m 6XV1 850-0CH50<br />
8 m 6XV1 850-0CH80<br />
12 m 6XV1 850-0CN12<br />
15 m 6XV1 850-0CN15<br />
20 m 6XV1 850-0CN20<br />
30 m 6XV1 850-0CN30<br />
40 m 6XV1 850-0CN40<br />
ITP XP st<strong>and</strong>ard cable 15/15<br />
Crossed ITP installation cable for<br />
direct connection of two terminals<br />
with ITP interface;<br />
with two 15-pin sub-D plugs<br />
2 m 6XV1 850-0DH20<br />
6 m 6XV1 850-0DH60<br />
10 m 6XV1 850-0DN10<br />
ITP Connector for Industrial<br />
Ethernet<br />
9-pin, for connection to<br />
6GK1 901-0CA00-0AA0<br />
OSM/ESM, OLM or ELM<br />
15-pin, for connection to termi- 6GK1 901-0CA01-0AA0<br />
nals with ITP interface<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
For other lengths of the FIBER OPTIC CABLE <strong>and</strong> other fiberoptic cables,<br />
see the IK PI catalog.<br />
Note:<br />
Supplementary components for the SIMATIC NET cable range can be ordered<br />
from your local contact person. For technical support, please contact:<br />
J. Hertlein, A&D SE V22<br />
Tel.: +49 (911) 750 44 65<br />
Fax: +49 (911)750 99 91<br />
E-mail: juergen.hertlein@siemens.com
■ Overview<br />
IE FC RJ45 plug with 90° outgoing cable (left) <strong>and</strong> with 180° outgoing<br />
cable (right)<br />
Industrial Ethernet FastConnect is a system for fast, easy assembly<br />
of Industrial Ethernet FC cables. The FastConnect stripping<br />
method enables fast <strong>and</strong> easy connection of the Industrial<br />
Ethernet FC cable to the RJ45 connection elements. Terminals<br />
<strong>and</strong>/or network components are connected through TP cord cables.<br />
Using the FC Stripping Tool it is possible to remove the outer<br />
casing <strong>and</strong> the woven shield accurately in a single step. The<br />
prepared cable is connected using the Industrial Ethernet<br />
FastConnect RJ45 Plugs.<br />
The FastConnect RJ45 Plugs enable fast <strong>and</strong> easy fitting of the<br />
FastConnect installation cables in the field. The Industrial Ethernet<br />
FastConnect Stripping Tool for preparing the cable end<br />
(stripping of cable sheath <strong>and</strong> shield in one operation) enables<br />
easy h<strong>and</strong>ling <strong>and</strong> fast error-free contacting of the cable on the<br />
plug-in connector. The plug-in connector has no parts that can<br />
get lost; fitting is thus possible even in difficult conditions.<br />
Another way to switch over RJ45 to the insulation displacement<br />
system is to use the FastConnect Outlet RJ45.<br />
Detailed information on TP cord cables <strong>and</strong> the FastConnect<br />
Outlet RJ45 can be found in the IK PI catalog, in the A&D Mall or<br />
in CA 01 at "Communication/Networks / SIMATIC NET communication<br />
systems".<br />
You will find other specifications of the network topology in the<br />
manual for TP <strong>and</strong> fiberoptic networks.<br />
Communication<br />
Industrial Ethernet<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
FastConnect<br />
■ Design<br />
Industrial Ethernet FastConnect RJ45 Plugs are available in two<br />
versions:<br />
with 180° (straight) outgoing cable,<br />
with 90° (offset) outgoing cable.<br />
They enable optimum connection of an Industrial Ethernet Fast-<br />
Connect cable to terminals <strong>and</strong> network components. The plugs<br />
have a robust, industry-compatible metal casing that protects<br />
the data communication effectively from interference. Contacting<br />
of the FC cable versions is simple <strong>and</strong> reliable with the 4 integrated<br />
insulation displacement contacts. The stripped end of<br />
the cable is inserted in the raised insulation displacement terminal<br />
<strong>and</strong> the terminal pressed down to make reliable contact with<br />
the conductor.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Industrial Ethernet<br />
6XV1 840-2AH10<br />
FC St<strong>and</strong>ard Cable<br />
TP installation cable for connection<br />
to Industrial Ethernet<br />
FC Outlet RJ45 for universal use,<br />
4-core, shielded,<br />
sold by the meter<br />
Max. delivery unit<br />
1000 m,<br />
minimum order 20 m<br />
Preferred length 1,000 m 6XV1 840-2AU10<br />
Industrial Ethernet<br />
6GK1 901-1GA00<br />
FC Stripping Tool<br />
Preset stripping tool for rapid<br />
stripping of insulation from Industrial<br />
Ethernet FC cables<br />
Industrial Ethernet<br />
6GK1 901-1GB00<br />
FC Blade Cassettes<br />
Spare blade cassettes for the<br />
FC stripping tool, 5 cassettes<br />
IE FC RJ45 Plug 180<br />
RJ45 plug-in connector for Industrial<br />
Ethernet with robust metal<br />
housing <strong>and</strong> integrated insulation<br />
displacement contacts for connecting<br />
Industrial Ethernet FC<br />
installation cables; with 180° outgoing<br />
cable; for network components<br />
<strong>and</strong> CPs/CPUs with<br />
Industrial Ethernet interface<br />
1 pack = 1 unit 6GK1 901-1BB10-2AA0<br />
1 pack = 10 units 6GK1 901-1BB10-2AB0<br />
1 pack = 50 units 6GK1 901-1BB10-2AE0<br />
IE FC RJ45 Plug 90<br />
RJ45 plug-in connector for Industrial<br />
Ethernet with robust metal<br />
housing <strong>and</strong> integrated insulation<br />
displacement contacts for connecting<br />
Industrial Ethernet FC<br />
installation cables; with 90° outgoing<br />
cable<br />
1 pack = 1 units 6GK1 901-1BB20-2AA0<br />
1 pack = 10 units 6GK1 901-1BB20-2AB0<br />
1 pack = 50 units 6GK1 901-1BB20-2AE0<br />
Industrial Ethernet<br />
See the IK PI catalog<br />
FC Outlet RJ45<br />
Documentation<br />
Manual<br />
for TP <strong>and</strong> fiberoptic networks<br />
Network architecture, components,<br />
configurations, installation<br />
German 6GK1 970-1BA10-0AA0<br />
English 6GK1 970-1BA10-0AA1<br />
9/7<br />
9
9<br />
Communication<br />
Industrial Ethernet<br />
<strong>System</strong> Connection PCS 7 systems<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The CP 443-1 communications module is used for connecting <strong>System</strong> Connection AS<br />
SIMATIC PCS 7 automation systems to Industrial Ethernet. CP 443-1<br />
6GK7 443-1EX11-0XE0<br />
The following selection criteria apply for connecting operator<br />
systems (single stations / server) <strong>and</strong> engineering systems to<br />
Industrial Ethernet:<br />
Communications module for connection<br />
of SIMATIC S7-400 to<br />
Industrial Ethernet through<br />
TCP/IP, ISO <strong>and</strong> UDP; for S7 com-<br />
The supplied FastEthernet card is sufficient for basic communications<br />
(connection of up to 8 lower-level automation systems).<br />
An alternative is to use a CP 1612 communications<br />
module incl. SOFTNET S7 software for Industrial Ethernet.<br />
munication, S5-compatible communication<br />
(SEND/RECEIVE) with<br />
FETCH/ WRITE with or without<br />
RFC 1006, diagnostics expansion,<br />
Multicast, commissioning<br />
If a maximum of 8 automation systems per operator system is<br />
not enough or a fault-tolerant automation system needs to be<br />
through LAN 10/100 Mbit/s, with<br />
electronic manual on CD-ROM<br />
connected you will need a CP 1613 communications module<br />
(see picture).<br />
S7-1613 software is required to operate the CP 1613.<br />
S7 REDCONNECT software is required instead to operate a<br />
<strong>System</strong> Connection OS/ES<br />
CP 1612<br />
PCI card for connection to Industrial<br />
Ethernet (10/100 Mbit/s), with<br />
6GK1 161-2AA00 B)<br />
fault-tolerant automation system. <strong>System</strong>s with S7-1613 soft- RJ45 connection<br />
ware, e.g. preassembled operator systems, can be upgraded<br />
to this software with an S7 REDCONNECT upgrade.<br />
SOFTNET S7 for<br />
Industrial Ethernet<br />
Software for S7 <strong>and</strong> S5-compatible<br />
communication, for CP 1612,<br />
can be used with Windows<br />
2000/XP,<br />
single license for 1 installation,<br />
runtime software, software <strong>and</strong><br />
electronic manual on CD-ROM,<br />
license key on diskette, Class A,<br />
bilingual (German/English)<br />
6GK1 704-1CW62-3AA0 D)<br />
CP 1613<br />
PCI card for connection to Industrial<br />
Ethernet (10/100 Mbit/s), with<br />
AUI/ITP <strong>and</strong> RJ45 connections<br />
6GK1 161-3AA00<br />
S7-1613 for Industrial Ethernet<br />
S7 communication software for<br />
CP 1613,<br />
can be used with Windows<br />
2000/XP,<br />
single license for 1 installation,<br />
runtime software, software <strong>and</strong><br />
electronic manual on CD-ROM,<br />
license key on diskette, Class A,<br />
bilingual (German/English)<br />
6GK1 716-1CB62-3AA0 D)<br />
S7-REDCONNECT<br />
Software for failsafe S7 communication<br />
through redundant networks,<br />
for CP 1613, can be used<br />
with Windows 2000/XP,<br />
single license for 1 installation,<br />
runtime software, software <strong>and</strong><br />
electronic manual on CD-ROM,<br />
license key on diskette, Class A,<br />
bilingual (German/English)<br />
6GK1 716-0HB62-3AA0 D)<br />
Upgrade S7-REDCONNECT<br />
Software for expansion of<br />
S7-1613 to S7-REDCONNECT,<br />
can be used with<br />
Windows 2000/XP,<br />
single license for 1 installation,<br />
runtime software, software <strong>and</strong><br />
electronic manual on CD-ROM,<br />
license key on diskette, Class A,<br />
bilingual (German/English)<br />
6GK1 716-0HB62-3AA4 D)<br />
9/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1
■ Overview<br />
Communication at field level with PROFIBUS<br />
Distributed peripherals such as I/O modules, measurement<br />
transducers, drives, valves or operator terminals communicate<br />
with the automation systems at field level through a powerful<br />
real-time bus system. This communication is characterized by<br />
the cyclic transmission of process data <strong>and</strong> the acyclic transmission<br />
of alarms, parameters <strong>and</strong> diagnostic data.<br />
PROFIBUS is predestined for these tasks because it enables<br />
high-speed communication with the distributed I/Os by means of<br />
a communications protocol (PROFIBUS DP), <strong>and</strong> permits direct<br />
connection of bus-capable intelligent field devices, including<br />
power supply in accordance with IEC 61158 (PROFIBUS PA).<br />
PROFIBUS is simple, rugged <strong>and</strong> reliable, <strong>and</strong> supports online<br />
parameterization of the distributed components, communication<br />
with HART field devices, redundancy <strong>and</strong> failsafe structures. It<br />
enables online expansions with new distributed components<br />
<strong>and</strong> can be used in st<strong>and</strong>ard environments or in hazardous areas.<br />
On account of these characteristics, PROFIBUS is now established<br />
in all sectors of the production, process <strong>and</strong> hybrid industries<br />
<strong>and</strong> has become the most successful open field bus in<br />
the world. This is confirmed by the more than 10 million<br />
PROFIBUS DP nodes <strong>and</strong> the more than 320,000 PROFIBUS PA<br />
nodes installed to date.<br />
■ Benefits<br />
SIMATIC PCS 7 utilizes the benefits of the PROFIBUS from start<br />
to finish:<br />
Optimal distributed system structure: Small space requirement,<br />
less cabling effort<br />
Effective engineering through st<strong>and</strong>ardization of the process<br />
signals, diagnostics <strong>and</strong> profiles<br />
Shorter commissioning times through short loop checks, easy<br />
parameterization <strong>and</strong> the elimination of calibration work<br />
Optimal life cycle management through best possible diagnostics<br />
<strong>and</strong> preventive maintenance<br />
■ Application<br />
Communication<br />
PROFIBUS<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
The PROFIBUS DP field bus enables the SIMATIC PCS 7 automation<br />
systems to communicate with distributed I/Os from the<br />
ET 200 range (remote I/Os) as well as with field/process devices,<br />
CPUs/CPs <strong>and</strong> operator terminals that have a PROFIBUS DP interface.<br />
The intrinsically safe version (PROFIBUS DP/iS) can be<br />
taken into Ex zone 1 when used with an additional field bus isolating<br />
transformer. Connection of the intelligent, distributed<br />
field/process devices <strong>and</strong> operator terminals on PROFIBUS PA<br />
to the automation system takes place likewise through<br />
PROFIBUS DP.<br />
Depending on the type of automation system <strong>and</strong> the number of<br />
available slots, up to 4 PROFIBUS DP lines can be connected to<br />
a SIMATIC PCS 7 automation system through internal interfaces<br />
in the CPU, <strong>and</strong> up to 10 PROFIBUS DP lines through additional<br />
CP 443-5 Extended communication modules. On a<br />
PROFIBUS DP line it is possible to operate up to 125 devices<br />
<strong>and</strong> on a bus segment up to 31 devices with PROFIBUS DP interface<br />
(32 stations).<br />
Electrical <strong>and</strong> optical transmission technologies offer many different<br />
configuration options for PROFIBUS DP networks. Electrical<br />
networks can span up to approx. 10 km. Network lengths of<br />
up to approx. 100 km are possible in combination with optical<br />
transmission technologies. With SIMATIC PCS 7, PROFIBUS DP<br />
topologies are always configured through the st<strong>and</strong>ard electrical<br />
PROFIBUS DP connection on the automation system in the form<br />
of electrical or mixed (electrical/optical) networks. In the case of<br />
mixed networks, the transition between the two media is implemented<br />
by OLM. As regards communication between the stations,<br />
there is no difference between electrical two-wire technology<br />
<strong>and</strong> fiber optic technology.<br />
Following topologies are configurable: Line, tree, ring, star, redundant<br />
9/9<br />
9
9<br />
Communication<br />
PROFIBUS DP<br />
Electrical networks<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Shielded twisted-pair cables are used as the transmission medium<br />
for electric PROFIBUS DP networks. The PROFIBUS DP<br />
PROFIBUS FastConnect St<strong>and</strong>ard<br />
Cable<br />
6XV1 830-0EH10<br />
stations are connected to these bus lines through a bus connec- St<strong>and</strong>ard type with special design<br />
tor (max. 32 stations per segment).<br />
Individual bus segments can be interconnected through repeaters.<br />
for fast mounting, 2-core,<br />
shielded, sold by the meter<br />
Specify length in m<br />
Max. delivery unit 1,000 m, mini-<br />
If required, a diagnostics repeater can be used for detailed dimum<br />
order quantity 20 m<br />
agnostics of PROFIBUS DP segments. It performs physical on- Preferred lengths<br />
line monitoring of the copper bus cables. In the event of a fault it<br />
sends a diagnostics message to the DP master containing detailed<br />
data on the fault type <strong>and</strong> fault location.<br />
-20 m<br />
-50 m<br />
6XV1 830-0EN20<br />
6XV1 830-0EN50<br />
Bus segments are terminated by the active RS 485 terminating<br />
-100 m 6XV1 830-0ET10<br />
element.<br />
-200 m 6XV1 830-0ET20<br />
RS485-iS<br />
-500 m 6XV1 830-0ET50<br />
The RS485-iS coupler is a field bus isolating transformer that en-<br />
Other PROFIBUS cables See the IK PI catalog<br />
ables PROFIBUS to be run intrinsically safely in hazardous ar- PROFIBUS FastConnect Strip- 6GK1 905-6AA00<br />
eas. The 6ES7972-0DA30-0XA0 plug with special (passive) terping Tool<br />
minating resistor is required to terminate the RS 485-iS.<br />
Preset stripping tool for rapid<br />
FastConnect<br />
stripping of PROFIBUS FastConnect<br />
bus cables<br />
PROFIBUS FastConnect is a system for fast <strong>and</strong> easy assembly<br />
of PROFIBUS copper cables. The system comprises compatible<br />
PROFIBUS FastConnect<br />
Blade Cassettes<br />
6GK1 905-6AB00<br />
components<br />
Spare blade cassettes for the<br />
FastConnect st<strong>and</strong>ard cable for fast assembly<br />
FastConnect stripping tool<br />
with FastConnect blade cassettes<br />
FastConnect PROFIBUS bus connector<br />
PROFIBUS FastConnect stripping<br />
tool<br />
PROFIBUS FastConnect Bus<br />
Connector RS 485 with 90°<br />
cable outlet<br />
With insulation displacement system,<br />
max. data transfer rate 12 Mbit/s<br />
Without PG interface 6ES7 972-0BA50-0XA0<br />
With PG interface 6ES7 972-0BB50-0XA0<br />
PROFIBUS FastConnect RS 485<br />
bus connector Plug 180<br />
With 180° cable outlet, with insulation<br />
displacement system, for<br />
connection of PC, PG, OP<br />
Other bus connectors<br />
See the IK PI catalog<br />
6GK1 500-0FC00<br />
RS 485 Repeater for PROFIBUS<br />
Data transfer rate up to max. 12<br />
Mbit/s,<br />
DC 24 V, IP20 housing<br />
6ES7 972-0AA01-0XA0<br />
Diagnostic Repeater RS 485<br />
For connection of up to 2 segments<br />
to PROFIBUS DP; with<br />
online diagnostics function for the<br />
monitoring of bus cables<br />
6ES7 972-0AB01-0XA0<br />
Active RS 485 Terminating Element<br />
for PROFIBUS<br />
For terminating bus segments for<br />
data transfer rates of 9.6 Kbit/s to<br />
12 Mbit/s<br />
6ES7 972-0DA00-0AA0<br />
RS485-iS Coupler<br />
PROFIBUS must be run intrinsically<br />
safely in hazardous areas<br />
through installation of a field bus<br />
isolating transformer<br />
6ES7 972-0AC80-0XA0<br />
Bus Connector<br />
Connector with special (passive)<br />
terminating resistor for terminating<br />
the RS485-iS<br />
6ES7 972-0DA30-0XA0<br />
9/10<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
Communication<br />
PROFIBUS DP<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Fiber optic cable<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Glass fiberoptic cables are 2-fiber cables for optical PROFIBUS<br />
networks in the indoor <strong>and</strong> outdoor area.<br />
FIBER OPTIC CABLE<br />
st<strong>and</strong>ard cable, splittable<br />
Preassembled with 4 BFOC con-<br />
The st<strong>and</strong>ard FIBER OPTIC CABLE is available in fixed lengths, nectors<br />
preassembled with 4 BFOC connectors. A BFOC connector set<br />
with 20 connectors is also available.<br />
Preferred lengths<br />
1 m 6XV1 820-5BH10 B)<br />
Optical Link Module<br />
5 m 6XV1 820-5BH50 B)<br />
Optical Link Modules (OLM) permit the construction of optical<br />
<strong>and</strong> hybrid (electrical/optical) networks in line, tree, ring or star<br />
topology. The maximum distance between two OLMs can be up<br />
10 m<br />
20 m<br />
6XV1 820-5BN10<br />
6XV1 820-5BN20<br />
B)<br />
B)<br />
to 15 km. The PROFIBUS OLM/G12 is equipped with one RS 485<br />
interface <strong>and</strong> two glass fiberoptic cable interfaces (4 BFOC<br />
sockets). The OLM enables a fiberoptic line length of up to<br />
3,000 m. Errors are quickly located by means of signal contacts<br />
<strong>and</strong> a measurement output.<br />
50 m<br />
Other lengths <strong>and</strong> cables<br />
BFOC Connector Set<br />
6XV1 820-5BN50<br />
See the IK PI catalog<br />
B)<br />
1)<br />
For st<strong>and</strong>ard <strong>and</strong> trailing FIBER<br />
OPTIC CABLES, 20 pcs<br />
6GK1 901-0DA20-0AA0 B)<br />
PROFIBUS OLM/G12<br />
Optical link module with 1 x RS<br />
485 <strong>and</strong> 2 x glass FOC interfaces<br />
(4 BFOC sockets), for st<strong>and</strong>ard<br />
distances up to 3,000 m, with signal<br />
contact <strong>and</strong> measuring output<br />
6GK1 502-3CB10 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
1) Note: You can order supplementary components for the SIMATIC NET<br />
range of cables from your local partner.<br />
Technical advice can be obtained from:<br />
J. Hertlein, A&D SE V22<br />
Tel.: +49 (911) 750 44 65, Fax: +49 (911)750 99 91<br />
E-mail: juergen.hertlein@siemens.com<br />
9/11<br />
9
9<br />
Communication<br />
PROFIBUS DP<br />
Plastic fiber optic cable<br />
■ Overview<br />
■ Design<br />
SIMATIC NET plastic fiberoptic cables can be used for the con- Different versions of plastic FOC are available:<br />
struction of optical PROFIBUS DP networks for indoor applications.<br />
Plastic fiberoptic cables are easy to assemble on-site with<br />
2 x 2 simplex connectors. The maximum cable length between<br />
two DP devices is 50 m.<br />
PROFIBUS plastic fiber optic st<strong>and</strong>ard cable<br />
rugged round cable with purple PVC outer casing <strong>and</strong> Kevlar<br />
tension-relief elements as well as plastic fibers with rugged<br />
polyamide inner casing. For indoor applications with cable<br />
Using SIMATIC PCS 7, plastic fiberoptic cables are an alterna- lengths up to 50 m<br />
tive for automation system connections of ET 200M with only failsafe<br />
I/O modules when compliance with SIL 3 is dem<strong>and</strong>ed for<br />
the failsafe application. Plastic fiberoptic cables are then used to<br />
connect the ET 200Ms through Optical Bus Terminals (OBT) to<br />
the electrical bus cable of the PROFIBUS DP. The advantage of<br />
this configuration is that it eliminates the disconnecting module<br />
for decoupling the signal between the IM <strong>and</strong> the failsafe mod-<br />
PROFIBUS plastic fiberoptic, duplex core<br />
flat double core with PVC inner casing <strong>and</strong> no outer casing, for<br />
indoor applications with low mechanical loads, e.g. inside<br />
cabinets. Cable length up to 50 m.<br />
To use the plastic FOC, following items are required in addition<br />
to the OBT:<br />
ules, which is otherwise obligatory for the direct electrical con- Simplex connector/polishing set (set with 100 simplex connection<br />
of the ET 200M (only failsafe modules in a rack with nectors <strong>and</strong> 5 polishing sets)<br />
IM 153-2).<br />
Stripping tool set for removing the outer casing <strong>and</strong> core casing<br />
Plug adapter for using simplex connectors with the integrated<br />
FO interfaces (e.g. IM 153-2 FO)<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PROFIBUS OBT<br />
Optical bus terminal for connecting<br />
a PROFIBUS station or an<br />
RS 485 segment without integrated<br />
optical interface to the<br />
optical PROFIBUS; without simplex<br />
connector<br />
6GK1 500-3AA00<br />
PROFIBUS Plastic Fiber Optic,<br />
St<strong>and</strong>ard Cable<br />
Robust round cable with 2 plastic<br />
fiberoptic cores, PVC external<br />
sheath <strong>and</strong> PA internal sheath,<br />
without connectors, for indoor<br />
6XV1 821-0AH10 B)<br />
use, sold by the meter<br />
OBT for PROFIBUS DP<br />
PROFIBUS Plastic Fiber Optic, 6XV1 821-2AN50 B)<br />
With the OBT (Optical Bus Terminal) for PROFIBUS it is possible Duplex Core<br />
to connect a PROFIBUS DP station with an integrated optical in- Plastic fiberoptic cable with<br />
terface to an RS 485 segment or a PROFIBUS DP station without 2 cores, PVC sheath, without con-<br />
an integrated optical interface. Plastic fiberoptic cables can be<br />
used for the optical connection between the PROFIBUS DP station<br />
with an integrated optical interface <strong>and</strong> the OBT.<br />
nectors, for use in environments<br />
with low mechanical stress, 50-m<br />
ring<br />
PROFIBUS Plastic Fiber Optic,<br />
Simplex Connector/<br />
Polishing Set<br />
100 simplex connectors <strong>and</strong><br />
5 polishing sets for assembling<br />
PROFIBUS plastic fiberoptic<br />
cables for the optical PROFIBUS<br />
DP<br />
6GK1 901-0FB00-0AA0 B)<br />
PROFIBUS Plastic Fiber Optic,<br />
Stripping Tool Set<br />
To remove the external or core<br />
sleeve of plastic fiberoptic cables<br />
6GK1 905-6PA10 B)<br />
Connection Adapter<br />
Pack of 50, for using simplex connectors<br />
with the integrated FO<br />
interfaces (e.g. IM 153-2 FO); for<br />
25 modules<br />
6ES7 195-1BE00-0XA0<br />
9/12<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
■ Overview<br />
PROFIBUS DP lines can be connected to a SIMATIC PCS 7 automation<br />
system through up to 4 internal interfaces in the CPU<br />
<strong>and</strong> up to 10 additional CP 443-5 Extended communication<br />
modules.<br />
If the module slot provided in the CPU for the PROFIBUS connection<br />
is not equipped yet, an IF 964-DP interface module will<br />
be required in addition. The CP 443-5 Extended communications<br />
processor is required for the PROFIBUS connection when<br />
data record routing is used with SIMATIC PDM.<br />
Benefits of the communication module:<br />
Compact design 9-pin Sub-D connector for connecting to<br />
PROFIBUS DP<br />
Easy assembly<br />
Can be installed in a slot of the AS subrack; connection with<br />
the other S7-400 modules through the backplane bus<br />
Can be operated without fans; a backup battery or memory<br />
module is not required.<br />
Communication<br />
PROFIBUS DP<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
AS connection<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
CP 443-5 Extended<br />
6GK7 443-5DX03-0XE0<br />
Communications module for connection<br />
of SIMATIC S7-400 to<br />
PROFIBUS as DP master or for S7<br />
communication,<br />
for data set routing of SIMATIC<br />
PDM<br />
IF 964-DP<br />
6ES7 964-2AA01-0AB0<br />
Interface module for connection<br />
of another PROFIBUS DP line, for<br />
plugging into a free DP module<br />
slot of the CPU<br />
9/13<br />
9
9<br />
Communication<br />
PROFIBUS DP<br />
Y-link<br />
■ Overview<br />
The Y-link is a bus coupler for transition from a redundant<br />
PROFIBUS DP master system to a single-channel<br />
PROFIBUS DP master system. It can be used for connecting devices<br />
with only one PROFIBUS DP interface to the redundant<br />
PROFIBUS DP master system AS 414H/ AS 417H.<br />
9/14<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Design<br />
The Y-link comprises:<br />
2 IM 157interface modules<br />
1 Y-coupler incl. RS 485 repeater<br />
1 BM IM 157 bus module<br />
1 BM Y-coupler bus module<br />
Evaluation of the Y-link diagnostics (<strong>and</strong> hence indirectly of the<br />
connected DP st<strong>and</strong>ard slaves) is supported by driver blocks.<br />
We recommend a redundant 24 V DC power supply, e.g. with<br />
two PS 307/PS 305 load power supplies.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Y link<br />
6ES7 197-1LA02-0XA0<br />
For connection of devices with<br />
only one PROFIBUS DP interface<br />
to a fault-tolerant automation system<br />
PS 307 Load Power Supply<br />
Including connection assembly;<br />
120/230 V AC; 24 V DC<br />
- 2 A; 50 mm wide 6ES7 307-1BA00-0AA0<br />
- 5 A; 80 mm wide 6ES7 307-1EA00-0AA0<br />
- 5 A, extended temperature 6ES7 307-1EA80-0AA0<br />
range; 80 mm wide<br />
- 10A, 200mm wide 6ES7 307-1KA01-0AA0<br />
PS 305 Load Power Supply<br />
Including connection assembly;<br />
24/48/60/110 V DC; 24 V DC<br />
- 2 A, extended temperature 6ES7 305-1BA80-0AA0<br />
range; 80 mm wide
■ Overview<br />
The transmission technology of the PROFIBUS PA profile is tailored<br />
to the needs of the process industry. The st<strong>and</strong>ardized<br />
communications services guarantee interoperability between<br />
multi-vendor field devices <strong>and</strong> remote parameterization of the<br />
field devices during operation.<br />
The PROFIBUS PA networks are based on electrical data transfer<br />
components. Data <strong>and</strong> the power supply are conveyed over<br />
a shielded 2-wire cable. Network lengths of up to approx. 1.9 km<br />
are possible with line, tree <strong>and</strong> star topologies. The passive terminating<br />
element for PROFIBUS PA (SpliTConnect terminator) is<br />
used for the termination of bus segments. The DP/PA Link is preferred<br />
for the gateway to the PROFIBUS DP.<br />
With SIMATIC PCS 7, communication between the automation<br />
system <strong>and</strong> the field devices takes place through token blocks<br />
in the CPU which cover all field device types. These token<br />
blocks are configured with the engineering system, which also<br />
creates the configuration data that are loaded into the<br />
DP/PA Link <strong>and</strong> the field devices during startup. Parameterization,<br />
commissioning <strong>and</strong> diagnostics are performed by the<br />
SIMATIC PDM process device manager, which is integrated in<br />
the engineering system.<br />
Communication<br />
PROFIBUS PA<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
■ Benefits<br />
The advantages of distributed field automation using the<br />
PROFIBUS PA are: less hardware, most cost-effective engineering,<br />
higher operational reliability <strong>and</strong> straightforward maintenance.<br />
These advantages are highlighted by the following characteristics:<br />
New plant concepts enabled by modularity <strong>and</strong> consistency<br />
from the sensor up into the control level<br />
Implementation of intrinsically safe applications through use of<br />
the field bus in use hazardous areas<br />
Reduced costs of configuration through simple, central engineering<br />
of the field devices (PROFIBUS PA <strong>and</strong> HART with<br />
SIMATIC PDM, multi-vendor devices also possible)<br />
Simple installation through 2-wire cable for joint conveyance<br />
of power supply <strong>and</strong> data<br />
Reduced commissioning costs through simplified loop check<br />
Low service costs thanks to simple wiring <strong>and</strong> more extensive<br />
diagnostics options<br />
9/15<br />
9
9<br />
Communication<br />
PROFIBUS PA<br />
Basic components<br />
■ Overview<br />
The DP/PA Link is a very simple gateway that interconnects the<br />
two bus systems PROFIBUS DP <strong>and</strong> PROFIBUS PA, but decouples<br />
their data transfer rates. It is thus possible to combine<br />
PROFIBUS DP <strong>and</strong> PROFIBUS PA without impairing the time-related<br />
performance of PROFIBUS DP.<br />
■ Design<br />
The DP/PA Link can be operated on PROFIBUS DP st<strong>and</strong>ard<br />
masters <strong>and</strong> enables the construction of large systems with<br />
large addressing ranges <strong>and</strong> high dem<strong>and</strong>s of cycle time.<br />
It is formed from the IM 157 interface module <strong>and</strong> up to<br />
five DP/PA couplers. DP/PA couplers are available in Ex <strong>and</strong><br />
non-Ex versions. All components of the DP/PA Link are interconnected<br />
through the S7 backplane bus.<br />
The use of active bus modules as the backplane bus enables<br />
hot swapping of individual modules <strong>and</strong> redundant configuration<br />
of the IM 157 interface module for PROFIBUS DP. Applications<br />
with a high level of availability are thus possible in conjunction<br />
with the AS 414H / AS 417H automation systems.<br />
The semi-modular DP/PA Link can be extended to a maximum of<br />
five PROFIBUS PA lines per DP connection, according to the<br />
number of DP/PA couplers. The PROFIBUS PA lines are physically<br />
separated as regards current input, but form one bus system<br />
in communication terms.<br />
Following basic components are available to configure the<br />
DP/PA Link:<br />
Load power supply PS 307 for 120/230 V AC; 24 V DC, version<br />
in 2, 5 or 10 A, or<br />
load power supply PS 305 for 24/48/60/110 V DC; 24 V DC,<br />
2A<br />
IM 157 interface module<br />
DP/PA coupler (Ex <strong>and</strong> non-Ex version)<br />
Hot swapping<br />
Following components are required in addition or as alternatives<br />
to the DP/PA Link basic components for the hot swapping function<br />
<strong>and</strong> for a redundant PROFIBUS DP interface module:<br />
Bus modules for hot swapping<br />
- BM IM 157 for two IM 157 modules, for redundant <strong>and</strong> nonredundant<br />
design, for extended temperature range<br />
- BM DP/PA for one DP/PA coupler, for extended temperature<br />
range (up to five DP/PA couplers per DP/PA Link possible)<br />
Profile rail for hot swapping (as an alternative to the st<strong>and</strong>ard<br />
profile rail)<br />
9/16<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Technical specifications<br />
DP/PA coupler<br />
Connection for PROFIBUS PA<br />
Intrinsically safe version 2-pin screw-type terminal, permanently<br />
integrated terminating<br />
resistor<br />
Output current max. 110 mA<br />
Output voltage 13...14 V DC<br />
Non-intrinsically safe version 4-pin screw-type terminal, switchable<br />
terminating resistor<br />
Output current max. 400 mA<br />
Output voltage 19... V DC<br />
Connection for PROFIBUS DP 9-pin Sub-D plug,<br />
contact assignment as described<br />
in IEC 61158/EN 50170<br />
Backplane bus Connection through S7 backplane<br />
bus connector (only necessary<br />
for PA Link ); non-isolated<br />
The active BM DP/PA bus modules<br />
are required for the hot<br />
swapping function<br />
Displays Bus activity DP (yellow)<br />
Bus activity PA (yellow)<br />
Supply voltage 24 V DC (green)<br />
Current consumption<br />
Ex version Max. 400 mA<br />
Non-Ex version Max. 750 mA<br />
Power loss<br />
Ex version Approx. 7 W<br />
Non-Ex version Approx. 7 W<br />
Operating temperature<br />
Ex version -25 ... +60 °C<br />
Non-Ex version -25 ... +60 °C<br />
Dimensions (W x H x D) in mm 80 x 125 x 130
Communication<br />
PROFIBUS PA<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Basic components<br />
■ Technical specifications<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
IM 157<br />
Function Linking of PROFIBUS DP<br />
(9.6 Kbit/s to 12 Mbit/s, slave<br />
functionality) <strong>and</strong> PROFIBUS PA<br />
PS 307 Load Power Supply<br />
Including connection assembly;<br />
120/230 V AC; 24 V DC<br />
2 A; 50 mm wide 6ES7 307-1BA00-0AA0<br />
with support of the "hot configuration"<br />
function (configuration when<br />
5 A; 80 mm wide 6ES7 307-1EA00-0AA0<br />
the plant is in operation)<br />
5 A, extended temperature 6ES7 307-1EA80-0AA0<br />
The DP/PA Link function is only<br />
range; 80 mm wide<br />
implemented by extending the<br />
IM 157 with one or more DP/PA<br />
couplers. St<strong>and</strong>-alone operation<br />
of the IM 157 is not possible.<br />
10A, 200mm wide<br />
PS 305 Load Power Supply<br />
24/48/60/110 V DC; 24 V DC<br />
6ES7 307-1KA01-0AA0<br />
Up to 5 DP/PA couplers <strong>and</strong> as 2 A, extended temperature 6ES7 305-1BA80-0AA0<br />
many as 64 slaves are connect- range; 80 mm wide<br />
able<br />
Isolation from the higher-level DP<br />
Master <strong>System</strong><br />
IM 157<br />
Interface module for DP/PA Link<br />
<strong>and</strong> Y-Link<br />
6ES7 157-0AA82-0XA0<br />
Interfaces<br />
DP/PA coupler<br />
Connection for PROFIBUS DP 9-pin Sub-D plug, contact assignment<br />
as described in<br />
For transition from RS 485 to<br />
IEC 61158<br />
IEC 61158/EN 50170, Vol. 2<br />
Intrinsically safe version 6ES7 157-0AD82-0XA0<br />
Backplane bus Connection through S7 bus backplane<br />
connector, non-isolated<br />
Bus modules <strong>and</strong> profile rails for<br />
hot swapping (see the section<br />
Non-intrinsically safe version<br />
St<strong>and</strong>ard Profile Rails<br />
(without hot swapping)<br />
6ES7 157-0AC81-0XA0<br />
"Hot swapping") are required for 482 mm wide (19 inches) 6ES7 390-1AE80-0AA0<br />
the hot swapping function <strong>and</strong> for<br />
a redundant PROFIBUS DP inter-<br />
530 mm wide 6ES7 390-1AF30-0AA0<br />
face module.<br />
Bus Modules for Hot Swapping<br />
Displays SF (red)<br />
BF DP (red)<br />
BF PA (red)<br />
BM IM 157<br />
For 2 IM 157 modules, for redundant<br />
<strong>and</strong> non-redundant config-<br />
6ES7 195-7HD80-0XA0<br />
Supply voltage<br />
Active (yellow)<br />
24 V DC (green)<br />
24 V DC<br />
uration, for extended<br />
temperature range, for hot<br />
swapping function,<br />
permissible operating tempera-<br />
Current consumption max. 100 mA (in DP/PA Link)<br />
ture -25...+60°C<br />
max. 200 mA (in Y-Link)<br />
BM DP/PA<br />
6ES7 195-7HF80-0XA0<br />
Power loss Approx. 2 W (in DP/PA Link)<br />
Approx. 4 W (in Y-Link)<br />
For 1 DP/PA coupler,<br />
for extended temperature range,<br />
for hot swapping function,<br />
Voltage failure bridging 20 ms<br />
permissible operating tempera-<br />
Mechanical design 4-pin screw terminal, short-cirture<br />
-25...+60°C<br />
cuiting link between PE <strong>and</strong> M24, Profile Rail for Hot Swapping<br />
for earth-free operation the shortcircuiting<br />
link must be removed<br />
482 mm wide (19 inches) 6ES7 195-1GA00-0XA0<br />
Permissible operating temperature<br />
(independent of this, the DP interface<br />
is always earth-free)<br />
-25...+60 °C<br />
530 mm wide<br />
620 mm wide<br />
6ES7 195-1GF30-0XA0<br />
6ES7 195-1GG30-0XA0<br />
Dimensions (W x H x D) in mm 40 x 125 x 130<br />
Configuration with STEP 7 in version 5.2 <strong>and</strong><br />
higher<br />
9/17<br />
9
9<br />
Communication<br />
PROFIBUS PA<br />
FastConnect/SpliTConnect<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PROFIBUS FC process cables, color-coded for the various ap- FC Process Cable<br />
plications (Ex, non-Ex area) are available for designing field bus 2-core, shielded<br />
networks in accordance with IEC 61158-2 (e.g. PROFIBUS PA).<br />
Blue for Ex applications 6XV1 830-5EH10<br />
The FastConnect stripping tool can be used to strip the FC process<br />
cable for PROFIBUS PA to the correct length for casing <strong>and</strong><br />
shield.<br />
Black for non-Ex applications<br />
Sold by the meter:<br />
Max. delivey unit 1000 m, mini-<br />
6XV1 830-5FH10<br />
■ Design<br />
mum ordering quantity 20 m<br />
PROFIBUS FastConnect<br />
Stripping Tool<br />
Stripping tool for rapid stripping<br />
of insulation from PROFIBUS<br />
FastConnect bus cables<br />
6GK1 905-6AA00<br />
PROFIBUS FastConnect<br />
Blade Cassettes<br />
Spare blade cassettes for the<br />
PROFIBUS FastConnect stripping<br />
tool, 5 pcs<br />
6GK1 905-6AB00<br />
SpliTConnect Tap<br />
For design of PROFIBUS PA segments<br />
<strong>and</strong> connection of PA field<br />
devices, insulation displacement<br />
system, IP67, 10 pcs<br />
6GK1 905-0AA00<br />
SpliTConnect M12 Outlet<br />
Replacement element for direct<br />
connection of PA field devices to<br />
the SpliTConnect Tap, 5 pcs<br />
6GK1 905-0AB10<br />
SpliTConnect Coupler<br />
Connection element for cascading<br />
SpliTConnect Taps in order to<br />
configure star points, 10 pcs<br />
SpliTConnect Terminator<br />
For termination of PROFIBUS PA<br />
6GK1 905-0AC00<br />
segments, 5 pcs<br />
SpliTConnect<br />
Terminator (Ex); use possible in 6GK1 905-0AD00<br />
The SpliTConnect Tap enables the design of field bus segments hazardous area<br />
according to IEC 61158-2 with field device connection points. Terminator (non-Ex); use not 6GK1 905-0AE00<br />
The SpliTConnect coupler can be used to construct a<br />
possible in hazardous area<br />
PROFIBUS PA hub by connecting SpliTConnect taps in series. SpliTConnect M12 Jack<br />
6GK1 905-0AF00<br />
By replacing the contacting screw with the SpliTConnect Terminator,<br />
the SpliTConnect tap can be used as a bus terminating element.<br />
The terminals can be connected directly through the FC process<br />
cable. Using the SpliTConnect M12 outlet, PA field devices can<br />
also be connected to the SpliTConnect Tap by M12 connection.<br />
The SpliTConnect M12 jack is a connecting element between<br />
FC process cable <strong>and</strong> M12 connector on the PROFIBUS PA field<br />
device. For details of SpliTConnect network components, see<br />
the IK PI catalog.<br />
Connection element between<br />
FC process cable <strong>and</strong> M12 plug<br />
on the PROFIBUS PA field device,<br />
5pcs<br />
9/18<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
Communication<br />
Other communication<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
AS-Interface<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
CP 343-2<br />
Communications module for connection<br />
of SIMATIC S7-300 <strong>and</strong><br />
ET 200M to AS-Interface, without<br />
front connector<br />
6GK7 343-2AH00-0XA0<br />
Front Connector<br />
6ES7 392-1AJ00-0AA0<br />
The actuator-sensor interface (AS-Interface) is a multi-vendor<br />
networking system for simple - usually binary - actuators <strong>and</strong><br />
20-pin, with screw contacts<br />
CP 343-2 Manual<br />
sensors in the lowest field area. AS-Interface enables a wiring Including software <strong>and</strong> examples<br />
loom with parallel wiring to be replaced by a simple two-wire cable<br />
shared by all sensors or actuators.<br />
The AS-Interface works by the master-slave principle. Sensors/actuators<br />
connected through the AS-Interface cable are<br />
German<br />
English<br />
French<br />
6GK7 343-2AH00-8AA0<br />
6GK7 343-2AH00-8BA0<br />
6GK7 343-2AH00-8CA0<br />
controlled by the master as slaves.<br />
Italian 6GK7 343-2AH00-8EA0<br />
Note:<br />
DP/AS-Interface Link 20E<br />
6GK1 415-2AA01<br />
AS-Interface is integrated in SIMATIC pcs 7 as a subordinate<br />
bus. Consequently, this bus does not offer the full functionality of<br />
SIMATIC PCS 7; this applies in particular to diagnostics functions.<br />
Further information, see Catalog IK PI.<br />
PROFIBUS DP/ AS-Interface<br />
gateway, degree of protection<br />
IP20<br />
DP/AS-Interface Link 20E Manual<br />
■ Design<br />
Including type <strong>and</strong> GSD files<br />
German 6GK1 971-2DS01-0AA0<br />
<strong>System</strong> components<br />
English 6GK1 971-2DS01-0AA1<br />
The basic components of a system installation are:<br />
French 6GK1 971-2DS01-0AA2<br />
CP 343-2 AS-Interface master module for ET 200M or/<strong>and</strong><br />
DP/AS-Interface link for connection of an AS-Interface line to<br />
PROFIBUS DP<br />
AS-Interface shaped cable (use of round cable also possible<br />
if preferred)<br />
Modules for connecting st<strong>and</strong>ard sensors/actuators<br />
Power supply unit for powering the slaves<br />
Actuators <strong>and</strong> sensors with integrated ASIC slave<br />
Address programming device for setting the slave address<br />
Spanish<br />
Italian<br />
6GK1 971-2DS01-0AA3<br />
6GK1 971-2DS01-0AA4<br />
9/19<br />
9
9<br />
Communication<br />
Other communication<br />
EIB instabus<br />
■ Overview<br />
DB/EIB Link connects the production automation <strong>and</strong> process<br />
automation to building installation systems<br />
Data is exchanged between PROFIBUS DP <strong>and</strong> EIB (European<br />
Installation Bus)<br />
Compact housing to degree of protection IP20, for use in<br />
switchgear cabinets as well as in distribution systems<br />
Configurable as a DP slave with STEP 7 or COM PROFIBUS<br />
st<strong>and</strong>ard tools <strong>and</strong> with the EIB configuring software ETS 2<br />
Note :<br />
EIB instabus is integrated in SIMATIC PCS 7 as a subordinate<br />
bus. Consequently, this bus does not offer the full functionality of<br />
SIMATIC PCS 7; this applies in particular to diagnostics functions.<br />
Further information, see Catalog IK PI.<br />
9/20<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
DP/EIB Link<br />
Gateway for data exchange<br />
between PROFIBUS DP <strong>and</strong> EIB<br />
6GK1 415-0AA01 E)<br />
DP/EIB Link Manual<br />
Including GSD file <strong>and</strong> ETS database<br />
entry<br />
German 6GK1 971-3DA00-0AA0<br />
English 6GK1 971-3DA00-0AA1<br />
E) Subject to export regulations: AL: N, ECCN: 5A991
Communication<br />
Other communication<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Modbus is connected to PROFIBUS DP using an ET 200M with<br />
a CP 341 communications module. The latter enables the fast<br />
CP 341 communications processor<br />
6ES7 341-1AH01-0AE0<br />
<strong>and</strong> efficient exchange of data through point-to-point coupling. with one RS 232 C (V.24) interface<br />
The CP 341 communications module is available in 3 versions RS 232 connecting cable<br />
with different transmission physics:<br />
for linking to SIMATIC S7<br />
RS 232C (V.24),<br />
5 m 6ES7 902-1AB00-0AA0<br />
20 mA (TTY)<br />
10 m 6ES7 902-1AC00-0AA0<br />
RS 422/RS 485 (X.27)<br />
The MODBUS Master or MODBUS Slave loadable drivers are<br />
15 m 6ES7 902-1AD00-0AA0<br />
needed for the Modbus coupling.<br />
CP 341 communications processor<br />
with one 20 mA (TTY) interface<br />
20 mA (TTY) connecting cable<br />
for linking to SIMATIC S7<br />
6ES7 341-1BH01-0AE0<br />
5 m 6ES7 902-2AB00-0AA0<br />
10 m 6ES7 902-2AC00-0AA0<br />
50 m 6ES7 902-2AG00-0AA0<br />
CP 341 communications pro- 6ES7 341-1CH01-0AE0<br />
cessor<br />
with one RS 422/485 (X.27) interface<br />
RS 422/485 connecting cable<br />
for linking to SIMATIC S7<br />
5 m 6ES7 902-3AB00-0AA0<br />
10 m 6ES7 902-3AC00-0AA0<br />
50 m 6ES7 902-3AG00-0AA0<br />
CP 341 manual<br />
German 6ES7 341-1AH00-8AA0<br />
Englisch 6ES7 341-1AH00-8BA0<br />
French 6ES7 341-1AH00-8CA0<br />
Italian 6ES7 341-1AH00-8EA0<br />
Loadable drivers for CP 341<br />
MODBUS Master (RTU format)<br />
Single license 6ES7 870-1AA01-0YA0<br />
Single license, without software 6ES7 870-1AA01-0YA1<br />
<strong>and</strong> documentation<br />
MODBUS Slave (RTU format)<br />
Single license 6ES7 870-1AB01-0YA0<br />
Single license, without software 6ES7 870-1AB01-0YA1<br />
<strong>and</strong> documentation<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Modbus<br />
9/21<br />
9
9<br />
9/22<br />
Communication<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
<strong>Automation</strong> systems<br />
10/2 Introduction<br />
10/3 Innovated<br />
st<strong>and</strong>ard automation systems<br />
10/6 Fault-tolerant<br />
automation systems<br />
10/9 Failsafe automation systems<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
10<br />
<strong>Automation</strong> systems<br />
Introduction<br />
■ Overview<br />
■ Technical specifications<br />
Select SIMATIC S7-400 components can be combined in the au-<br />
AS 416-3 AS 417-4/<br />
tomation systems of the SIMATIC PCS 7 process control system.<br />
AS 417H<br />
The following characteristics make the SIMATIC S7-400 predes- Analog value measurements 125 150<br />
tined for use as a SIMATIC PCS 7 automation system:<br />
Digital value measurements 300 400<br />
modular <strong>and</strong> fan-free design,<br />
Dosing rates 10 15<br />
high degree of expansion capability <strong>and</strong> robust design,<br />
Motors 125 150<br />
simple or redundant design,<br />
PID controls 100 130<br />
comprehensive communications capabilities,<br />
Valves 125 150<br />
integral system functions <strong>and</strong><br />
simple connection of central or distributed I/Os.<br />
SFC<br />
Steps<br />
30<br />
300<br />
50<br />
500<br />
Various automation systems are available with a price/performance<br />
ratio which can be tailored to your system requirements.<br />
All automation systems are equipped with an onboard<br />
or<br />
Digital inputs DI 675 850<br />
PROFIBUS DP field-bus connection. Additional PROFIBUS communication<br />
modules can be fitted if required.<br />
Digital outputs DO<br />
Analog inputs AI<br />
260<br />
210<br />
315<br />
275<br />
■ Design<br />
Analog outputs AO 100 130<br />
The automation systems are delivered as preassembled <strong>and</strong><br />
tested complete systems without surcharge, <strong>and</strong> are comprised<br />
Typical mixed quantity frameworks for SIMATIC PCS 7 automation systems<br />
of:<br />
Note:<br />
Subracks with 9 or 18 slots, which can be physically separate<br />
in the case of redundant systems<br />
The values quoted here are not AS-specific maximum values for the particular<br />
item but represent a typical distribution of the available total capacity<br />
of the AS during mixed operation of all the items of an assembled<br />
St<strong>and</strong>ard CPU 414-3, 416-2, 416-3 or 417-4 as well as the redundant<br />
CPU 414-4H <strong>and</strong> 417-4H<br />
24 V DC or 120/230 V AC power supply incl. backup battery<br />
(batteries)<br />
Main memory from 768 Kbyte to 20 Mbyte<br />
Memory card with 1 to 16 Mbyte RAM<br />
Connection to Industrial Ethernet<br />
A corresponding Runtime licence is required per automation<br />
system when using the "PCS 7 Library Blocks V6.0” library (see<br />
ordering data for accessories).<br />
block. Individual calculation of these quantity frameworks is possible using<br />
the configurator software, which can be found on the current CD-<br />
ROM of the CA 01 Interactive Catalog.<br />
10/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
■ Overview<br />
Compared to the previous st<strong>and</strong>ard automation systems, the innovated<br />
st<strong>and</strong>ard automation systems have the following key<br />
features:<br />
7 Improved processing capacity (1.6 - 3x as fast)<br />
7 Significantly improved communications capacity<br />
7 Larger integrated main memory (5x for AS 417, 1.75 - 2x for<br />
AS 414 <strong>and</strong> AS 416)<br />
The AS 414-3 automation systems are tailored for small applications<br />
with small quantity frameworks. They therefore meet the dem<strong>and</strong><br />
for low-cost initial implementation with a modular <strong>and</strong> scalable<br />
system. Larger quantity frameworks can be implemented<br />
with the AS 416-2, AS 416-3 <strong>and</strong> AS 417-4 automation systems.<br />
These systems are preferred for medium-sized systems <strong>and</strong> bigger.<br />
The automation systems are available complete with subrack,<br />
power supply, CPU, memory card <strong>and</strong> PROFIBUS DP interface.<br />
They are delivered already assembled <strong>and</strong> tested. Each version<br />
has a different main memory:<br />
AS 414-3: Main memory 1.4 MByte<br />
(0.7 MByte for program <strong>and</strong> data respectively)<br />
AS 416-2: Main memory 2.8 MByte<br />
(1.4 MByte for program <strong>and</strong> data respectively)<br />
AS 416-3: Main memory 5.6 MByte<br />
(2.8 MByte for program <strong>and</strong> data respectively)<br />
AS 417-4: Main memory 20 Mbyte<br />
(10 Mbyte for program <strong>and</strong> data respectively)<br />
All systems are available with a choice of 120/230 V AC or<br />
24 V DC power supply.<br />
■ Technical specifications<br />
Selected technical data<br />
<strong>Automation</strong> systems<br />
Innovated st<strong>and</strong>ard automation systems<br />
AS type Integrated main<br />
memory in Mbyte<br />
AS 414-3: 1,4 60<br />
AS 416-2: 2,8 40<br />
AS 416-3: 5,6 40<br />
AS 417-4: 20 30<br />
Processing time in<br />
ns<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
10/3<br />
10
10<br />
<strong>Automation</strong> systems<br />
Innovated st<strong>and</strong>ard automation systems<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Ordering units for automation systems<br />
AS 414-3 <strong>Automation</strong> <strong>System</strong><br />
Comprising:<br />
controller type 414-3 with<br />
3 interfaces (MPI/DP, DP <strong>and</strong> slot<br />
for IF module), 1.4 Mbyte main<br />
memory (0.7 Mbyte available for<br />
program <strong>and</strong> data respectively),<br />
memory card 2 Mbyte RAM,<br />
2 backup batteries, CP 443-<br />
1EX11 communications module<br />
for connection to Industrial Ethernet<br />
plant bus<br />
UR1 subrack (18 slots):<br />
- PS 407 power supply; 20 A for 6ES7 654-3QD47-0XX0<br />
120/230 V AC<br />
- PS 405 power supply; 20 A for 6ES7 654-6QD47-0XX0<br />
24 V DC<br />
UR2 subrack (9 slots):<br />
- PS 407 power supply; 10 A for 6ES7 654-1QD57-0XX0<br />
120/230 V AC<br />
- PS 405 power supply; 10 A for 6ES7 654-4QD57-0XX0<br />
24 V DC<br />
AS 416-2 <strong>Automation</strong> <strong>System</strong><br />
Comprising:<br />
controller type 416-2 with<br />
2 interfaces (MPI/DP <strong>and</strong> DP), 2.8<br />
Mbyte main memory (1.4 Mbyte<br />
available for program <strong>and</strong> data<br />
respectively), memory card 2<br />
Mbyte RAM, 4 backup batteries,<br />
CP 443-1EX11 communications<br />
module for connection to Industrial<br />
Ethernet plant bus<br />
UR1 subrack (18 slots):<br />
- PS 407 power supply; 20 A for 6ES7 654-3JE47-0XX0<br />
120/230 V AC<br />
- PS 405 power supply; 20 A for 6ES7 654-6JE47-0XX0<br />
24 V DC<br />
UR2 subrack (9 slots):<br />
- PS 407 power supply; 10 A for 6ES7 654-1JE57-0XX0<br />
120/230 V AC<br />
- PS 405 power supply; 10 A for 6ES7 654-4JE57-0XX0<br />
24 V DC<br />
10/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
AS 416-3 <strong>Automation</strong> <strong>System</strong><br />
Comprising:<br />
controller type 416-3 with<br />
3 interfaces (MPI/DP, DP <strong>and</strong> slot<br />
for IF module), 5.6 Mbyte main<br />
memory (2.8 Mbyte available for<br />
program <strong>and</strong> data respectively),<br />
memory card 8 Mbyte RAM,<br />
2 backup batteries, CP 443-<br />
1EX11 communications module<br />
for connection to Industrial Ethernet<br />
plant bus<br />
UR1 subrack (18 slots):<br />
- PS 407 power supply; 20 A for 6ES7 654-3KF47-0XX0<br />
120/230 V AC<br />
- PS 405 power supply; 20 A for 6ES7 654-6KF47-0XX0<br />
24 V DC<br />
UR2 subrack (9 slots):<br />
- PS 407 power supply; 10 A for 6ES7 654-1KF57-0XX0<br />
120/230 V AC<br />
- PS 405 power supply; 10 A for 6ES7 654-4KF57-0XX0<br />
24 V DC<br />
AS 417-4 <strong>Automation</strong> <strong>System</strong><br />
Comprising:<br />
controller type 417-4 with with<br />
4 interfaces (MPI/DP, DP <strong>and</strong><br />
2 slots for IF modules), 20 Mbyte<br />
main memory (10 Mbyte available<br />
for program <strong>and</strong> data respectively),<br />
memory card 2 Mbyte<br />
RAM, 2 backup batteries,<br />
CP 443-1EX11 communications<br />
module for connection to Industrial<br />
Ethernet plant bus<br />
UR1 subrack (18 slots):<br />
- PS 407 power supply; 20 A for 6ES7 654-3LE47-0XX0<br />
120/230 V AC <strong>and</strong><br />
memory card, 4 Mbyte RAM<br />
- PS 407 power supply; 20 A for 6ES7 654-3LG47-0XX0<br />
120/230 V AC <strong>and</strong><br />
memory card, 16 Mbyte RAM<br />
- PS 405 power supply; 20 A for 6ES7 654-6LE47-0XX0<br />
24 V DC <strong>and</strong><br />
memory card, 4 Mbyte RAM<br />
- PS 405 power supply; 20 A for 6ES7 654-6LG47-0XX0<br />
24 V DC <strong>and</strong><br />
memory card, 16 Mbyte RAM<br />
UR2 subrack (9 slots):<br />
- PS 407 power supply; 10 A for 6ES7 654-1LE57-0XX0<br />
120/230 V AC <strong>and</strong><br />
memory card, 4 Mbyte RAM<br />
- PS 407 power supply; 10 A for 6ES7 654-1LG57-0XX0<br />
120/230 V AC <strong>and</strong><br />
memory card, 16 Mbyte RAM<br />
- PS 405 power supply; 10 A for 6ES7 654-4LE57-0XX0<br />
24 V DC <strong>and</strong><br />
memory card, 4 Mbyte RAM<br />
- PS 405 power supply; 10 A for 6ES7 654-4LG57-0XX0<br />
24 V DC <strong>and</strong><br />
memory card, 16 Mbyte RAM
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Individual components for automation systems<br />
CPU 414-3<br />
Main memory 1.4 Mbyte integrated<br />
(0.7 Mbyte for program<br />
<strong>and</strong> data respectively);<br />
module occupies 2 slots<br />
6ES7 414-3XJ04-0AB0<br />
CPU 416-2<br />
Main memory 2.8 Mbyte integrated<br />
(1.4 Mbyte for program<br />
<strong>and</strong> data respectively);<br />
module occupies 1 slot<br />
6ES7 416-2XK04-0AB0<br />
CPU 416-3<br />
Main memory 5.6 Mbyte integrated<br />
(2.8 Mbyte for program<br />
<strong>and</strong> data respectively);<br />
module occupies 2 slots<br />
6ES7 416-3XL04-0AB0<br />
CPU 417-4<br />
Main memory 20 Mbyte integrated<br />
(10 Mbyte for program<br />
<strong>and</strong> data respectively);<br />
module occupies 2 slots<br />
Memory Card RAM<br />
6ES7 417-4XL04-0AB0<br />
2 Mbyte 6ES7 952-1AL00-0AA0<br />
4 Mbyte 6ES7 952-1AM00-0AA0<br />
8 Mbyte 6ES7 952-1AP00-0AA0<br />
16 Mbyte<br />
Memory Card Flash-EPROM<br />
Only required to update firmware<br />
6ES7 952-1AS00-0AA0 B)<br />
4 Mbyte 6ES7 952-1KM00-0AA0<br />
CP 443-1EX11<br />
Communications module for connection<br />
of SIMATIC S7-400 to<br />
Industrial Ethernet through TCP/IP<br />
<strong>and</strong> ISO; for S7 communication,<br />
S5-compatible communication<br />
(SEND/RECEIVE) with<br />
FETCH/WRITE with or without<br />
RFC 1006, 10/100 Mbit/s, with<br />
AUI/ITP <strong>and</strong> RJ45 connections,<br />
electronic manual on CD;<br />
module occupies 1 slot<br />
6GK7 443-1EX11-0XE0<br />
CP 443-5 Extended<br />
Communications module for connection<br />
of SIMATIC S7-400 to<br />
PROFIBUS as DP master or for S7<br />
communication, for increasing the<br />
number of DP lines, for data set<br />
routing with SIMATIC PDM <strong>and</strong> for<br />
10-ms time stamp,<br />
electronic manual on CD;<br />
module occupies 1 slot<br />
6GK7 443-5DX03-0XE0<br />
IF 964-DP<br />
Interface module for connection<br />
of another PROFIBUS DP line, for<br />
plugging into a free DP module<br />
slot of the CPU<br />
6ES7 964-2AA04-0AB0<br />
<strong>Automation</strong> systems<br />
Innovated st<strong>and</strong>ard automation systems<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PS 407 power supply module; 6ES7 407-0KA01-0AA0<br />
10 A<br />
120/230 V AC; 5 V DC/10 A,<br />
24 V DC/1 A;<br />
with battery compartment for<br />
2 backup batteries, module occupies<br />
2 slots<br />
PS 407 power supply module; 6ES7 407-0KR00-0AA0<br />
10 A, redundant design possible<br />
120/230 V AC; 5 V DC/10 A,<br />
24 V DC/1 A;<br />
with battery compartment for<br />
2 backup batteries, module occupies<br />
2 slots<br />
PS 407 power supply module; 6ES7 407-0RA01-0AA0<br />
20 A<br />
120/230 V AC; 5 V DC/20 A,<br />
24 V DC/1 A;<br />
with battery compartment for<br />
2 backup batteries, module occupies<br />
3 slots<br />
PS 405 power supply module; 6ES7 405-0KA01-0AA0<br />
10 A<br />
24 V DC; 5 V DC/10 A,<br />
24 V DC/1 A;<br />
with battery compartment for<br />
2 backup batteries, module occupies<br />
2 slots<br />
PS 405 power supply module; 6ES7 405-0KR00-0AA0<br />
10 A, redundant design possible<br />
24 V DC; 5 V DC/10 A,<br />
24 V DC/1 A;<br />
with battery compartment for<br />
2 backup batteries, module occupies<br />
2 slots<br />
PS 405 power supply module; 6ES7 405-0RA01-0AA0<br />
20 A<br />
24 V DC; 5 V DC/20 A, 24 V<br />
DC/1 A;<br />
with battery compartment for<br />
2 backup batteries, module occupies<br />
3 slots<br />
Backup Battery<br />
6ES7 971-0BA00<br />
Type AA, 1.9 Ah<br />
UR1 Subrack<br />
6ES7 400-1TA01-0AA0<br />
18 slots<br />
UR2 Subrack<br />
6ES7 400-1JA01-0AA0<br />
9 slots<br />
Runtime licenses for libraries<br />
PCS 7 Library Blocks V6.0 6ES7 653-2BG06-2YB0<br />
runtime license<br />
valid for one SIMATIC PCS 7 automation<br />
system<br />
trilingual (German, English,<br />
French)<br />
Type of delivery: Certificate of<br />
license<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
10/5<br />
10
10<br />
<strong>Automation</strong> systems<br />
Fault-tolerant automation systems<br />
■ Overview<br />
Fault-tolerant automation systems are used to minimize the risk<br />
of production failures. The higher investment in fault-tolerant automation<br />
systems is often negligible compared to the costs resulting<br />
from production stoppages. The higher the costs resulting<br />
from loss of production, the more important a fault-tolerant<br />
system becomes.<br />
■ Design<br />
The AS 414-4-1H <strong>and</strong> AS 417-4-1H automation systems are initially<br />
equipped with just one CPU. They are used in particular<br />
when the redundant subsystems have to be physically separated<br />
from one another for safety reasons or when the customer<br />
would like to keep open his options for a redundant configuration<br />
in the future. The failsafe AS 414F <strong>and</strong> AS 417F automation systems<br />
are based likewise on this hardware in the corresponding<br />
version.<br />
There are two configuration possibilities for the AS 414-4-1H <strong>and</strong><br />
AS 417-4-1H automation systems:<br />
Configuration with two st<strong>and</strong>ard subracks (UR1 or UR2)<br />
This configuration is ideal when the two redundant subsystems<br />
have to be completely separated for availability reasons.<br />
Each subsystem contains a CPU, a potentially redundant<br />
power supply module (AC), <strong>and</strong> a communication<br />
module for Industrial Ethernet.<br />
Configuration with a UR2-H subrack<br />
The UR2-H compact subrack with split backplane bus is suitable<br />
for configuring a complete fault-tolerant automation system.<br />
For the AS 414-4-1H <strong>and</strong> AS 417-4-1H the UR2-H is<br />
equipped with a CPU, a potentially redundant power supply<br />
module <strong>and</strong> a communications module for Industrial Ethernet.<br />
In the case of the redundant AS 414-4-2H <strong>and</strong> AS 417-4-2H automation<br />
systems, the two subsystems are accommodated in<br />
the UR2-H subrack. Each subsystem is equipped with a CPU, a<br />
potentially redundant power supply module <strong>and</strong> a communications<br />
module for Industrial Ethernet.<br />
In all the configurations described, potentially redundant power<br />
supply modules can be exp<strong>and</strong>ed to redundant configuration by<br />
retrofitting a second power supply module of the same type.<br />
Another 4 sync modules <strong>and</strong> 2 sync cables have to be ordered<br />
in addition to create a redundant system from two AS 414-4-1H<br />
or AS 417-4-1H automation system (UR1/UR2 subracks) <strong>and</strong> to<br />
subsequently exp<strong>and</strong> an AS 414-4-1H or AS 417-4-1H in a UR2-<br />
H subrack into a redundant AS 414-4-2H or AS 417-4-2H system.<br />
10/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Connection of process I/Os<br />
Several PROFIBUS DP lines with distributed process I/Os can be<br />
operated on each sub-AS through the internal PROFIBUS DP interface<br />
or by using additional communications processors.<br />
The distributed ET 200M I/Os are connected through two<br />
IM 153-2 interface modules on a special bus module to two redundant<br />
PROFIBUS DP lines, <strong>and</strong> the intelligent field devices on<br />
the PROFIBUS PA are connected through a redundant<br />
DP/PA link with two IM 157 interface modules. The Y-link can<br />
also be used to connect non-redundant PROFIBUS DP devices<br />
to the redundant PROFIBUS DP.<br />
A mixture of these configurations is also possible.<br />
Communication through the plant bus<br />
The redundant, fault-tolerant AS 414H <strong>and</strong> AS 417H automation<br />
systems are connected by one communication module per sub-<br />
AS to the plant bus. The plant bus can be implemented in the<br />
form of a ring structure, which can also be configured with redundant<br />
architecture if the availability requirements are high.<br />
When there are two redundant rings it makes sense to use two<br />
communication module per sub-AS <strong>and</strong> to distribute their connections<br />
between the two rings. Double faults such as OSM failure<br />
on ring 1 with simultaneous splitting of the bus cable on ring<br />
2 can thus be tolerated.<br />
■ Function<br />
The AS 414H <strong>and</strong> AS 417H models are the fault-tolerant automation<br />
systems for use with SIMATIC PCS 7. They are based on the<br />
1-out-of-2 principle <strong>and</strong> switch to the backup system in the event<br />
of a fault. These systems use a completely redundant design to<br />
maximize availability. This means that all major components<br />
such as CPU, power supply <strong>and</strong> hardware for coupling the two<br />
CPUs are present in pairs. Which other components are also<br />
made available in pairs in the interest of availability depends on<br />
the particular automation task.<br />
The two subsystems of a redundant automation system are electrically<br />
isolated from one another. This increases the system stability<br />
with respect to EMC interference. A redundant automation<br />
system can be installed mechanically in a one- or two-rack architecture.<br />
<strong>Automation</strong> systems are installed in two racks, for example,<br />
if the two parts of the automation system have to be physically<br />
separated from one another by a fire-resistant wall.<br />
Appropriate complete units are available for every type of application.<br />
Mixed operation of redundant <strong>and</strong> st<strong>and</strong>ard systems is<br />
also possible.
■ Selection <strong>and</strong> Ordering Data Order No.<br />
AS 414-4-1H<br />
<strong>Automation</strong> <strong>System</strong><br />
Prepared system with one<br />
CPU 414-4H for physically separated<br />
redundant systems, for<br />
F systems or for later upgrading<br />
to a redundant system<br />
Comprising:<br />
1 x CPU 1414 with 2 interfaces<br />
(MPI/DP <strong>and</strong> DP), 768 Kbyte main<br />
memory (384 Kbyte available<br />
user memory), memory card<br />
1 Mbyte RAM, 2 backup batteries,<br />
CP 443-1 communications<br />
module for connection to Industrial<br />
Ethernet plant bus<br />
PS 407 power supply; 10 A for<br />
120/230 V AC, redundant design<br />
possible, with subrack<br />
- UR1 (18 slots) 6ES7 654-2UA34-0XX0<br />
- UR2 (9 slots) 6ES7 654-2UB34-0XX0<br />
- UR2-H (2 x 9 slots) 6ES7 654-2UR34-0XX0<br />
PS 405 power supply; 10 A for<br />
24 V DC, with subrack<br />
- UR1 (18 slots) 6ES7 654-5UA34-0XX0<br />
- UR2 (9 slots) 6ES7 654-5UB34-0XX0<br />
- UR2-H (2 x 9 slots) 6ES7 654-5UR34-0XX0<br />
AS 414-4-2H<br />
<strong>Automation</strong> <strong>System</strong><br />
Complete fault-tolerant programmable<br />
logic controller with two<br />
CPUs 414-4H<br />
Comprising:<br />
2 x CPU 1414H with each<br />
2 interfaces (MPI/DP <strong>and</strong> DP),<br />
768 Kbyte main memory<br />
(384 Kbyte available user memory),<br />
2 memory cards 1 Mbyte<br />
RAM, 4 backup batteries,<br />
4 sync modules, 2 sync cables,<br />
2 CP 443-1 communications<br />
modules for connection to Industrial<br />
Ethernet plant bus<br />
PS 407 power supply; 10 A for 6ES7 654-2VR34-0XX0<br />
120/230 V AC, redundant design<br />
possible, with<br />
UR2-H subrack (2 x 9 slots)<br />
PS 405 power supply; 10 A for 6ES7 654-5VR34-0XX0<br />
24 V DC, with UR2-H subrack<br />
(2 x 9 slots)<br />
<strong>Automation</strong> systems<br />
Fault-tolerant automation systems<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
AS 417-4-1H<br />
<strong>Automation</strong> <strong>System</strong><br />
Prepared system with one<br />
CPU 417-4H for physically separated<br />
redundant systems, for F<br />
systems or for later upgrading to<br />
a redundant system<br />
Comprising:<br />
1 x CPU 1414H with 2 interfaces<br />
(MPI/DP <strong>and</strong> DP), 4,000 Kbyte<br />
main memory (2,000 Kbyte available<br />
user memory), memory card<br />
4 Mbyte RAM, 2 backup batteries,<br />
CP 443-1 communications<br />
module for connection to Industrial<br />
Ethernet plant bus<br />
PS 407 power supply; 10 A for<br />
120/230 V AC, redundant design<br />
possible, with subrack<br />
- UR1 (18 slots) 6ES7 654-2SA34-0XX0<br />
- UR2 (9 slots) 6ES7 654-2SB34-0XX0<br />
- UR2-H (2 x 9 slots) 6ES7 654-2SR34-0XX0<br />
PS 405 power supply; 10 A for<br />
24 V DC, with subrack<br />
- UR1 (18 slots) 6ES7 654-5SA34-0XX0<br />
- UR2 (9 slots) 6ES7 654-5SB34-0XX0<br />
- UR2-H (2 x 9 slots) 6ES7 654-5SR34-0XX0<br />
AS 417-4-2H<br />
<strong>Automation</strong> <strong>System</strong><br />
Complete fault-tolerant programmable<br />
logic controller with two<br />
CPUs 417-4H<br />
Comprising:<br />
2 x CPU 417-H with each<br />
2 interfaces (MPI/DP <strong>and</strong> DP),<br />
4,000 Kbyte main memory<br />
(2,000 Kbyte available user memory),<br />
2 memory cards 4 Mbyte<br />
RAM, 4 backup batteries,<br />
4 sync modules, 2 sync cables,<br />
2 CP 443-1 communications<br />
modules for connection to Industrial<br />
Ethernet plant bus<br />
PS 407 power supply; 10 A for 6ES7 654-2TR34-0XX0<br />
120/230 V AC, redundant design<br />
possible, with<br />
UR2-H subrack (2 x 9 slots)<br />
PS 405 power supply; 10 A for 6ES7 654-5TR34-0XX0<br />
24 V DC, with UR2-H subrack<br />
(2 x 9 slots)<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
10/7<br />
10
10<br />
<strong>Automation</strong> systems<br />
Fault-tolerant automation systems<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Individual components of fault-tolerant automation systems<br />
CPU 414-4H<br />
Main memory 768 Kbyte<br />
module occupies 2 slots<br />
6ES7 414-4HJ00-0AB0<br />
CPU 417-4H<br />
Main memory 4,000 Kbyte<br />
module occupies 2 slots<br />
6ES7 417-4HL01-0AB0<br />
Sync Module<br />
For linking the two CPUs 414-4H<br />
or 417-4H;<br />
two modules required per CPU<br />
6ES7 960-1AA00-0XA0 B)<br />
Sync Cable (fiberoptic cable)<br />
For connecting the two<br />
CPUs 414-4H or 417-4H;<br />
each redundant automation systems<br />
requires 2 cables<br />
1 m 6ES7 960-1AA00-5AA0<br />
2 m 6ES7 960-1AA00-5BA0<br />
10 m 6ES7 960-1AA00-5KA0<br />
Other lengths On request<br />
RAM Expansion for CPU 417-4H<br />
Main Memory RAM<br />
(only for CPU 417-x; 2 can be<br />
plugged in each)<br />
4 (2 x 2) Mbyte 6ES7 955-2AL00-0AA0<br />
8 (2 x 4) Mbyte 6ES7 955-2AM00-0AA0<br />
Memory Card RAM<br />
1 Mbyte 6ES7 952-1AK00-0AA0<br />
2 Mbyte 6ES7 952-1AL00-0AA0<br />
4 Mbyte 6ES7 952-1AM00-0AA0<br />
8 Mbyte 6ES7 952-1AP00-0AA0<br />
16 Mbyte 6ES7 952-1AS00-0AA0 B)<br />
Memory Card Flash-EPROM<br />
Only required to update firmware<br />
4 Mbyte 6ES7 952-1KM00-0AA0<br />
CP 443-1<br />
6GK7 443-1EX11-0XE0<br />
Communications module for connection<br />
of SIMATIC S7-400 to<br />
Industrial Ethernet through TCP/IP<br />
<strong>and</strong> ISO; for S7 communication,<br />
S5-compatible communication<br />
(SEND/RECEIVE) with<br />
FETCH/WRITE with or without<br />
RFC 1006, 10/100 Mbit/s,<br />
with AUI/ITP <strong>and</strong> RJ45 connections,<br />
electronic manual on CD;<br />
module occupies 1 slot<br />
CP 443-5 Extended<br />
6GK7 443-5DX03-0XE0<br />
Communications module for connection<br />
of SIMATIC S7-400 to<br />
PROFIBUS as DP master or for S7<br />
communication, for increasing the<br />
number of DP lines, for data set<br />
routing with SIMATIC PDM <strong>and</strong> for<br />
10-ms time stamp,<br />
electronic manual on CD;<br />
module occupies 1 slot<br />
10/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PS 407 power supply module 6ES7 407-0KR00-0AA0<br />
for redundant use; 10 A<br />
120/230 V AC; 5 V DC/10 A,<br />
24 V DC/1 A; with battery compartment<br />
for 2 backup batteries,<br />
module occupies 2 slots<br />
PS 405 power supply module; 6ES7 405-0KA01-0AA0<br />
10 A<br />
24 V DC; 5 V DC/10 A,<br />
24 V DC/1 A; with battery compartment<br />
for 2 backup batteries,<br />
module occupies 2 slots<br />
Backup Battery<br />
6ES7 971-0BA00<br />
Type AA, 1.9 Ah<br />
UR1 Subrack<br />
6ES7 400-1TA01-0AA0<br />
18 slots<br />
UR2 Subrack<br />
6ES7 400-1JA01-0AA0<br />
9 slots<br />
UR2-H Subrack<br />
6ES7 400-2JA00-0AA0<br />
For divided central controllers;<br />
2 x 9 slots<br />
Runtime licenses for libraries<br />
PCS 7 Library Blocks V6.0 6ES7 653-2BG06-2YB0<br />
runtime license<br />
valid for one SIMATIC PCS 7 automation<br />
system<br />
trilingual (German, English,<br />
French)<br />
Type of delivery: Certificate of<br />
license<br />
<strong>Engineering</strong><br />
(see the section "<strong>Engineering</strong> system")<br />
In the case of engineering systems with st<strong>and</strong>ard engineering software<br />
SIMATIC PCS 7 V6.0 up to ServicePack 2 you must install the S7-400H<br />
option package in order to be able to configure automation systems with<br />
H architecture (H/F/FH systems). With Service Pack 3 <strong>and</strong> higher, the<br />
functionality of the S7-400H option package is already integrated in the<br />
st<strong>and</strong>ard engineering software.<br />
S7-400H V5.2 Option Package 6ES7 833-2AC01-0YB0<br />
For STEP 7 <strong>and</strong> SIMATIC PCS 7<br />
Only for engineering systems with<br />
st<strong>and</strong>ard engineering software<br />
SIMATIC PCS 7 V6.0 up to Service<br />
Pack 2<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
Y-link<br />
Y-link<br />
6ES7 197-1LA02-0XA0<br />
For connection of devices with<br />
only one PROFIBUS DP interface<br />
to a fault-tolerant automation system<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
■ Options<br />
Y-link<br />
Bus coupler for transition from a redundant PROFIBUS DP<br />
master system to a single-channel PROFIBUS DP master system<br />
For connecting devices with only one PROFIBUS DP interface<br />
to the redundant PROFIBUS DP master system AS 414H/<br />
AS 417H<br />
Detailed information on Y-link can be found at "Communication /<br />
PROFIBUS DP“
■ Overview<br />
Failsafe automation systems (F/FH systems) are used for critical<br />
applications in which an incident can result in danger to persons,<br />
plant damage or environmental pollution. They detect not<br />
only errors in the process but also their own internal errors, <strong>and</strong><br />
will automatically set the plant to a safe state if an error is detected.<br />
The failsafe automation systems (F/FH systems) based on<br />
AS 414H <strong>and</strong> AS 417H combine st<strong>and</strong>ard factory automation<br />
<strong>and</strong> safety engineering in a single system. They are certified by<br />
TÜV (German Technical Inspectorate) <strong>and</strong> comply with safety requirements<br />
class SIL 1 to SIL 3 according to IEC 61508, requirements<br />
class AK 1 to AK 6 according to DIN V 19250/DIN V<br />
VDE 0801, <strong>and</strong> category 2 to 4 according to EN 954-1.<br />
The safety function configured by the user in CFC is executed<br />
twice in various parts of the processor by means of redundant,<br />
diversified comm<strong>and</strong> processing. Potential errors are then detected<br />
in the subsequent comparison of results.<br />
■ Design<br />
The failsafe automation systems are based on the hardware of<br />
the fault-tolerant systems. The picture shows the various packaging<br />
options for failsafe systems, all of which comply with<br />
safety class SIL 3 (IEC 61508) or AK 6 (VDE 0801).<br />
<strong>Automation</strong> systems<br />
Failsafe automation systems<br />
Failsafe automation systems can be designed as single-channel<br />
systems (F systems with a CPU) <strong>and</strong> redundant systems<br />
(FH systems).<br />
The redundancy of FH systems is not relevant for failsafety. It is<br />
not used for error detection, but serves only to increase the availability<br />
of failsafe automation systems.<br />
■ Benefits<br />
7 Use of SIMATIC S7 st<strong>and</strong>ard components for failsafe applications<br />
7 Safety levels SIL 3, AK 6 can be achieved with just one CPU<br />
7 Safe monitoring of communication through PROFIBUS with<br />
PROFIsafe<br />
7 Safe communication through Industrial Ethernet plant bus<br />
7 St<strong>and</strong>ard (S) <strong>and</strong> failsafe (F) functions can be mixed in the<br />
same automation system<br />
7 S <strong>and</strong> F I/Os can be operated on the same PROFIBUS DP line<br />
7 Configuration of S <strong>and</strong> F functions using a common engineering<br />
tool - CFC<br />
7 F-Tool (S7 F <strong>System</strong>s) provides support for the TÜV acceptance:<br />
– separation of S <strong>and</strong> F functions<br />
– checksum by means of application program<br />
– comparison function<br />
– access to F functions is password protected<br />
7 Reduction of engineering costs through simple data exchange<br />
between st<strong>and</strong>ard <strong>and</strong> failsafe systems<br />
7 Minimum training requirements since same tools are used for<br />
st<strong>and</strong>ard <strong>and</strong> failsafe systems<br />
7 Simple fault analysis since same operation <strong>and</strong> monitoring for<br />
st<strong>and</strong>ard <strong>and</strong> failsafe systems (message sequence)<br />
7 Low hardware costs through mixed configurations; optimum<br />
for small applications<br />
7 Minimization of life cycle costs<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
10/9<br />
10
10<br />
<strong>Automation</strong> systems<br />
Failsafe automation systems<br />
■ Function<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Safety functions<br />
F-Runtime License<br />
6ES7 833-1CC00-6YX0<br />
The safety functions of the F/FH systems are present in the F program<br />
of the CPU <strong>and</strong> in the failsafe ET 200 I/O modules. The<br />
PROFIsafe profile is used for the safety-oriented PROFIBUS DP<br />
For processing failsafe application<br />
programs, for one<br />
AS 414F/FH or AS 417F/FH system<br />
communication between CPU <strong>and</strong> process I/Os. Using this additional<br />
safety message, F/FH systems <strong>and</strong> F I/O modules can<br />
recognize corrupt data <strong>and</strong> can initiate appropriate error re-<br />
AS 414F/FH <strong>and</strong> AS 417F/FH <strong>Engineering</strong><br />
see chapter "<strong>Engineering</strong> system")<br />
sponses.<br />
S7 F <strong>System</strong>s V5.2<br />
6ES7 833-1CC00-0YX0<br />
St<strong>and</strong>ard modules as well as failsafe I/Os can be used in F/FH<br />
systems. A plant consisting of safety-oriented <strong>and</strong> st<strong>and</strong>ard areas<br />
can thus be automated with one <strong>and</strong> the same system <strong>and</strong><br />
be configured with uniform st<strong>and</strong>ard tools.<br />
F programming tool<br />
with F block library for programming<br />
failsafe user programs on<br />
the engineering system, comprising<br />
F program software <strong>and</strong> func-<br />
Integrated in the SIMATIC Manager is the F-Tool (S7 F systems).<br />
tion block library, single license<br />
This engineering tool enables the parameterization of the CPU Bilingual (German, English)<br />
<strong>and</strong> the F signal modules as well as the generation of failsafe ap- Type of delivery:<br />
plications in the CFC based on predefined, TÜV-approved Certificate of license, software<br />
blocks. The failsafe blocks are extremely robust <strong>and</strong> intercept<br />
programming errors such as division by zero or out-of-range val-<br />
<strong>and</strong> electronic documentation on<br />
CD<br />
ues. They save the user having to perform diverse programming<br />
tasks for detecting <strong>and</strong> reacting to errors. Functions such as the<br />
In the case of engineering systems with st<strong>and</strong>ard engineering software<br />
SIMATIC PCS 7 V6.0 up to ServicePack 2 you must install the S7-400H<br />
comparison of F programs, the detection of changes in F pro- option package in order to be able to configure automation systems with<br />
gramming using a checksum, or access privileges using passwords<br />
provide further support <strong>and</strong> guarantee simple, safe operation.<br />
H architecture (H/F/FH systems). With Service Pack 3 <strong>and</strong> higher, the<br />
functionality of the S7-400H option package is already integrated in the<br />
st<strong>and</strong>ard engineering software.<br />
The application program may contain failsafe (F) <strong>and</strong> non-failsafe<br />
st<strong>and</strong>ard programs (S), where strict separation of F <strong>and</strong> S<br />
program components together with data exchange by means<br />
special conversion blocks prevent conflicts. An error detected in<br />
the F program does not result in stopping of the CPU, but leads<br />
to triggering of configurable shutdown logic which sets either the<br />
affected F sequence group or the entire F program to a safe<br />
state. The st<strong>and</strong>ard program continues to run as normal <strong>and</strong> can<br />
trigger reactions as required. After the fault is eliminated, the<br />
F program can be started again with the CPU still running.<br />
S7-400H V5.2 Option Package<br />
For STEP 7 <strong>and</strong> SIMATIC PCS 7<br />
Only for engineering systems with<br />
st<strong>and</strong>ard engineering software<br />
SIMATIC PCS 7 V6.0 up to Service<br />
Pack 2<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
6ES7 833-2AC01-0YB0<br />
10/10<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Options<br />
Order information<br />
An AS 414H or AS 417H automation system is required as hardware<br />
for a failsafe AS 414F or AS 417F automation system.<br />
Following H systems can be used, depending on the type <strong>and</strong><br />
design of the failsafe automation system:<br />
For failsafe systems (F systems): one AS 414-1H or AS 417-1H<br />
each<br />
For failsafe <strong>and</strong> system, fault-tolerant systems (FH systems),<br />
- the two subsystems on one subrack: one AS 414-2H or<br />
AS 417-2H each<br />
- the two subsystems on separate racks: two AS 414-1H or<br />
AS 417-1H each<br />
The following components are required in addition:<br />
F-Tool (S7 F <strong>System</strong>s)<br />
F programming tool with F block library for programming failsafe<br />
application programs on the engineering system (see the<br />
chapter "<strong>Engineering</strong> system")<br />
F-Runtime license<br />
for processing failsafe application programs,<br />
for one AS 414F/FH or AS 417F/FH system
Process I/O<br />
11/2 Introduction<br />
11/3 Centralized I/O<br />
11/3 Central I/O modules<br />
11/4 Expansion devices for central I/Os<br />
11/5 ET 200M distributed I/O<br />
11/5 Introduction<br />
11/6 Power supply<br />
11/6 Interface module<br />
11/7 Accessories<br />
11/8 Bundles<br />
11/9 DI - digital input modules<br />
11/11 DO - digital output modules<br />
11/13 AI - analog input modules<br />
11/14 AO - analog output modules<br />
11/15 Ex modules [EEi xb]<br />
11/16 Ex modules with HART<br />
11/17 F modules<br />
11/19 Controller modules<br />
11/20 Controller modules<br />
11/20 Counter modules<br />
11/21 ET 200iS distributed I/O<br />
11/21 Introduction<br />
11/21 Stainless steel wall housing<br />
11/22 Electronic modules<br />
11/23 Power supply <strong>and</strong> interface modules<br />
11/24 ET 200S distributed I/O<br />
11/24 Introduction<br />
11/26 Terminal modules<br />
11/28 Interface modules<br />
11/28 Power modules<br />
11/29 Digital electronic modules<br />
11/30 Analog electronic modules<br />
11/31 Motor starters<br />
11/33 SIGUARD safety engineering<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
11<br />
Process I/O<br />
Introduction<br />
■ Overview<br />
■ Design<br />
The SIMATIC PCS 7 process control system offers various options<br />
for connecting I/O devices <strong>and</strong> for detecting <strong>and</strong> emitting<br />
process signals through sensors <strong>and</strong> actuators:<br />
analog <strong>and</strong> digital I/O modules of the SIMATIC S7-400 operated<br />
centrally in the automation systems<br />
distributed ET 200M, ET 200S <strong>and</strong> ET 200iS with an extensive<br />
range of cost-effective signal <strong>and</strong> function modules, connected<br />
through PROFIBUS DP to the automation system (AS)<br />
direct AS connection of intelligent, distributed field/process<br />
devices <strong>and</strong> operator terminals through PROFIBUS DP/PA (redundant<br />
or in hazard zones 0, 1 or 2 also possible)<br />
Signal groups of the SIMATIC S7-400 can be operated centrally<br />
in the automation system <strong>and</strong> are mainly used in small applications<br />
or systems of limited distributed expansion.<br />
Characteristics such as<br />
modularity <strong>and</strong> consistency,<br />
flexible adaptability to the plant structure,<br />
minimum cabling <strong>and</strong> engineering requirements,<br />
low commissioning, service <strong>and</strong> life cycle costs <strong>and</strong> a<br />
wide range of technical options<br />
Integration of I/O modules in hazardous areas<br />
are the main reasons why distributed process peripherals are<br />
now predominant: ET 200 remote I/Os in conjunction with classic<br />
field/process devices <strong>and</strong> HART field devices or intelligent<br />
The picture shows the various possibilities for integrating I/O<br />
modules in hazardous areas:<br />
field/process devices directly on PROFIBUS.<br />
Ex I/O modules from the ET 200M spectrum<br />
■ Function<br />
The ET 200M can be run in Ex zone 2. The actuators/sensors<br />
can be positioned in Ex zone 1 when suitable Ex I/O modules are<br />
Possible online modifications among the process I/Os<br />
used. The hot swapping of I/O modules within Ex zone 2 is allowed<br />
with the right permit (e.g. fire certificate). FM approvals:<br />
ET 200M Adding/removing ET 200M stations<br />
Class I, Division 2 <strong>and</strong> Class I, Zone 2.<br />
ET 200S, ET 200iS<br />
Adding/removing new I/O modules<br />
Parameterization of I/O modules<br />
Parameterization of connected HART field devices<br />
through SIMATIC PDM<br />
Adding/removing ET 200S/iS stations<br />
Field devices with PROFIBUS PA capability<br />
Using PROFIBUS it is possible to integrate field/process devices<br />
directly in Ex zone 1 or 2, <strong>and</strong> sensors/actuators can also be integrated<br />
in zone 0. FM approvals: Class I, Division 1 <strong>and</strong> Class<br />
I, Zone 0.<br />
ET 200iS: Parameterization of I/O modules, as<br />
well as HART field devices connected to HART Integration of actuators/sensors using ET 200iS<br />
modules, through SIMATIC PDM<br />
ET 200iS can be installed directly in Ex zone 1 or 2<br />
PROFIBUS DP, Adding/removing PROFIBUS DP stations<br />
(EEx de ib [ia/ib] IIC T4), <strong>and</strong> the sensors/actuators can also be<br />
PROFIBUS PA Adding/removing DP/PA links <strong>and</strong> field devices<br />
Parameterization of field devices with<br />
SIMATIC PDM<br />
installed in zone 0 if required. FM approvals: Class I, Division 2<br />
<strong>and</strong> Class I, Zone 1.<br />
11/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
An intrinsically safe PC operator control unit can be used in hazardous<br />
areas, zone 1 or 2, if required. For further details of this<br />
operator control unit, see the catalog "Add Ons for the SIMATIC<br />
PCS 7 Process Control <strong>System</strong>“.
Process I/O<br />
Centralized I/O<br />
Central I/O modules<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data<br />
SM 421 Digital Input Modules<br />
Order No.<br />
32 inputs, 24 V DC 6ES7 421-1BL01-0AA0<br />
32 inputs, 120 V AC/DC 6ES7 421-1EL00-0AA0<br />
16 inputs, 24 V DC,<br />
with process/diagnostics interrupt<br />
6ES7 421-7BH01-0AB0<br />
16 inputs, 24 to 60 V AC/DC,<br />
with process/diagnostics interrupt<br />
6ES7 421-7DH00-0AB0<br />
16 inputs, 120/230 V AC/DC, inputs<br />
according to IEC 1131-2<br />
Type 2<br />
SM 422 Digital Output Modules<br />
6ES7 421-1FH20-0AA0<br />
32 outputs; 24 V DC, 0.5 A 6ES7 422-1BL00-0AA0<br />
32 outputs, 24 V DC, 0.5 A;<br />
with diagnostics<br />
6ES7 422-7BL00-0AB0<br />
If required, signal modules from the SIMATIC S7-400 range can<br />
be used in the SIMATIC PCS 7 automation system. These mod-<br />
16 outputs, 24 V DC; 2 A<br />
16 outputs; relay contacts<br />
6ES7 422-1BH11-0AA0<br />
6ES7 422-1HH00-0AA0<br />
ules are an alternative to distributed I/Os particularly for small 16 outputs, 120/230 V AC; 2 A 6ES7 422-1FH00-0AA0<br />
applications or plants with limited distributed expansion.<br />
SM 431 Analog Input Modules<br />
The I/O modules listed in the order data from the S7-400 signal<br />
module range were selected for SIMATIC PCS 7.<br />
16 inputs, non-floating, 13 bit<br />
8 inputs, floating, 13 bit<br />
6ES7 431-0HH00-0AB0<br />
6ES7 431-1KF00-0AB0<br />
8 inputs, floating, 14 bit, with lin- 6ES7 431-1KF10-0AB0<br />
Notes:<br />
earization (RTD/ TC)<br />
Apart from these selected modules it is also possible to use -<br />
8 inputs, floating, 14 bit 6ES7 431-1KF20-0AB0<br />
with limitations in functions - all other I/O modules from the cur- 16 inputs, floating, 16 bit; pro- 6ES7 431-7QH00-0AB0<br />
rent S7-400 signal module range.<br />
cess interrupt capability, with di-<br />
All the process data from the I/Os is available for PCS 7 engineering<br />
in the CFC <strong>and</strong> can be graphically linked to the signal<br />
names from the signal list. The diagnostics information is generated<br />
automatically when using the I/O modules listed below.<br />
agnostics interrupt<br />
8 inputs, floating, 16 bit; process<br />
interrupt capability, for thermocouples,<br />
with diagnostics interrupt<br />
6ES7 431-7KF00-0AB0 B)<br />
Integration in SIMATIC PCS 7 is limited to the process data when<br />
using other I/O components, i.e. the full range of diagnostics<br />
8 inputs, floating, 16 bit; process<br />
interrupt capability, for thermal<br />
6ES7 431-7KF10-0AB0 B)<br />
functions is not automatically available. These modules can resistors, with diagnostics inter-<br />
therefore only be used meaningfully in SIMATIC PCS 7 if it is perruptmissible to omit the diagnostics functions.<br />
SM 432 analog output modules<br />
Online modifications <strong>and</strong> redundancy are not supported by the<br />
central I/O modules.<br />
8 outputs, floating, 13 bit; for<br />
±10 V, 0 to 10 V,<br />
6ES7 432-1HF00-0AB0<br />
1 to 5 V, ± 20 mA, 0 to 20 mA,<br />
■ Technical specifications<br />
4to20 mA<br />
Front Connector (1 pc)<br />
Detailed technical data of the S7-400 modules can be found<br />
in the ST 70 catalog or<br />
in the Mall / CA 01 at "Industry automation systems / Controls /<br />
SIMATIC S7“<br />
With screw contacts<br />
With spring clamps<br />
With crimp contacts<br />
6ES7 492-1AL00-0AA0<br />
6ES7 492-1BL00-0AA0<br />
6ES7 492-1CL00-0AA0<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/3<br />
11
11<br />
Process I/O<br />
Centralized I/O<br />
Expansion devices for central I/Os<br />
■ Overview<br />
Expansion devices can be used for the distributed expansion of<br />
the SIMATIC S7-400. The IM 460-x interface modules are used<br />
as the interface for these expansion devices.<br />
Restriction compared to st<strong>and</strong>ard I/O modules from the<br />
ET 200M range<br />
no redundant connection of the expansion devices<br />
no configuration during operation<br />
Subracks<br />
The universal racks (UR modules) are used for SIMATIC PCS 7.<br />
They can be used as central racks <strong>and</strong> as expansion racks.<br />
Other module racks, see Catalog ST 70.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
IM 460-0 Interface Module 6ES7 460-0AA01-0AB0<br />
Transmitting module for central<br />
device<br />
Without transmission of voltage<br />
to the expansion device<br />
Cable up to 5 m long<br />
With K-Bus for communication<br />
with CPs <strong>and</strong> FMs in the expansion<br />
device<br />
For connecting as many as 8 expansion<br />
devices<br />
IM 461-0 Interface Module 6ES7 461-0AA01-0AA0<br />
Corresponding receiving module<br />
for the expansion device<br />
IM 460-1 Interface Module 6ES7 460-1BA01-0AB0<br />
Transmitting module for central<br />
device<br />
With transmission of the 5 V voltage<br />
supply for I/O modules<br />
Cable up to 1.5 m long<br />
Without transmission of the K-<br />
Bus, hence solely for communication<br />
from I/O modules<br />
IM 461-1 Interface Module 6ES7 461-1BA01-0AA0<br />
Corresponding receiving module<br />
for the expansion device<br />
11/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
6ES7 460-3AA01-0AB0<br />
IM 460-3 Interface Module<br />
Transmitting module for central<br />
device<br />
Without transmission of voltage<br />
to the expansion device<br />
Cable up to 100 m long<br />
With K-Bus for communication<br />
with CPs <strong>and</strong> FMs in the expansion<br />
device<br />
For connecting as many as 8 expansion<br />
devices<br />
IM 461-3 Interface Module<br />
Corresponding receiving module<br />
for the expansion device<br />
UR1 Subrack<br />
for central <strong>and</strong> expansion devices<br />
18 slots<br />
suitable for redundant power<br />
supply<br />
UR2 Subrack<br />
for central <strong>and</strong> expansion devices<br />
9 slots<br />
suitable for redundant power<br />
supply<br />
6ES7 461-3AA01-0AA0<br />
6ES7 400-1TA01-0AA0<br />
6ES7 400-1JA01-0AA0<br />
■ Accessories Order No.<br />
468-1 Connecting Cable<br />
for connecting IM 460-0 <strong>and</strong><br />
IM 461-0; IM 460-3 <strong>and</strong> IM 461-3<br />
0.75 m 6ES7 468-1AH50-0AA0<br />
1.5 m 6ES7 468-1BB50-0AA0<br />
5 m 6ES7 468-1BF00-0AA0<br />
additional lengths for connecting<br />
IM 460-3 <strong>and</strong> IM 461-3<br />
10 m 6ES7 468-1CB00-0AA0<br />
25 m 6ES7 468-1CC50-0AA0<br />
50 m 6ES7 468-1CF00-0AA0<br />
100 m 6ES7 468-1DB00-0AA0<br />
Terminating Connector<br />
6ES7 461-0AA00-7AA0<br />
for IM 461-0<br />
468-3 Connecting Cable<br />
for connecting IM 460-1 <strong>and</strong><br />
IM 461-1<br />
0.75 m 6ES7 468-3AH50-0AA0<br />
1.5 m 6ES7 468-3BB50-0AA0
■ Overview<br />
The ET 200M distributed I/O stations are the line of choice from<br />
the ET 200 family for process control applications with SIMATIC<br />
PCS 7.<br />
The ET 200M line contains a diversified selection of I/O modules<br />
in S7-300 design, some with special control functions:<br />
St<strong>and</strong>ard-S7-300 signal modules<br />
Redundant S7-300 signal modules (DI 16 x 24 V DC, with diagnostics;<br />
DO 32 x 24 V DC/0.5 A; AI 8 x 12 Bit)<br />
I & C modules with enhanced diagnostics capability<br />
Ex I/O modules<br />
Controller <strong>and</strong> counter modules<br />
HART modules<br />
F modules for failsafe applications<br />
When active bus modules are used, defective I/O modules can<br />
be replaced during operation of the plant without neighboring<br />
modules being affected (hot swapping function).<br />
Following actions are possible in RUN mode of the automation<br />
system:<br />
adding new modules within a station<br />
reparameterization of modules<br />
adding ET 200M stations<br />
The connected HART field devices can be parameterized<br />
through SIMATIC PDM.<br />
Note :<br />
Apart from these selected modules it is also possible to use -<br />
with limitations in functions - all other I/O modules from the current<br />
S7-300 signal module range.<br />
Process I/O<br />
ET 200M distributed I/O<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
■ Design<br />
The ET 200M distributed I/O station consists of<br />
1 or 2 (redundant) power supply modules,<br />
1 or 2 (redundant) IM 153 interface modules for connecting<br />
through PROFIBUS DP with data transfer rates up to 12 Mbit/s<br />
up to 8 I/O modules for connecting the sensor/actuator technology<br />
All I/O modules are optically isolated from the backplane bus.<br />
Up to 8 I/O modules can be connected to one interface module.<br />
The interface modules can be also be configured for a redundant<br />
architecture if required.<br />
In addition to the SIMATIC S7 st<strong>and</strong>ard input/output modules<br />
there are special IC I/O modules whose functions include the following:<br />
channel-specific diagnostics, e.g. wire break, short-circuit,<br />
overflow/underflow values<br />
internal module monitoring, e.g. parameterizaiton error, RAM<br />
error, fuse drop<br />
chatter monitoring for transducers<br />
pulse extension<br />
output of a parameterizable substitute value when the CPU<br />
fails<br />
The modules with diagnostics capability automatically send the<br />
corresponding signal to the operator system when a fault occurs,<br />
enabling the problem to be solved quickly <strong>and</strong> easily.<br />
The ET 200M can be run in st<strong>and</strong>ard environments or in Ex zone<br />
2. The actuators/sensors can be positioned in Ex zone 1 when<br />
suitable Ex I/O modules are used. The hot swapping of I/O modules<br />
within Ex zone 2 is allowed with the right permit (e.g. fire certificate).<br />
■ Technical specifications<br />
Detailed technical data on ET 200M <strong>and</strong> S7-300 signal modules<br />
can be found<br />
in the ST 70 catalog or<br />
in the Mall / CA 01 at "Industry automation systems / Controls<br />
/ SIMATIC S7“<br />
11/5<br />
11
11<br />
Process I/O<br />
ET 200M distributed I/O<br />
Power supply<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The PS 307 or PS 305 load power supply is used to supply power PS 307 Load Power Supply<br />
to the ET 200M. There is a choice of input voltages <strong>and</strong> output Including connection assembly;<br />
currents (AC 120/230 V with 2 A, 5 A or 10 A, or DC 24...110 V<br />
with 2 A) to suit the field of application.<br />
120/230 V AC; 24 V DC<br />
- 2 A; 50 mm wide 6ES7 307-1BA00-0AA0<br />
- 5 A; 80 mm wide 6ES7 307-1EA00-0AA0<br />
- 5 A, extended temperature<br />
range; 80 mm wide<br />
6ES7 307-1EA80-0AA0<br />
- 10A, 200mm wide<br />
PS 305 Load Power Supply<br />
Including connection assembly;<br />
24/48/60/110 V DC; 24 V DC<br />
6ES7 307-1KA01-0AA0<br />
- 2 A, extended temperature<br />
range; 80 mm wide<br />
6ES7 305-1BA80-0AA0<br />
Interface module<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
An IM 153-2 High Feature interface module is needed to connect IM 153-2 High Feature<br />
6ES7 153-2BA00-0XB0 B)<br />
the ET 200M to the PROFIBUS DP field bus. It supports the fol- Slave interface module for conlowing<br />
functions:<br />
nection of an ET 200M to<br />
7 HART configuring of intelligent field devices,<br />
PROFIBUS DP, with time stamp<br />
(accuracy 5 ms), support of<br />
7 configuration of ET 200M I/Os in RUN mode of the automation HART functionality, F modules,<br />
system,<br />
7 connection to redundant AS 414H / AS 417H automation systems,<br />
7 use of ET 200M function modules (controller <strong>and</strong> counter modules).<br />
FM modules, "Configuration in<br />
RUN" function; also for use in<br />
redundant systems<br />
IM 153-2 FO High Feature<br />
Slave interface module for connection<br />
of an ET 200M to optical<br />
6ES7 153-2BB00-0XB0 B)<br />
This interface module is also available in a fiberoptic (FO) version<br />
for connecting to an optical PROFIBUS.<br />
PROFIBUS DP; support of HART<br />
functionality, F modules, FM modules,<br />
"Configuration in RUN" function;<br />
also for use in redundant<br />
systems<br />
Notes:<br />
Plastic fiberoptic cables <strong>and</strong> a mounting set for simplex connectors<br />
are required for use of the IM 153-2 FO (see "Plastic fiberoptic<br />
cables“ in the section "Communication/PROFI-<br />
BUS“)<br />
The active bus modules <strong>and</strong> the profile rail for hot swapping are<br />
required in order to be able to use the hot swapping function.<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
11/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
The picture shows the various bus modules being used for hot<br />
swapping. Top: for redundant connection, Bottom: for singular<br />
connection.<br />
Process I/O<br />
ET 200M distributed I/O<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Following components are available as accessories for the Bus Modules for Hot Swapping<br />
ET 200M:<br />
BM PS/IM for power supply <strong>and</strong> 6ES7 195-7HA00-0XA0<br />
Bus modules for hot swapping<br />
Profile rails for hot swapping<br />
Covers for bus backplanes <strong>and</strong> bus modules<br />
IM 153,<br />
incl. 1 bus module cover<br />
BM 2x40 for 2 modules, each<br />
40 mm wide<br />
6ES7 195-7HB00-0XA0<br />
Front connectors<br />
BM 1x80 for 1 module, 80 mm 6ES7 195-7HC00-0XA0<br />
Ex partition for ET 200M<br />
wide<br />
LK 393 cable duct<br />
IM 153/IM 153<br />
for two IM 153-2/-2 FOs for design<br />
of redundant systems<br />
6ES7 195-7HD10-0XA0<br />
Ex partition<br />
Profile Rail for Hot Swapping<br />
A mechanical isolation is required between the IM 153 interface 482 mm long (19 inches) 6ES7 195-1GA00-0XA0<br />
module <strong>and</strong> the first Ex I/O module. For the hot swapping function,<br />
an Ex partition is installed which guarantees the prescribed<br />
isolation distance between non-intrinsically-safe <strong>and</strong> intrinsi-<br />
530 mm long<br />
630 mm long<br />
6ES7 195-1GF30-0XA0<br />
6ES7 195-1GG30-0XA0<br />
cally-safe areas of the ET 200M distributed I/O system.<br />
Covers<br />
6ES7 195-1JA00-0XA0<br />
LK 393 cable duct<br />
Pack with 4 backplane bus covers<br />
<strong>and</strong> 1 bus module cover<br />
The LK 393 cable duct guarantees the prescribed isolation between<br />
the load voltage input <strong>and</strong> the intrinsically safe inputs/outputs.<br />
The cable duct is easy to fit following insertion of the load<br />
Front Connector (1 pcs)<br />
20-pin, with screw contacts 6ES7 392-1AJ00-0AA0<br />
voltage inputs L+.<br />
20-pin, with spring contacts 6ES7 392-1BJ00-0AA0<br />
■ Design<br />
40-pin, with screw contacts<br />
40-pin, with spring contacts<br />
6ES7 392-1AM00-0AA0<br />
6ES7 392-1BM01-0AA0<br />
Front connector for Ex analog<br />
input module 6ES7 331-7SF00-<br />
0AB0 (1 pcs)<br />
20-pin, with screw contacts<br />
enables an accuracy of ± 1.5 K<br />
for the internal reference point<br />
temperature when taking thermoelement<br />
temperature measurements<br />
in the measuring mode<br />
"internal compensation" at ambient<br />
temperatures of 0 ... 60 °C<br />
6ES7 392-1AJ20-0AA0<br />
Ex partition for ET 200M<br />
Separation of IM 153 <strong>and</strong> downstream<br />
Ex modules within an<br />
ET 200M line<br />
Mixed operation of non-Ex <strong>and</strong><br />
Ex modules within an ET 200M<br />
line<br />
for supporting the hot swapping<br />
function in connection with<br />
IM 153-2<br />
6ES7 195-1KA00-0XA0<br />
LK 393 cable duct<br />
[EEx ib] IIC-conform routing of<br />
load voltage cable in front plug,<br />
5pcs<br />
6ES7 393-4AA00-0AA0<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Accessories<br />
11/7<br />
11
11<br />
Process I/O<br />
ET 200M distributed I/O<br />
Bundles<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Following preassembled bundles are available for ET 200M: I/O Subsystem ZuS<br />
I/O Subsystem ZuS:<br />
ET 200M with hot swapping of modules, comprising<br />
- profile rail for active bus modules,<br />
- PS/IM bus module <strong>and</strong><br />
- IM 153-2 High Feature bus interface module<br />
IM 153 redundancy bundle:<br />
comprising two IM 153-2 High Feature <strong>and</strong> one active<br />
ET 200M with hot swapping of<br />
modules, comprising profile rail<br />
for active bus modules size 482<br />
mm (19 inches), PS/IM bus module<br />
<strong>and</strong><br />
IM 153-2 High Feature bus interface<br />
module<br />
for support of HART functional-<br />
6ES7 654-0XX06-1XA0 B)<br />
IM 153/IM 153 bus module, for operating the ET 200M on the ity, F modules, FM modules,<br />
fault-tolerant AS 414H / AS 417H automation system.<br />
HART bundle with Ex analog input modules for redundant<br />
PROFIBUS connection,<br />
for operation in the AS 414H / AS 417H fault-tolerant automa-<br />
Configuration in RUN" function;<br />
also for use in redundant systems<br />
IM 153 Redundancy Bundle 6ES7 153-2AR01-0XA0 B)<br />
tion system, comprising<br />
comprising two IM 153-2 High<br />
- one 482 mm profile rail,<br />
- one IM 153 / IM 153 active bus module,<br />
- four 2x40 bus modules,<br />
- two IM 153-2 High Feature <strong>and</strong><br />
- eight HART-capable Ex analog input modules.<br />
Feature <strong>and</strong> one active<br />
IM 153/IM 153 bus module,<br />
for operating the ET 200M on the<br />
fault-tolerant AS 414H / AS 417H<br />
automation system<br />
HART bundle with Ex AI modules<br />
[EEx ib]<br />
for redundant PROFIBUS connection,<br />
comprising:<br />
two IM 153-2 High Feature interface<br />
modules<br />
8 Ex analog input modules with<br />
HART<br />
one IM 153 / IM 153 bus module<br />
four 2x40 bus modules for<br />
2 modules<br />
one 482 mm profile rail<br />
6ES7 650-0XX06-0XX0 B)<br />
11/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
16 inputs, 48...125 V DC,<br />
floating in groups of 8<br />
required front connector: 20-pin<br />
16 inputs, 48...125 V DC,<br />
floating in groups of 8;<br />
temperature range -25...+60 °C<br />
required front connector: 20-pin<br />
6ES7 321-1CH20-0AA0<br />
6AG1 321-1CH20-2AA0 B)<br />
Process I/O<br />
ET 200M distributed I/O<br />
DI - digital input modules<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The digital input modules described here break down into SM 321 for floating contacts (with DC/AC supply)<br />
simple signal modules for direct <strong>and</strong> alternating voltage, <strong>and</strong><br />
modules with diagnostics capability that send a corresponding<br />
signal to the operator system when a fault occurs.<br />
16 inputs, 24...48 V AC/DC, 6ES7 321-1CH00-0AA0<br />
floating in groups of 1<br />
required front connector: 40-pin<br />
SM 321 for floating contacts (with AC supply)<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
32 inputs, 120 V AC,<br />
floating in groups of 8<br />
6ES7 321-1EL00-0AA0<br />
SM 321 for Floating Contacts (with DC supply)<br />
required front connector: 40-pin<br />
16 inputs, 24 V DC,<br />
floating in groups of 16, redundant<br />
design possible<br />
required front connector: 20-pin<br />
6ES7 321-1BH02-0AA0<br />
8 inputs, 120/230 V AC,<br />
floating in groups of 2, redundant<br />
design possible<br />
required front connector: 20-pin<br />
6ES7 321-1FF01-0AA0<br />
16 inputs, 24 V DC,<br />
floating in groups of 16;<br />
temperature range -25...+60 °C<br />
required front connector: 20-pin<br />
6AG1 321-1BH02-2AA0 B)<br />
8 inputs, 120/230 V AC,<br />
floating in groups of 2;<br />
temperature range -25...+60 °C<br />
required front connector: 20-pin<br />
6AG1 321-1FF01-2AA0 B)<br />
16 inputs, 24 V DC,<br />
floating in groups of 16; m-reading<br />
6ES7 321-1BH50-0AA0<br />
16 inputs, 120/230 V AC,<br />
floating in groups of 4<br />
required front connector: 20-pin<br />
6ES7 321-1FH00-0AA0<br />
required front connector: 20-pin<br />
SM 321 for non-floating contacts (with AC supply)<br />
16 inputs, 24 V DC, High Speed<br />
floating in groups of 16;<br />
0.05 ms input delay<br />
required front connector: 20-pin<br />
32 inputs, 24 V DC,<br />
floating in groups of 16, redundant<br />
design possible<br />
required front connector: 40-pin<br />
32 inputs, 24 V DC,<br />
floating in groups of 16;<br />
6ES7 321-1BH10-0AA0<br />
6ES7 321-1BL00-0AA0<br />
6AG1 321-1BL00-2AA0 B)<br />
8 inputs, 120/230 V AC,<br />
floating in groups of 1<br />
required front connector: 40-pin<br />
SM 323 Digital I/O Module<br />
8 inputs 24 V DC,<br />
8 outputs 24 V DC, 0.5 A;<br />
temperature range -25...+60 °C<br />
required front connector: 20-pin<br />
6ES7 321-1FF10-0AA0<br />
6AG1 323-1BH01-2AA0<br />
B)<br />
B)<br />
temperature range -25...+60 °C<br />
required front connector: 40-pin<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/9<br />
11
11<br />
Process I/O<br />
ET 200M distributed I/O<br />
DI - digital input modules<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SM 321 Modules with Diagnostics Capability (IM 153-2 High Feature<br />
interface module required)<br />
For floating contacts (with DC supply)<br />
16 inputs, 24 V DC<br />
- Floating in groups of 16, redundant<br />
design possible<br />
- Time stamp in connection<br />
with IM 153-2 High Feature,<br />
5 ms accuracy, rising or falling<br />
edge, channelselective<br />
parameterization possible<br />
- Two short-circuit resistant sensor<br />
power supplies, each for<br />
8 channels<br />
- Sensor power supply through<br />
the module; external redundant<br />
sensor power supply also<br />
possible<br />
- Diagnostics of missing sensor<br />
power supply for channel<br />
group (8 channels)<br />
- Diagnostics inside module<br />
- Wire break monitoring<br />
- required front connector:<br />
20-pin<br />
6ES7 321-7BH01-0AB0<br />
16 inputs, 24 V DC<br />
- Data same as 6ES7 321-<br />
7BH01-0AB0,<br />
- <strong>and</strong> temperature range -<br />
25...+60 °C<br />
- required front connector:<br />
20-pin<br />
6AG1 321-7BH01-2AB0 B)<br />
11/10<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
6ES7 321-7TH00-0AB0<br />
16 inputs, NAMUR<br />
- Floating in groups of 8, redundant<br />
design possible<br />
- Time stamp in connection<br />
with IM 153-2 High Feature,<br />
5 ms accuracy, rising or falling<br />
edge, channelselective<br />
parameterization possible<br />
- Two sensor power supplies<br />
(each 8.2 V DC or 18 V DC)<br />
- Connection of NAMUR sensors<br />
or contacts with resistor<br />
circuit<br />
- Pulse extension<br />
- Channel-selective diagnostics<br />
(short circuit, wire break, chatter<br />
monitoring, discrepancy<br />
between changeover contacts)<br />
- Diagnostics inside module<br />
- required front connector:<br />
40-pin<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
Process I/O<br />
ET 200M distributed I/O<br />
DO - digital output modules<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The digital output modules described here break down into<br />
simple signal modules for direct <strong>and</strong> alternating voltage with<br />
different output currents per channel, with a selection of relay<br />
modules available for high output currents <strong>and</strong> voltages,<br />
modules with diagnostics capability that supply data for trou-<br />
SM 322 for AC Voltage<br />
(suitable for AC magnet coils, contactors, motor starters, miniature<br />
motors <strong>and</strong> indicator lights)<br />
8 outputs, 120/230 V AC / 2 A, 6ES7 322-1FF01-0AA0<br />
floating in groups of 4, redundant<br />
design possible<br />
bleshooting <strong>and</strong> enable parameterizable reactions to the fail- required front connector: 20-pin<br />
ure of the automation system.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
16 outputs, 120/230 V AC / 1 A,<br />
floating in groups of 8<br />
required front connector: 20-pin<br />
6ES7 322-1FH00-0AA0<br />
SM 322 for Direct Voltage<br />
(suitable for solenoid valves, contactors, indicator lights etc.)<br />
32 outputs, 120/230 V AC / 1 A,<br />
floating in groups of 8<br />
6ES7 322-1FL00-0AA0<br />
8 outputs, 24 V DC / 2 A,<br />
floating in groups of 4, redun-<br />
6ES7 322-1BF01-0AA0<br />
required front connector:<br />
2x20-pin<br />
dant design possible<br />
required front connector: 20-pin<br />
SM 322 for Relay Output<br />
(suitable for AC/DC solenoid valves, contactors, motor starters,<br />
16 outputs, 24 V DC / 0.5 A, 6ES7 322-1BH01-0AA0<br />
miniature motors <strong>and</strong> indicator lights)<br />
floating in groups of 8<br />
required front connector: 20-pin<br />
8 outputs, 24...120 V DC,<br />
48...230 V AC / max. 2 A,<br />
6ES7 322-1HF01-0AA0<br />
16 outputs, 24 V DC / 0.5 A,<br />
floating in groups of 8;<br />
6AG1 322-1BH01-2AA0 B) floating in groups of 2<br />
required front connector: 20-pin<br />
temperature range -25...+60 °C<br />
required front connector: 20-pin<br />
8 outputs, 24...120 V DC,<br />
48...230 V AC / max. 5 A,<br />
6ES7 322-1HF10-0AA0<br />
16 inputs, 24 V DC / 0.5 A, High<br />
Speed<br />
6ES7 322-1BH10-0AA0<br />
floating in groups of 1<br />
required front connector: 40-pin<br />
floating in groups of 8;<br />
0.2 ms input delay<br />
required front connector: 20-pin<br />
8 outputs, 24...120 V AC,<br />
48...230 V AC, max. 5 A<br />
floating in groups of 1;<br />
6AG1 322-1HF10-2AA0 B)<br />
32 outputs, 24 V DC / 0.5 A,<br />
floating in groups of 8, redun-<br />
6ES7 322-1BL00-0AA0<br />
temperature range -25...+60 °C<br />
required front connector: 40-pin<br />
dant design possible<br />
required front connector: 40-pin<br />
16 outputs, 24...120 V DC,<br />
48...230 V AC / max. 2 A,<br />
6ES7 322-1HH01-0AA0<br />
8 outputs, 48...125 V DC / 1.5 A,<br />
floating in groups of 4<br />
6ES7 322-1CF00-0AA0 B) floating in groups of 8<br />
required front connector: 20-pin<br />
required front connector: 20-pin<br />
SM 323 Digital I/O Module<br />
8 outputs, 48...120 V DC / 1.5 A,<br />
floating in groups of 4;<br />
temperature range -25...+60 °C<br />
required front connector: 20-pin<br />
6AG1 322-1CF00-2AA0 B) 8 inputs 24 V DC,<br />
8 outputs 24 V DC, 0.5 A;<br />
temperature range -25...+60 °C<br />
required front connector: 20-pin<br />
6AG1 323-1BH01-2AA0 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/11<br />
11
11<br />
Process I/O<br />
ET 200M distributed I/O<br />
DO - digital output modules<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SM 322 Modules with Diagnostics Capability (with channel <strong>and</strong><br />
module diagnostics)<br />
For direct voltage<br />
(suitable for solenoid valves, DC contactors <strong>and</strong> indicator lights)<br />
8 outputs, 24 V DC / 0.5 A,<br />
floating in groups of 8, redundant<br />
design possible<br />
- Two connections per output<br />
(with <strong>and</strong> without series diode)<br />
- Connecting a default value by<br />
channel in the event of CPU<br />
stop (parameterizable)<br />
- Broken wire monitoring by<br />
channel<br />
- Monitoring of load voltage per<br />
channel<br />
- Short-circuit monitoring according<br />
to M/L+ per channel<br />
- Diagnostics functions inside<br />
the module<br />
- required front connector:<br />
20-pin<br />
6ES7 322-8BF00-0AB0<br />
8 outputs, 24 V DC / 0.5 A,<br />
floating in groups of 8<br />
- Data same as 6ES7 322-<br />
8BF00-0AB0,<br />
- <strong>and</strong> temperature range<br />
-25...+60 °C<br />
- required front connector:<br />
20-pin<br />
6AG1 322-8BF00-2AB0 B)<br />
16 outputs, 24 V DC / 0.5 A,<br />
floating in groups of 4<br />
- Connecting a default value by<br />
channel in the event of CPU<br />
stop (parameterizable)<br />
- Broken wire monitoring per<br />
channel (with 0 <strong>and</strong> 1 signal)<br />
- Signal when output is overloaded<br />
- Monitoring of load voltage or<br />
ground per channel group<br />
- Short-circuit monitoring according<br />
to M/L+ per channel<br />
- Diagnostics functions inside<br />
the module<br />
- required front connector: 40pin<br />
11/12<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
6ES7 322-8BH01-0AB0<br />
■ Selection <strong>and</strong> Ordering Data<br />
For AC voltage<br />
Order No.<br />
(suitable for AC magnet coils, contactors, motor starters, miniature<br />
motors <strong>and</strong> indicator lights)<br />
8 outputs, 120/230 V AC / 2 A,<br />
floating in groups of 1<br />
- Connecting a default value by<br />
channel in the event of CPU<br />
stop (parameterizable)<br />
- Diagnostics functions inside<br />
the module<br />
required front connector:<br />
40-pin<br />
6ES7 322-5FF00-0AB0 B)<br />
16 outputs, 24/48 V AC/DC /<br />
0.5 A,<br />
floating in groups of 1<br />
- Connecting a default value by<br />
channel in the event of CPU<br />
stop (parameterizable)<br />
- Diagnostics functions inside<br />
the module<br />
- required front connector:<br />
40-pin<br />
For relay output<br />
6ES7 322-5GH00-0AB0 B)<br />
(suitable for AC/DC magnet coils, contactors, motor starters, miniature<br />
motors <strong>and</strong> indicator lights<br />
8 outputs, 24...120 V DC,<br />
24...230 V AC / max. 5 A,<br />
floating in groups of 1<br />
- With RC quenching element<br />
for protecting the contacts per<br />
channel<br />
- Connecting a default value by<br />
channel in the event of CPU<br />
stop (parameterizable)<br />
- Diagnostics functions inside<br />
the module<br />
- required front connector:<br />
40-pin<br />
6ES7 322-5HF00-0AB0 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
SM 331 Modules for Current/Voltage Measurement <strong>and</strong> Temperature<br />
Measurement<br />
8 inputs, individually parameterizable<br />
- Resolution 12 bit + sign<br />
- Current measurement<br />
0/4...20 mA (8 channels;<br />
2 wires with external supply or<br />
4wires)<br />
- Voltage measurement<br />
(8 channels)<br />
- Resistance thermometer<br />
Pt100, Ni100, Ni1000, LG-<br />
Ni1000 (8 channels; 2, 3 or<br />
4wires)<br />
- required front connector: 40-pin<br />
6ES7 331-1KF01-0AB0<br />
8 inputs in 4 channel groups, redundant<br />
design possible<br />
- Changeover of measurement<br />
type by range module per<br />
channel group<br />
- Resolution 14 bit + sign<br />
- Current measurement<br />
0/4...20 mA (8 channels; 2 or 4<br />
wires)<br />
- Voltage measurement<br />
(8 channels)<br />
- Resistance thermometer<br />
Pt100, Ni100 (4 channels, 2 or<br />
4wires)<br />
- Thermocouples type E, N, J, K,<br />
L (8 channels),<br />
internal compensation or external<br />
compensation with compensating<br />
box or 0 °C<br />
comparison point<br />
- Wire break monitoring<br />
- Redundant design possible<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
6ES7 331-7KF02-0AB0<br />
2 inputs in 1 channel group<br />
- Changeover of measurement<br />
type by range module<br />
- Resolution 14 bit + sign<br />
- Current measurement<br />
0/4...20 mA (2 channels; 2 or 4<br />
wires)<br />
- Voltage measurement<br />
(2 channels)<br />
- Resistance thermometer<br />
Pt100, Ni100 (1 channel, 2 or<br />
4wires)<br />
- Thermocouples type E, N, J, K,<br />
L (2 channels),<br />
internal compensation or external<br />
compensation with compensating<br />
box or 0 °C<br />
comparison point<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
6ES7 331-7KB02-0AB0 B)<br />
Process I/O<br />
ET 200M distributed I/O<br />
AI - analog input modules<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The analog input modules described here break down into<br />
multifunction modules for current, voltage <strong>and</strong> temperature<br />
measurement, <strong>and</strong><br />
2 inputs in 1 channel group<br />
- Data same as 6ES7 331-<br />
7KB02-0AB0,<br />
- <strong>and</strong> temperature range<br />
6AG1 331-7KB02-2AB0 B)<br />
special high-precision modules for current/voltage measurement<br />
or temperature measurement.<br />
-25...+60 °C<br />
- required front connector:<br />
20-pin<br />
All modules automatically supply channel-specific <strong>and</strong> moduleinternal<br />
diagnostics data, except module 6ES7 331-1KF00-<br />
0AB0. With the latter module, channel failure is identified by the<br />
PCS 7 analog driver block.<br />
SM 331 Modules for Current <strong>and</strong> Voltage Measurement<br />
8 inputs in 4 channel groups, 6ES7 331-7NF00-0AB0<br />
redundant design possible<br />
- Resolution 15 bit + sign<br />
B)<br />
The individual channels of the analog input modules can be parameterized<br />
in groups independently of each other.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
- Current measurement<br />
0/4...20 mA (8 channels; 2 or 4<br />
wires)<br />
- Voltage measurement<br />
(8 channels)<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
- required front connector: 40-pin<br />
8 inputs in 4 channel groups<br />
- Resolution 15 bit + sign<br />
- Fast module cycle (min. 10 ms<br />
for 4 channels)<br />
- Current measurement<br />
0/4...20 mA (8 channels;<br />
2 wires with external supply or<br />
4wires)<br />
- Voltage measurement<br />
(8 channels)<br />
- Wire break monitoring<br />
- Short-circuit-proof<br />
- Isolation between channel<br />
groups<br />
- Diagnostics inside module<br />
- required front connector: 40-pin<br />
6ES7 331-7NF10-0AB0 B)<br />
SM 331 Modules for Temperature Measurement<br />
8 inputs in 4 channel groups<br />
- Resolution 15 bit<br />
- Resistance thermometer<br />
Pt100...1000, Ni100...1000,<br />
Cu10 (8 channels; 2, 3 or<br />
4wires)<br />
- Short-circuit-proof<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
- required front connector: 40-pin<br />
6ES7 331-7PF00-0AB0 B)<br />
8 inputs in 4 channel groups<br />
- Resolution 15 bit<br />
- Thermocouples type B, C, N,<br />
E, R, S, J, L, T, K, U<br />
(8 channels),<br />
internal compensation; external<br />
compensation with Pt100<br />
through separate inputs possible<br />
- Fast module cycle (10 ms for<br />
4 channels)<br />
- Short-circuit-proof<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
- required front connector: 40-pin<br />
6ES7 331-7PF10-0AB0 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/13<br />
11
11<br />
Process I/O<br />
ET 200M distributed I/O<br />
AO - analog output modules<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The analog output modules for voltage <strong>and</strong> current described SM 332 Modules for Current <strong>and</strong> Voltage Outputs<br />
here break down into<br />
2 outputs in 2 channel groups 6ES7 332-5HB01-0AB0<br />
modules with 12 bit resolution <strong>and</strong> various numbers of channels,<br />
<strong>and</strong><br />
a high-precision module with 15 bit resolution.<br />
- Resolution 12 bit + sign<br />
- Voltage 0/1...5/10 V; ±10 V<br />
(2 channels; 2 or 4 wires)<br />
- Current 0/4...20 mA; ±20 mA<br />
The analog output modules can be parameterized in groups independently<br />
of each other <strong>and</strong> automatically supply all channelspecific<br />
<strong>and</strong> module-internal diagnostics data.<br />
(2 channels; 2 wires)<br />
- Parameterizable substitute<br />
value output in case of CPU<br />
stop<br />
- Broken wire monitoring (only<br />
for current)<br />
- Short circuit monitoring (only<br />
for voltage)<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
2 outputs in 2 channel groups<br />
- Data same as 6ES7 332-<br />
5HB01-0AB0,<br />
- <strong>and</strong> temperature range<br />
-25...+60 °C<br />
- required front connector: 20-pin<br />
6AG1 332-5HB01-2AB0 B)<br />
4 outputs in 4 channel groups,<br />
redundant design possible<br />
- Resolution 12 bit + sign<br />
- Voltage 0/1...5/10 V; ±10 V<br />
(4 channels; 4 wires)<br />
- Current 0/4...20 mA; ±20 mA<br />
(4 channels; 2 wires)<br />
- Parameterizable substitute<br />
value output in case of CPU<br />
stop<br />
- Broken wire monitoring (only<br />
for current)<br />
- Short circuit monitoring (only<br />
for voltage)<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
6ES7 332-5HD01-0AB0<br />
8 outputs in 8 channel groups,<br />
redundant design possible<br />
- Resolution 12 bit + sign<br />
- Voltage 0/1...5/10 V; ±10 V<br />
(8 channels; 4 wires)<br />
- Current 0/4...20 mA; ±20 mA<br />
(8 channels; 2 wires)<br />
- Parameterizable substitute<br />
value output in case of CPU<br />
stop<br />
- Broken wire monitoring (only<br />
for current)<br />
- Short circuit monitoring (only<br />
for voltage)<br />
- Diagnostics inside module<br />
- required front connector: 40-pin<br />
6ES7 332-5HF00-0AB0<br />
4 outputs in 4 channel groups<br />
- Resolution 15 bit + sign<br />
- Voltage 0/1...5/10 V; ±10 V<br />
(4 channels; 4 wires)<br />
- Current 0/4...20 mA; ±20 mA<br />
(4 channels; 2 wires)<br />
- Parameterizable substitute<br />
value output in case of CPU<br />
stop<br />
- Isolated by channel<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
6ES7 332-7ND01-0AB0 B)<br />
11/14<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
Process I/O<br />
ET 200M distributed I/O<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
Ex modules [EEi xb]<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The following analog <strong>and</strong> digital I/O modules are suitable for use Ex Analog Modules<br />
in hazardous plants. They separate the non-intrinsically safe<br />
electrical circuits of the automation system <strong>and</strong> the intrinsically<br />
safe electrical circuit of the process. Sensors <strong>and</strong> actuators suitable<br />
for placing in zone 1 <strong>and</strong> 2 hazardous areas as well as intrinsically<br />
safe equipment compliant with DIN 50020 <strong>and</strong><br />
[EEx ib] IIC can be operated from these modules.<br />
Ex Analog Input Module<br />
4 inputs, 0/4...20 mA in<br />
4 channel groups, redundant<br />
design possible<br />
- Individually floating channels<br />
- Resolution 15 bit + sign<br />
6ES7 331-7RD00-0AB0<br />
All Ex modules with HART come with diagnostics capability<br />
(channel <strong>and</strong> module diagnostics).<br />
- Connection of 2 or 4-wire measurement<br />
transducer possible<br />
- Wire break monitoring<br />
- Measurement range monitor-<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
ing<br />
- Short-circuit-proof<br />
Ex Digital Modules<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
Ex Digital Input Modules<br />
8 inputs in 4 channel groups 6ES7 331-7SF00-0AB0<br />
4 NAMUR inputs in 4 channel<br />
groups, redundant design possible<br />
- Voltage supply to sensors<br />
8.2 V<br />
- Individually floating channels<br />
- Wire break <strong>and</strong> short-circuit<br />
monitoring (directly at the contact<br />
for contacts with external<br />
resistor circuit)<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
Ex Digital Output Module<br />
4 outputs, 24 V DC / 10 mA in<br />
4 channel groups, redundant<br />
design possible<br />
- Individually floating channels<br />
- Wire break monitoring<br />
- Short-circuit monitoring<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
6ES7 321-7RD00-0AB0<br />
6ES7 322-5SD00-0AB0<br />
- Resolution 15 bit + sign<br />
- Thermocouples type T, U, E, J,<br />
L, K, N, R, S, B (8 channels),<br />
internal compensation; external<br />
compensation with Pt100<br />
(2 channels), compensating<br />
box or 0/50°C comparison<br />
point<br />
- Resistance thermometer<br />
Pt100, Pt200, Ni100<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
Note :<br />
A special front connector for the<br />
Ex analog input module 6ES7<br />
331-7SF00-0AB0 enables greater<br />
accuracy when taking thermocouple<br />
temperature measurements<br />
in "internal compensation"<br />
measuring mode (see the section<br />
"Accessories").<br />
4 outputs, 15 V DC / 20 mA in<br />
4 channel groups, redundant<br />
design possible<br />
- Individually floating channels<br />
- Wire break monitoring<br />
- Short-circuit monitoring<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
6ES7 322-5RD00-0AB0<br />
Ex Analog Output Module<br />
4 outputs, 0/4...20 mA in<br />
4 channel groups<br />
- Individually floating channels<br />
- Resolution 15 bit<br />
- for 2-wire measurement transducers<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
- required front connector: 20-pin<br />
6ES7 332-5RD00-0AB0 B)<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/15<br />
11
11<br />
Process I/O<br />
ET 200M distributed I/O<br />
Ex modules with HART<br />
■ Overview<br />
The Ex modules with HART (Highway Addressable Remote<br />
Transducer), which can be used in distributed I/O devices of the<br />
ET 200M (with IM 153-2 High Feature interface module), enable<br />
HART devices with approval for potentially explosive areas to be<br />
connected to SIMATIC PCS 7 automation systems .<br />
All measurement transducers <strong>and</strong> HART actuators that are certified<br />
for digital communication with the HART protocol can be<br />
connected through these modules.<br />
In addition, conventional transducers with 4 to 20 mA technology<br />
without HART protocol can also be connected<br />
All Ex modules with HART come with diagnostics capability<br />
(channel <strong>and</strong> module diagnostics).<br />
■ Application<br />
HART is a serial transfer protocol which is used to transfer additional<br />
parameter data, such as measurement range, isolation<br />
etc. to connected measuring transducers <strong>and</strong> actuators through<br />
a 4 to 20 mA power loop. The Ex I/O modules offered here enable<br />
the HART protocol to also be used for communication with<br />
HART devices in the hazardous area. The modules themselves<br />
<strong>and</strong> the ET 200M are positioned in the safe area of in Ex zone 2.<br />
A KEMA certificate confirms that the modules are approved for<br />
operation with HART devices in the hazardous area.<br />
■ Function<br />
The HART jobs can be initiated remotely for each channel<br />
through PROFIBUS DP. This usually takes place from the central<br />
engineering system of the SIMATIC PCS 7 process control system<br />
using SIMATIC PDM.<br />
The Ex modules with HART have the following characteristics:<br />
Connection compatibility with conventional analog modules of<br />
the ET 200M<br />
Additional communication option through the current loop<br />
Low energy requirement<br />
2 analog channels per module<br />
Each channel is a primary master of the HART protocol<br />
All channels can be operated by several clients simultaneously<br />
<strong>and</strong> independently of one another<br />
The channels are electrically isolated from one another<br />
Selectable current signal per channel:<br />
- 0...20 mA (without HART function)<br />
- 4...20 mA (with/without HART function)<br />
Parameterization<br />
Remote parameterization is possible for:<br />
- conversion time,<br />
- resolution,<br />
- limit values,<br />
- alarms, etc.<br />
Remote parameterization of the HART measurement transducers<br />
<strong>and</strong> actuators is possible with SIMATIC PDM through<br />
PROFIBUS DP<br />
It is still possible to parameterize the HART devices with an<br />
operator terminal.<br />
11/16<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Technical specifications<br />
Detailed technical data of the Ex modules with HART can be<br />
found<br />
in the IK PI catalog (section "Distributed I/Os“) or<br />
in the Mall / CA 01 at "Distributed I/Os / ET 200M“<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Ex Analog Input Module with<br />
HART [EEx ib]<br />
2 inputs, 0/4...20 mA in<br />
2 channel groups<br />
- Individually floating channels<br />
- Resolution: 15 bit + sign<br />
- Connection of 2 or 4-wire measurement<br />
transducers possible<br />
- Wire break monitoring<br />
- Short-circuit-proof<br />
- HART (2 or 4 wires)<br />
- required front connector: 20-pin<br />
6ES7 331-7TB00-0AB0 B)<br />
6ES7 650-0XX06-0XX0 B)<br />
HART bundle with<br />
Ex IO modules [EEx ib]<br />
for redundant PROFIBUS connection,<br />
comprising:<br />
two IM 153-2 High Feature interface<br />
modules<br />
8 Ex analog input modules with<br />
HART<br />
one IM 153 / IM 153 bus module<br />
four 2x40 bus modules for<br />
2 modules<br />
one 482 mm profile rail<br />
Note: The load power supply<br />
(PS 305/307) has to be ordered<br />
separately<br />
Ex Analog Output Module with<br />
HART [EEx ib]<br />
2 outputs, 0/4...20 mA in<br />
2 channel groups<br />
- Individually floating channels<br />
- Resolution: 12 bit + sign<br />
- For 2-wire actuators<br />
- Wire break monitoring<br />
-HART<br />
- required front connector: 20-pin<br />
6ES7 332-5TB00-0AB0 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
Process I/O<br />
ET 200M distributed I/O<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
F modules<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The special safety functions of the failsafe systems are coordinated<br />
with the failsafe I/O modules of the distributed ET 200M<br />
SM 326F Failsafe Digital Output<br />
Module<br />
6ES7 326-2BF01-0AB0<br />
devices, whose job it is to also ensure plant safety should the 10 outputs, 24 V DC, 2 A,<br />
CPU fail. The failsafe signal modules of these peripheral devices<br />
(digital inputs/outputs, analog input) are able to diagnose internal<br />
<strong>and</strong> external errors, have a redundant setup on account of<br />
safety dem<strong>and</strong>s, <strong>and</strong> meet requirements up to SIL 3 (IEC 61508)<br />
or AK 6 (VDE 0801).<br />
floating in groups of 5, redundant<br />
design possible (outputs<br />
with internal diode)<br />
- SIL 2, SIL 3 | parameterizable<br />
(10 channels)<br />
- Wire break <strong>and</strong> short-circuit<br />
The input modules work in SIL 3/AK 6 with internal 2-of-2 channel<br />
evaluation. A safety response is triggered immediately there<br />
are any differences. The digital output modules enable safe disconnection<br />
through a second disconnect path in the event of a<br />
faulty output.<br />
monitoring<br />
- Diagnostics inside module<br />
- ProfiSafe frame<br />
SM 336F Failsafe Analog Input<br />
Module<br />
6 inputs, 4...20 mA, redundant<br />
6ES7 336-1HE00-0AB0<br />
■ Selection <strong>and</strong> Ordering Data<br />
SM 326F Failsafe Digital Input<br />
Module<br />
for floating contacts<br />
Order No.<br />
design possible<br />
- Isolated from the backplane<br />
bus<br />
- 2- or 4-wire connection<br />
- SIL 2: two-channel evaluation,<br />
6 sensors<br />
24 inputs, 24 V DC,<br />
floating in groups of 12, redundant<br />
design possible<br />
- 4 short-circuit resistant sensor<br />
power supplies, each for<br />
6 channels, floating in groups<br />
of 3<br />
- External sensor power supply<br />
6ES7 326-1BK00-0AB0<br />
- SIL 3: two-channel evaluation,<br />
12 sensors (adjustable tolerance<br />
window)<br />
- Wire break monitoring<br />
- Tolerance monitoring between<br />
2 sensors (SIL 3)<br />
- Diagnostics inside module<br />
- ProfiSafe frame<br />
possible<br />
- SIL 2: single-channel evaluation,<br />
24 channels<br />
- SIL 3: 2-of-2 evaluation on the<br />
module, 12 channels (adjust-<br />
Isolating module<br />
For F modules, 40 mm wide<br />
For isolation of F <strong>and</strong> st<strong>and</strong>ard<br />
modules in an ET 200M rack<br />
6ES7 195-7KF00-0XA0 B)<br />
able discrepancy time)<br />
- Short-circuit monitoring after<br />
L+<br />
- Discrepancy monitoring<br />
- Diagnostics inside module<br />
For signal isolation when using a<br />
copper bus connection (only F<br />
modules in a rack with IM 153-2)<br />
Isolating bus module<br />
6ES7 195-7HG00-0XA0<br />
- ProfiSafe frame<br />
80 mm wide, for isolating module,<br />
8 inputs, NAMUR [EEx ib]<br />
isolated by channel, redundant<br />
6ES7 326-1RF00-0AB0<br />
when using an active backplane<br />
bus<br />
design possible<br />
- 8 short-circuit resistant sensor<br />
power supplies, each for<br />
1 channel, mutually isolated<br />
- SIL 2: single-channel evaluation,<br />
8 channels<br />
- SIL 3: 2-of-2 evaluation on the<br />
module, 4 channels (adjustable<br />
discrepancy time)<br />
- Wire break <strong>and</strong> short-circuit<br />
monitoring (for contacts with<br />
external resistor circuit)<br />
- Discrepancy monitoring<br />
- Diagnostics inside module<br />
- ProfiSafe frame<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
11/17<br />
11
11<br />
Process I/O<br />
ET 200M distributed I/O<br />
F modules<br />
■ Options<br />
11/18<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Isolating module<br />
Following components can be used as accessories for the F<br />
modules:<br />
Isolating module<br />
- for isolation of F <strong>and</strong> st<strong>and</strong>ard modules in an ET 200M rack,<br />
- for signal isolation when using a copper bus connection<br />
(only F modules in a rack with IM 153-2)<br />
Isolating bus module for the isolating module, when using an<br />
active backplane bus<br />
Note<br />
The isolating module for F modules <strong>and</strong> the isolating bus module<br />
can only be used together. The 40 mm wide gap cannot be used<br />
for other modules.
■ Overview<br />
■ Integration<br />
The FM 355 controller module is the intelligent 4-channel controller<br />
module for universal control tasks. It can be used to control<br />
temperature, pressure <strong>and</strong> flow.<br />
The FM 355 module is available in four versions:<br />
FM 355 C is a continuous-action controller with 4 analog outputs<br />
for controlling analog actuators<br />
FM 355 S is a step or pulse controller with 8 digital outputs for<br />
controlling motor-driven (integrating) actuators or binary controlled<br />
actuators (e.g. electrical heating strips <strong>and</strong> cartridges)<br />
FM 355-2 C/S is specially optimized for temperature control<br />
applications with user-friendly integrated online self-optimization<br />
■ Function<br />
The FM 355 / FM 355-2 modules have four separate control<br />
channels. These controllers have the following features:<br />
Predefined controller structures for<br />
- fixed-setpoint control,<br />
- cascade control,<br />
- ratio control,<br />
- 3-component control<br />
Various operating modes:<br />
- automatic mode,<br />
- manual mode,<br />
-safety mode,<br />
- follow-up mode,<br />
- backup mode<br />
Sampling interval (dependent on the resolution of the analog<br />
inputs <strong>and</strong> the compensation input):<br />
- at 12 bit: 20 ms to 100 ms (only FM 355-2)<br />
- at 14 bit: 100 ms to 500 ms (dependent on the number of enabled<br />
analog inputs)<br />
2 control algorithms:<br />
- self-optimized temperature control algorithm,<br />
- PID algorithm<br />
Integrated online self-optimization without configuration (only<br />
FM 355-2)<br />
- for faster adoption of the operating point<br />
User-friendly controller optimization<br />
Backup mode: The controller can maintain its control function<br />
in the event of CPU failure or CPU stop. Programmable safety<br />
setpoint values or safety manipulated variables are set for this<br />
purpose.<br />
Feedforward control: The analog inputs can be optionally<br />
used for feedforward control as well as for actual value acquisition.<br />
Process I/O<br />
ET 200M distributed I/O<br />
Controller modules<br />
Use in SIMATIC PCS 7<br />
With the FM 355 / FM 355-2 modules in SIMATIC PCS 7 it is possible<br />
to implement controller tasks outside the S7-400 CPU of the<br />
automation system. The modules have not only controller structures<br />
but also analog <strong>and</strong> digital channels, thus eliminating the<br />
need for additional modules to detect the setpoint/actual value<br />
or to control the actuator.<br />
On the one h<strong>and</strong> this reduces the work load for the CPU, on the<br />
other h<strong>and</strong> it enables a backup behavior, i.e. the control system<br />
continues to work even if the CPU fails. In this case the FM 355<br />
module can be operated further with an OP17 operator panel<br />
(does not apply for FM 355-2).<br />
If the CPU of the automation system fails, the FM 355 module can<br />
be operated further with an OP17 operator panel. The operator<br />
panel is connected to the PROFIBUS DP field bus for this purpose.<br />
The CPU of the automation system can surrender input<br />
privilege to the operator panel in normal operation as well. The<br />
parameters that can be operated with the operator panel are setpoint<br />
value <strong>and</strong> manipulated variable. If the FM 355 module is<br />
operated from the operator panel, the automation system reads<br />
back the values operable from the operator panel after the input<br />
privilege is withdrawn or recovered again. Bumpless continuation<br />
of the operations is thus assured.<br />
IM 153-2 High Feature interface modules are needed for the<br />
PROFIBUS DP connection when the FM 355 / FM 355-2 controller<br />
modules are used in ET 200M.<br />
PCS 7 blocks<br />
CFC blocks with OS faceplates for all FM 355 modules are included<br />
in delivery of the st<strong>and</strong>ard SIMATIC PCS 7 library (part of<br />
<strong>Engineering</strong> Software). These blocks are integrated in the PCS 7<br />
driver concept, thus resulting in a homogeneous integration<br />
(incl. automatic diagnostics messages).<br />
Parameterization in HW Config<br />
A configuration package containing all parameterization masks<br />
required for configuring, parameterizing <strong>and</strong> commissioning are<br />
included in delivery of the FM 355 C <strong>and</strong> FM 355 S controller<br />
modules.<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/19<br />
11
11<br />
Process I/O<br />
ET 200M distributed I/O<br />
Controller modules<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
FM 355 C Controller Module 6ES7 355-0VH10-0AE0<br />
With 4 analog outputs for<br />
4 continuous-action controllers<br />
required front connector: 2 x 20pin<br />
Incl. multi-lingual configuration<br />
package, manual <strong>and</strong> Getting<br />
Started (German, English,<br />
French, Italian) on CD-ROM<br />
FM 355 S Controller Module 6ES7 355-1VH10-0AE0<br />
With 8 digital outputs for 4 step or<br />
pulse controllers<br />
required front connector: 2 x 20pin<br />
Incl. multi-lingual configuration<br />
package, manual <strong>and</strong> Getting<br />
Started (German, English,<br />
French, Italian) on CD-ROM<br />
11/20<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
FM 355-2 C Temperature Con- 6ES7 355-2CH00-0AE0<br />
troller Module<br />
With 4 analog outputs for<br />
4 continuous-action controllers<br />
required front connector: 2 x 20pin<br />
Incl. multi-lingual configuration<br />
package, manual <strong>and</strong> Getting<br />
Started (German, English,<br />
French, Italian) on CD-ROM<br />
FM 355-2 S Temperature Con- 6ES7 355-2SH00-0AE0<br />
troller Module<br />
With 8 digital outputs for 4 step or<br />
pulse controllers<br />
required front connector: 2 x 20pin<br />
Incl. multi-lingual configuration<br />
package, manual <strong>and</strong> Getting<br />
Started (German, English,<br />
French, Italian) on CD-ROM<br />
Following operator panels can be<br />
used specially for local operation<br />
of the FM 355 C/S:<br />
SIMATIC OP17/DP operator<br />
panel<br />
6AV3 617-1JC20-0AX1<br />
Note:<br />
In the case of the FM 355 C <strong>and</strong> FM 355 S controller module, the<br />
channels are not electrically isolated from one another<br />
Counter module<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
The FM 350-1 counter module is a single-channel intelligent FM 350-1 Counter Module 6ES7 350-1AH03-0AE0<br />
counter module for simple counting tasks, designed for the di- Counting functions up to 500 kHz<br />
rect connection of incremental encoders. It provides a compari- 1 channel for the connection of<br />
son function with 2 preselectable reference values, as well as integrated<br />
digital outputs for outputing a reaction upon reaching<br />
5 V <strong>and</strong> 24 V incremental encoders<br />
the reference value.<br />
required front connector:<br />
The FM 350-2 counter module is an eight-channel intelligent<br />
counter module for universal counting <strong>and</strong> measuring tasks, as<br />
well as for simple positioning jobs (max. 4 axes).<br />
1x20-pin<br />
incl. configuration package on<br />
CD-ROM<br />
FM 350-2 Counter Module<br />
8 channels with max. 20 kHz<br />
counting frequency, whereby up<br />
to 4 channels are available when<br />
used with SIMATIC PCS 7; for<br />
24 V transducers, for the following<br />
tasks:<br />
counting, frequency measurement,<br />
speed measurement,<br />
period measurement, dosing<br />
required front connector:<br />
1x40-pin<br />
incl. configuration package on<br />
CD-ROM<br />
6ES7 350-2AH00-0AE0
■ Overview<br />
The intrinsically safe distributed ET 200iS I/O device in degree of<br />
protection IP30 can be installed directly in Ex zone 1 or 2<br />
(EEx de ib [ia/ib] IIC T4) as well as in non-hazardous areas. The<br />
sensors/actuators can also be placed in zone 0 if required. The<br />
ET 200iS is connected through PROFIBUS DP. With the help of<br />
an isolating transformer (RS485-iS coupler) it is possible for<br />
PROFIBUS DP to be taken into Ex zone 1 as an intrinsically safe<br />
bus.<br />
Process I/O<br />
ET 200iS distributed I/O<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
The ET 200iS is of bit-modular design: pressure-encapsulated<br />
power supply, interface module for PROFIBUS DP, <strong>and</strong> up to<br />
32 electronic modules. HART capability is st<strong>and</strong>ard, as is the hot<br />
swapping of individual modules without a fire certificate. Data<br />
transfer rates of up to 1.5 Mbit/s are possible.<br />
Integration in SIMATIC PCS 7 covers CFC driver blocks, system<br />
diagnostics <strong>and</strong> time stamp. Putting the ET 200iS into operation<br />
is easy <strong>and</strong> user-friendly. The configuration of electronic modules<br />
<strong>and</strong> the parameterization of field devices are performed<br />
with SIMATIC PDM in the engineering system.<br />
The range of electronic modules covers a NAMUR digital input<br />
module, a digital output module <strong>and</strong> analog input/output modules<br />
with <strong>and</strong> without HART.<br />
SIMATIC PDM is needed to paramterize the electronic modules<br />
<strong>and</strong> the connected HART field devices.<br />
Note :<br />
Apart from these selected modules it is also possible to use -<br />
with limitations in functions - all other ET 200iS electronic modules<br />
from the current range.<br />
■ Technical specifications<br />
Detailed technical data on the ET 200iS can be found<br />
in the IK PI catalog or<br />
in the Mall / CA 01 at "Distributed I/Os / ET 200iS“<br />
Stainless steel wall housing<br />
■ Design<br />
■ Selection <strong>and</strong> Ordering Data<br />
Stainless steel housing with<br />
IP66 for Ex zone 1 in protection<br />
class EEx e<br />
Empty housing<br />
excl. installation of modules<br />
Order No.<br />
- Wall housing 600 x 400 x 230<br />
for accommodating as many<br />
as 11 ET 200iS modules<br />
6DL2 804-0AA00<br />
- Wall housing 800 x 400 x 230<br />
for accommodating as many<br />
as 16 ET 200iS modules<br />
6DL2 804-0AB00<br />
- Wall housing 1050 x 400 x 230<br />
for accommodating as many<br />
as 25 ET 200iS modules<br />
Empty housing<br />
incl. installation of an ET 200iS<br />
system<br />
6DL2 804-0AC00<br />
Stainless steel wall housing<br />
ET 200iS modules can also be installed in stainless steel wall<br />
housings designed to meet more exacting protection requirements.<br />
The housings are available in three different sizes. They<br />
comply with degree of protection IP66 <strong>and</strong> can also be used in<br />
Ex zone 1.<br />
1)<br />
- Wall housing 600 x 400 x 230 6DL2 804-1AA00<br />
incl. installation of one<br />
ET 200iS with as many as<br />
11 I/O modules<br />
- Wall housing 800 x 400 x 230 6DL2 804-1AB00<br />
incl. installation of one<br />
ET 200iS with as many as<br />
16 I/O modules<br />
- Wall housing 1050 x 400 x 230<br />
incl. installation of one<br />
ET 200iS with as many as<br />
25 I/O modules<br />
6DL2 804-1AC00<br />
1) The ET 200iS components have to be ordered separately<br />
11/21<br />
11
11<br />
Process I/O<br />
ET 200iS distributed I/O<br />
Electronic modules<br />
■ Overview<br />
The electronic modules are plugged into the corresponding<br />
terminal modules TM-E30S-44iS (screw-type terminal) or<br />
TM-E30C-44iS (cage-clamp method) (to be ordered separately).<br />
The modules are mechanically coded for automatic protection<br />
against polarity reversal when they are plugged in.<br />
Modules can be replaced under potentially explosive conditions<br />
during runtime.<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Digital electronic modules<br />
Digital input module for floating<br />
contacts<br />
4 x NAMUR or contact with resistor<br />
circuit<br />
- Short-circuit monitoring<br />
- Wire break monitoring<br />
- Chatter monitoring<br />
- Diagnostics inside module<br />
Digital Output Module for Ex-i<br />
Solenoid Valves, DC Relays <strong>and</strong><br />
Actuators<br />
2 x 25 V DC, 25 mA<br />
- Short-circuit monitoring<br />
- Wire break monitoring<br />
- Parameterizable connection of<br />
a default value in case of CPU<br />
failure<br />
- Diagnostics inside module<br />
Analog Electronic Modules<br />
Analog Input / Current Measurement<br />
2 x 4...20 mA, 2-wire transducer<br />
- Resolution 12 bit + sign<br />
- Short-circuit monitoring<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
2 x 0(4)...20 mA, 4-wire transducer<br />
- Resolution 12 bit + sign<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
2 x 4...20 mA, HART; 2-wire<br />
measurement transducer<br />
- Resolution 12 bit + sign<br />
- Short-circuit monitoring<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
2 x 4...20 mA, HART; 4-wire<br />
transducer<br />
- Resolution 12 bit + sign<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
11/22<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
6ES7 131-5RD00-0AB0 B)<br />
6ES7 132-5SB00-0AB0 B)<br />
6ES7 134-5RB00-0AB0 B)<br />
6ES7 134-5RB50-0AB0 B)<br />
6ES7 134-5TB00-0AB0 B)<br />
6ES7 134-5TB50-0AB0 B)<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Analog Input / Temperature<br />
Measurement<br />
2 x TC (thermocouples)<br />
- Type E, N, J, K, L, S, R, B, T, U<br />
- Resolution 15 bit + sign<br />
- Compensation through Pt100<br />
with module 6ES7 134-5SB50-<br />
0AB0 of the same station<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
2 x RTD, resistance thermometer<br />
Pt100/Ni100<br />
- 2-, 3-, 4-wire<br />
- Resolution 15 bit + sign<br />
- Short-circuit monitoring<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
Analog Output Module<br />
2 x 0(4)...20 mA, 2-wire transducer<br />
- Resolution: 14 bit<br />
- Short-circuit monitoring<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
- Parameterizable default value<br />
in case of CPU failure<br />
2 x 0(4)...20 mA, 2-wire transducer<br />
HART<br />
- Resolution: 14 bit<br />
- Short-circuit monitoring<br />
- Wire break monitoring<br />
- Diagnostics inside module<br />
- Parameterizable default value<br />
in case of CPU failure<br />
Terminal Module<br />
TM-E30S44-iS<br />
Terminal module for ET 200iS,<br />
for integrating electronic modules,<br />
screw-type terminals<br />
TM-E30C44-iS<br />
Terminal module for ET 200iS,<br />
for integrating electronic modules,<br />
spring-loaded terminals<br />
6ES7 134-5SB00-0AB0 B)<br />
6ES7 134-5SB50-0AB0 B)<br />
6ES7 135-5RB00-0AB0 B)<br />
6ES7 135-5TB00-0AB0 B)<br />
6ES7 193-5CB00-0AA0<br />
6ES7 193-5CB10-0AA0<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
Process I/O<br />
ET 200iS distributed I/O<br />
Power supply <strong>and</strong> interface modules<br />
■ Overview<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Thepower supply module is plugged into the corresponding ter- Starter Package for ET 200iS 6ES7 151-2AR00-0AB0 A)<br />
minal module TM-PS-iS (to be ordered separately). The power IM 151-2 interface module <strong>and</strong><br />
supply unit<br />
power supply module, each with<br />
provides a reliable isolated power supply for the ET 200iS with<br />
the necessary operating voltages for:<br />
- logic (through the backplane bus)<br />
- PROFIBUS DP interface of IM 151-2<br />
- power bus<br />
takes over the safety limit of the output voltage<br />
has an explosion-proof plastic enclosure (explosion protection<br />
type EX d)<br />
terminal module <strong>and</strong> RS485-iS<br />
coupler<br />
With SIMATIC PDM parameter<br />
assignment software, incl. integration<br />
in STEP 7<br />
Power Supply<br />
Power Supply Module<br />
For ET 200iS<br />
6ES7 138-5EA00-0AA0 B)<br />
The interface module IM151-2 is plugged into the corresponding<br />
TM-PS-iS Terminal Module 6ES7 193-5DA00-0AA0<br />
terminal module TM-IM-iS (to be ordered separately). The interface<br />
module IM 151-2 has the following properties:<br />
For integrating the power supply<br />
module<br />
connects the ET 200iS to PROFIBUS DP<br />
Bus Interface<br />
prepares data for the fitted electronic modules<br />
Interface Module IM 151-2 6ES7 151-2AA00-0AB0<br />
the PROFIBUS address of ET 200iS can be adjusted by switch For ET 200iS, incl. power bus terminating<br />
module<br />
A Starter Package for ET 200iS is avaliable as a complete package.<br />
It contains an IM 151-2 interface module <strong>and</strong> power supply<br />
module, each with a terminal module <strong>and</strong> RS485-iS coupler, with<br />
SIMATIC PDM parameter assignment software incl. integration<br />
TM-IM-iS Terminal Module<br />
For integrating the IM 151-2 interface<br />
module<br />
6ES7 193-5DB00-0AA0<br />
in STEP 7.<br />
Accessories<br />
The RS485-iS coupler is a field bus isolating transformer that en- Bus Connector<br />
6ES7 972-0BA30-0XA0<br />
ables PROFIBUS to be run intrinsically safely in hazardous ar- For intrinsically safe PROFIBUS,<br />
eas. The 6ES7972-0DA30-0XA0 plug with special (passive) ter- 1.5Mbit/s<br />
minating resistor is required to terminate the RS 485-iS.<br />
RS485-iS Coupler<br />
PROFIBUS must be run intrinsically<br />
safely in hazardous areas<br />
through installation of a field bus<br />
isolating transformer<br />
6ES7 972-0AC80-0XA0<br />
Bus Connector<br />
Connector with special (passive)<br />
terminating resistor for terminating<br />
the RS485-iS<br />
6ES7 972-0DA30-0XA0<br />
A) Subject to export regulations: AL: N, ECCN: 5D992B2<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/23<br />
11
11<br />
Process I/O<br />
ET 200S distributed I/O<br />
Introduction<br />
■ Overview<br />
The ET 200S is a bit-modular distributed I/O system rated for<br />
IP20 <strong>and</strong> approved for operation in Ex zone 2 (except the operation<br />
of motor starters). It is designed with permanent wiring that<br />
supports the hot swapping of I/O modules (with hot work permits).<br />
The range of I/Os that can be used with SIMATIC PCS 7 includes<br />
power modules for electronic modules <strong>and</strong> motor starters, analog<br />
<strong>and</strong> digital signal modules, <strong>and</strong> motor starters up to 7.5 kW.<br />
The implementation of safety engineering applications is supported<br />
by:<br />
failsafe terminal, power <strong>and</strong> electronic modules<br />
SIGUARD safety engineering for motor starter applications in<br />
plants of safety category 2 to 4 (EN 954-1)<br />
Note :<br />
Apart from these selected modules it is also possible to use -<br />
with limitations in functions - all other ET 200S electronic modules<br />
from the current range.<br />
11/24<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Design<br />
Main components of the distributed ET 200S I/O system:<br />
Terminal modules<br />
enable the electrical <strong>and</strong> mechanical connection of the<br />
I/O modules <strong>and</strong> carry the terminals for the process wiring:<br />
- TM-P Terminal Modules for Power Modules<br />
- TM-E Terminal Modules for Electronic Modules<br />
- TM-DS/TM-RS Terminal Modules for Motor Starters <strong>and</strong><br />
TM-xB Expansion Modules<br />
IM 151 interface module<br />
for connecting PROFIBUS DP to the ET 200S station. The terminal<br />
module is included in the scope of supply.<br />
Power modules for PM-E electronic modules <strong>and</strong> PM-D motor<br />
starters<br />
- for individual grouping of load <strong>and</strong> sensor supply voltages<br />
<strong>and</strong> their monitoring as well as<br />
for the safe shutting down of digital output modules with<br />
PROFIsafe<br />
- for supplying <strong>and</strong> monitoring the auxiliary voltages for motor<br />
starters as well as for the shutting down of a complete group<br />
of motor starters<br />
Electronic modules<br />
for process data exchange:<br />
- digital electronic modules for connecting digital sensors <strong>and</strong><br />
actuators<br />
- analog electronic modules for connecting analog sensors<br />
<strong>and</strong> actuators<br />
Motor starter modules<br />
for switching <strong>and</strong> protecting three-phase current loads<br />
Accessories<br />
- Reserve module for reserving a slot for an electronic module<br />
- Label sheets for printing ID labels on a laser printer<br />
- Shield connection: shield connecting element, shield terminal,<br />
ground terminal, copper voltage bus 3 x 10 mm;<br />
components for the low-impedance connection of cable<br />
shielding at low cost of installation
Mounting<br />
The terminal modules that can be mounted on a profile rail<br />
(35 x 15 x 7.5 or 15 mm) form the carrier system for the<br />
I/O modules. They are used for the process wiring <strong>and</strong> enable<br />
the electrical <strong>and</strong> mechanical connection of the I/O modules.<br />
The terminal modules can be prewired <strong>and</strong> tested without the<br />
I/O modules. Later the I/O modules are simply plugged in place.<br />
Terminal modules are available with screw connections, springloaded<br />
terminals or Fast Connect design for fast mounting.<br />
The automatic coding of the I/O modules reliably prevents the<br />
risk of injury to persons <strong>and</strong>/or destruction of modules through<br />
accidental mounting of the wrong module.<br />
Expansion limits<br />
Depending on the IM 151 interface module used, the expansion<br />
of an ET 200S station is subject to the following limits:<br />
A maximum total of 63 I/O modules per station can be inserted<br />
between interface module <strong>and</strong> terminating module.<br />
The maximum permissible width of an ET 200S station is 2 m.<br />
The maximum address volume of all the inserted I/O modules<br />
is 244 byte for input data <strong>and</strong> 244 byte for output data.<br />
The maximum number of parameters is restricted to 244 byte<br />
per station.<br />
ET 200S configuration<br />
The ET 200S Configurator software tool is available for st<strong>and</strong>ard<br />
configuration. The data entered can be transferred directly to<br />
STEP7, <strong>and</strong> the electronic ordering of components is also possible<br />
through the Mall.<br />
■ Technical specifications<br />
Process I/O<br />
ET 200S distributed I/O<br />
Detailed technical data on the ET 200S can be found<br />
in the IK PI catalog or<br />
in the Mall / CA 01 at "Distributed I/Os / ET 200S“<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
11/25<br />
11
11<br />
Process I/O<br />
ET 200S distributed I/O<br />
Terminal modules<br />
■ Overview<br />
Mechanical modules for integrating the power <strong>and</strong> electronic<br />
modules as well as the motor starters <strong>and</strong> expansion modules<br />
(ordering data of the terminal modules for motor starters <strong>and</strong><br />
expansion module can be found at "Motor starters")<br />
For setting up permanent wiring through self-configuring voltage<br />
buses<br />
Alternatively with screw-type or spring-loaded terminals <strong>and</strong><br />
Fast Connect design<br />
Replaceable terminal box<br />
Automatic coding of the electronic modules<br />
Self-shielding of the backplane bus for high data security<br />
Optional plug-in shield connection<br />
Color coding facility for the terminals <strong>and</strong> for identifying the<br />
slot numbers<br />
11/26<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Terminal Modules TM-P for<br />
Power Modules<br />
TM-P15S23-A1 Terminal Module<br />
2 x 3 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, screw-type terminals<br />
Ordering unit 1 piece<br />
TM-P15C23-A1 Terminal Module<br />
2 x 3 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, spring-type terminals<br />
Ordering unit 1 piece<br />
TM-P15N23-A1 Terminal Module<br />
2 x 3 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, FastConnect<br />
Ordering unit 1 piece<br />
TM-P15S23-A0 Terminal Module<br />
2 x 3 terminals, terminal access to<br />
AUX1 bus, AUX1 interrupted to<br />
the left, screw-type terminals<br />
Ordering unit 1 piece<br />
TM-P15C23-A0 Terminal Module<br />
2 x 3 terminals, terminal access to<br />
AUX1 bus, AUX1 interrupted to<br />
the left, spring-type terminals<br />
Ordering unit 1 piece<br />
TM-P15N23-A0 Terminal Module<br />
2 x 3 terminals, terminal access to<br />
AUX1 bus, AUX1 interrupted to<br />
the left, FastConnect<br />
Ordering unit 1 piece<br />
TM-P15S22-01 Terminal Module<br />
2 x 2 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, screw-type<br />
terminals<br />
Ordering unit 1 piece<br />
TM-P15C22-01 Terminal Module<br />
2 x 2 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, springloaded<br />
terminals<br />
Ordering unit 1 piece<br />
TM-P15N22-01 Terminal Module<br />
2 x 2 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, FastConnect<br />
Ordering unit 1 piece<br />
TM-P30S44-A0 Terminal Module<br />
7 x 2 terminals, terminal access to<br />
AUX1 bus, AUX1 interrupted to<br />
the left, screw-type terminals for<br />
PM-E F PROFIsafe<br />
Ordering unit 1 piece<br />
TM-P30C44-A0 Terminal Module<br />
7 x 2 terminals, terminal access to<br />
AUX1 bus, AUX1 interrupted to<br />
the left, spring-loaded terminals<br />
for PM-E F PROFIsafe<br />
Ordering unit 1 piece<br />
6ES7 193-4CC20-0AA0<br />
6ES7 193-4CC30-0AA0<br />
6ES7 193-4CC70-0AA0<br />
6ES7 193-4CD20-0AA0<br />
6ES7 193-4CD30-0AA0<br />
6ES7 193-4CD70-0AA0<br />
6ES7 193-4CE00-0AA0<br />
6ES7 193-4CE10-0AA0<br />
6ES7 193-4CE60-0AA0<br />
6ES7 193-4CK20-0AA0<br />
6ES7 193-4CK30-0AA0
■ Selection <strong>and</strong> Ordering Data Order No.<br />
TM-E Terminal Modules for<br />
Electronic Modules<br />
TM-E15S24-A1 Terminal Module 6ES7 193-4CA20-0AA0<br />
2 x 4 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, screw-type terminals<br />
Ordering unit 5 pcs<br />
TM-E15C24-A1 Terminal Module 6ES7 193-4CA30-0AA0<br />
2 x 4 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, spring-type terminals<br />
Ordering unit 5 pcs<br />
TM-E15N24-A1 Terminal Module 6ES7 193-4CA70-0AA0<br />
2 x 4 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, FastConnect<br />
Ordering unit 5 pcs<br />
TM-E15S24-01 Terminal Module 6ES7 193-4CB20-0AA0<br />
2 x 4 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, screw-type<br />
terminals<br />
Ordering unit 5 pcs<br />
TM-E15C24-01 Terminal Module 6ES7 193-4CB30-0AA0<br />
2 x 4 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, spring-type<br />
terminals<br />
Ordering unit 5 pcs<br />
TM-E15N24-01 Terminal Module 6ES7 193-4CB70-0AA0<br />
2 x 4 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, FastConnect<br />
Ordering unit 5 pcs<br />
TM-E15S23-01 Terminal Module 6ES7 193-4CB00-0AA0<br />
2 x 3 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, screw-type<br />
terminals<br />
Ordering unit 5 pcs<br />
TM-E15C23-01 Terminal Module 6ES7 193-4CB10-0AA0<br />
2 x 3 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, spring-type<br />
terminals<br />
Ordering unit 5 pcs<br />
TM-E15N23-01 Terminal Module 6ES7 193-4CB60-0AA0<br />
2 x 3 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, FastConnect<br />
Ordering unit 5 pcs<br />
TM-E15N26-A1 Terminal Module 6ES7 193-4CA80-0AA0<br />
2 x 6 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, FastConnect<br />
Ordering unit 5 pcs<br />
TM-E15S26-A1 Terminal Module 6ES7 193-4CA40-0AA0<br />
2 x 6 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, screw-type terminals<br />
Ordering unit 5 pcs<br />
Process I/O<br />
ET 200S distributed I/O<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Terminal modules<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
TM-E15C26-A1 Terminal Module 6ES7 193-4CA50-0AA0<br />
2 x 6 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, spring-type terminals<br />
Ordering unit 5 pcs<br />
TM-E30S44-01 Terminal Module 6ES7 193-4CG20-0AA0<br />
4 x 4 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, screw-type<br />
terminals<br />
Ordering unit 1 piece<br />
TM-E30C44-01 Terminal Module 6ES7 193-4CG30-0AA0<br />
4 x 4 terminals, no terminal<br />
access to AUX1 bus, AUX1 interconnected<br />
to the left, spring-type<br />
terminals<br />
Ordering unit 1 piece<br />
TM-E30S46-A1 Terminal Module 6ES7 193-4CF40-0AA0<br />
4 x 6 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, screw-type terminals<br />
Ordering unit 1 piece<br />
TM-E30C46-A1 Terminal Module 6ES7 193-4CF50-0AA0<br />
4 x 6 terminals, terminal access to<br />
AUX1 bus, AUX1 interconnected<br />
to the left, spring-type terminals<br />
Ordering unit 1 piece<br />
TM-E15S24-AT Terminal Module 6ES7 193-4CL20-0AA0<br />
For internal temperature compensation<br />
with 2AI TC High Feature,<br />
screw-type terminals<br />
Ordering unit 1 piece<br />
TM-E15C24-AT Terminal Module 6ES7 193-4CL30-0AA0<br />
For internal temperature compensation<br />
with 2AI TC High Feature,<br />
spring-loaded terminals<br />
Ordering unit 1 piece<br />
Accessories for the terminal modules, see the IK PI catalog or A&D Mall /<br />
CA 01 at "Distributed I/Os / ET 200S“<br />
11/27<br />
11
11<br />
Process I/O<br />
ET 200S distributed I/O<br />
Interface modules<br />
■ Overview<br />
IM 151-1 High Feature (RS 485)<br />
Interface module for electrical connection of the ET 200S to<br />
PROFIBUS DP through copper bus cables<br />
H<strong>and</strong>les all data exchange with the PROFIBUS DP master<br />
Power modules<br />
■ Overview<br />
Power Modules for PM-E Electronic Modules<br />
For monitoring <strong>and</strong>, depending on the version, securing the<br />
load <strong>and</strong> encoder supply voltage to the electronic module<br />
Diagnostic message of voltage <strong>and</strong> fuse drop (can be<br />
switched off through configuration)<br />
PM-E F PROFIsafe Failsafe Power Module<br />
For safely switching off downstream digital st<strong>and</strong>ard output<br />
modules, 24 V DC up to 10 A (AK 4, SIL 2)<br />
Also 2 digital outputs, 24 V DC / 2 A (AK 6, SIL 3)<br />
Power modules for PM-D motor starters<br />
For incoming supply <strong>and</strong> monitoring of auxiliary voltages for<br />
motor starters<br />
Possible to switch off a complete group of motor starters without<br />
additional effort (safety category 1 according to EN 954-1)<br />
PM-D F PROFIsafe failsafe power module for failsafe motor<br />
starters<br />
In EMERGENCY STOP applications the failsafe motor starters<br />
are shut down selectively by means of the upstream PM-D F<br />
PROFIsafe power module. A total of 6 shut-down groups can<br />
be formed per power module. The interface from ET 200S<br />
PROFIsafe to systems with conventional safety engineering is<br />
formed by F-CM failsafe contact multipliers with 4 floating contacts.<br />
11/28<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
IM151-1 Interface Module<br />
For ET 200S, High Feature<br />
6ES7 151-1BA00-0AB0 B)<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
■ Selection <strong>and</strong> Ordering Data<br />
Power Modules for PM-E Electronic<br />
Modules<br />
PM-E Power Module<br />
Order No.<br />
24 V DC/10 A<br />
- Monitoring of the load voltage<br />
6ES7 138-4CA00-0AA0 B)<br />
24 V DC, 48 V; 24 V, 48 V, 120 V<br />
AC; 230 V AC<br />
- Monitoring of the fuse<br />
- Monitoring of the load voltage<br />
6ES7 138-4CB10-0AB0 B)<br />
PM-E F Failsafe Power Module<br />
PM-E F PROFIsafe<br />
- 1 x relay 24 V DC/10 A, P/M<br />
switching, for switching off<br />
downstream st<strong>and</strong>ard digital<br />
output modules (up to AK 4,<br />
SIL 2)<br />
- 2 x 24 V DC/2 A, P/M switching,<br />
with broken wire monitoring<br />
by channel (with "1" signal)<br />
- Safe monitoring of communication<br />
with PROFIsafe<br />
- Diagnostics inside module<br />
- Overload diagnostics by channel<br />
Power Module for PM-D Motor<br />
Starters<br />
PM-D Power Module<br />
2 x 24 V DC/10 A<br />
- For supplying the electronics<br />
<strong>and</strong> contactors of motor starters<br />
- Monitoring of the load voltage<br />
Power Modules for PM-D F Failsafe<br />
Motor Starters<br />
PM-D F PROFIsafe Power Module<br />
For 6 vector groups; safety-oriented<br />
F-CM Failsafe Contact Multiplier<br />
Expansion to PM-D F PROFIsafe;<br />
PM-D F X1 Failsafe Power Module<br />
Overvoltage protection; for<br />
incoming supply of external emergency<br />
stop signals; for 6 vector<br />
groups<br />
6ES7 138-4CF01-0AB0<br />
3RK1 903-0BA00 F)<br />
3RK1 903-3BA00<br />
3RK1 903-3CA00<br />
3RK1 903-3DA00<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
F) Subject to export regulations: AL: N, ECCN: EAR99
■ Overview<br />
2- <strong>and</strong> 4-channel digital inputs <strong>and</strong> outputs for the ET 200S<br />
Can be connected to TM-E terminal modules with automatic<br />
coding<br />
High-feature variants for enhanced plant availability, additional<br />
functions <strong>and</strong> comprehensive diagnostics<br />
Module replacement during operation <strong>and</strong> under power (hot<br />
swapping)<br />
Failsafe digital input module 4/8 F-DI PROFIsafe<br />
Failsafe digital output module 4 F-DO PROFIsafe 24 V DC/2 A<br />
Isolated from the backplane bus<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Digital Inputs for Floating Contacts<br />
DI 2 x 24 V DC, st<strong>and</strong>ard 6ES7 131-4BB00-0AA0 B)<br />
DI 4 x 24 V DC, st<strong>and</strong>ard 6ES7 131-4BD00-0AA0<br />
DI 2 x 24 V DC, High Feature;<br />
with diagnostics<br />
- Short-circuit monitoring<br />
6ES7 131-4BB00-0AB0<br />
DI 4 x 24 V DC, High Feature;<br />
with diagnostics<br />
- Short-circuit monitoring<br />
6ES7 131-4BD00-0AB0<br />
DI 4 x 24...48 V AC/DC, High<br />
Feature; with diagnostics<br />
- Wire break monitoring (external<br />
resistor circuit required)<br />
- Monitoring of the fuse<br />
- Monitoring of the load voltage<br />
6ES7 131-4CD00-0AB0 B)<br />
DI 2 x 120 V AC, st<strong>and</strong>ard 6ES7 131-4EB00-0AB0 B)<br />
DI 2 x 230 V AC, st<strong>and</strong>ard<br />
Failsafe Digital Input<br />
6ES7 131-4FB00-0AB0 B)<br />
4/8 F-DI 24 V DC PROFIsafe<br />
8 DI safety-oriented SIL-2 or 4 DI<br />
safety-oriented SIL-3, with diagnostics<br />
- Cyclic short-circuit test<br />
- Discrepancy monitoring of 2<br />
channels for SIL 3 (adjustable<br />
discrepancy time)<br />
- Safe monitoring of communication<br />
with PROFIsafe<br />
Digital Outputs for direct voltage<br />
(suitable for solenoid<br />
valves, DC contactors, indicator<br />
lights etc.)<br />
6ES7 138-4FA01-0AB0<br />
DO 2 x 24 V DC/0.5 A, st<strong>and</strong>ard 6ES7 132-4BB00-0AA0<br />
DO 2 x 24 V DC/2 A, st<strong>and</strong>ard 6ES7 132-4BB30-0AA0<br />
DO 2 x 24 V DC/0.5 A, High Feature,<br />
with diagnostics<br />
- Connection of a default value<br />
by channel in the event of CPU<br />
failure (parameterizable)<br />
- Short-circuit monitoring by<br />
channel<br />
- Broken wire monitoring by<br />
channel (when "1" signal)<br />
6ES7 132-4BB00-0AB0<br />
DO 2 x 24 V DC/2 A, High Feature,<br />
with diagnostics<br />
- Connection of a default value<br />
by channel in the event of CPU<br />
failure (parameterizable)<br />
- Short-circuit monitoring by<br />
channel<br />
- Broken wire monitoring by<br />
channel (when "1" signal)<br />
6ES7 132-4BB30-0AB0 B)<br />
DO 4 x 24 V DC/0.5 A, st<strong>and</strong>ard 6ES7 132-4BD00-0AA0 B)<br />
DO 4 x 24 V DC/2 A, st<strong>and</strong>ard 6ES7 132-4BD30-0AA0<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Digital output for AC voltage<br />
(suitable for solenoid valves,<br />
AC contactors, indicator lights<br />
etc.)<br />
DO 2 x 24...230 V AC, 2 A<br />
- Connection of a default value<br />
by channel in the event of CPU<br />
failure (parameterizable)<br />
Relay output (suitable for<br />
AC/DC solenoid valves, contactors,<br />
motor starters, miniature<br />
motors <strong>and</strong> indicator lights)<br />
2 x relays 24...230 V AC/DC, 5 A<br />
- Connection of a default value<br />
by channel in the event of CPU<br />
failure (parameterizable)<br />
Failsafe Digital Output<br />
4 F-DO 24 V DC/2 A PROFISafe<br />
safety-oriented up to SIL-3, with<br />
diagnostics, PM switching<br />
- Short-circuit monitoring by<br />
channel<br />
- Overload monitoring by channel<br />
- Broken wire monitoring by<br />
channel (when "1" signal)<br />
- Safe monitoring of communication<br />
with PROFIsafe<br />
- Diagnostics inside module<br />
Process I/O<br />
ET 200S distributed I/O<br />
Digital electronic modules<br />
6ES7 132-4FB00-0AB0 B)<br />
6ES7 132-4HB00-0AB0<br />
6ES7 138-4FB01-0AB0<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/29<br />
11
11<br />
Process I/O<br />
ET 200S distributed I/O<br />
Analog electronic modules<br />
■ Overview<br />
Analog inputs <strong>and</strong> outputs for the ET 200S<br />
Can be connected to TM-E terminal modules with automatic<br />
coding<br />
High-feature variants with enhanced accuracy <strong>and</strong> resolution<br />
Hot swapping of modules<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Analog Input<br />
AI 2xU (±5 V, 1...5V, ±10 V) /<br />
13 bit, st<strong>and</strong>ard<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
AI 2xI, 2-wire MU (4...20 mA) /<br />
13 bit, st<strong>and</strong>ard<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
- Wire break monitoring<br />
AI 2xI, 4-wire MU (±20 mA,<br />
4...20 mA) / 13 bit, st<strong>and</strong>ard<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
- Wire break monitoring<br />
AI 2xTC / 15 bit, st<strong>and</strong>ard<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
- Wire break monitoring<br />
- Compensation through external<br />
Pt100 in the same station<br />
with AI 2xRTD St<strong>and</strong>ard<br />
AI 2xRTD / 15 bit, st<strong>and</strong>ard<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
- Wire break monitoring<br />
- Pt100 resistance thermometer,<br />
Ni100 (2, 3 or 4 wires)<br />
AI 2xU (1...5 V, ±5 V, ±10 V) /<br />
15 bit, high resolution<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
AI 2xI (±20 mA, 4...20 mA) /<br />
15 bit, high resolution<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
- Wire break monitoring<br />
AI 2xTC / 15 bit, High Feature<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
- Wire break monitoring<br />
- Internal temperature compensation<br />
with TM-E15S24-AT or<br />
TM-E15C24-AT terminal module<br />
AI 2xRTD / 15 bit, High Feature<br />
- Diagnostics inside module<br />
- Overflow/underflow diagnostics<br />
- Wire break monitoring<br />
- Resistance thermometer<br />
Pt100/200/500/1,000,<br />
Ni100/1,000 (2, 3 or 4 wires)<br />
- Temperature in Celsius or<br />
Fahrenheit<br />
11/30<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
6ES7 134-4FB00-0AB0 B)<br />
6ES7 134-4GB00-0AB0 B)<br />
6ES7 134-4GB10-0AB0 B)<br />
6ES7 134-4JB00-0AB0 B)<br />
6ES7 134-4JB50-0AB0 B)<br />
6ES7 134-4LB00-0AB0 B)<br />
6ES7 134-4MB00-0AB0 B)<br />
6ES7 134-4NB00-0AB0 B)<br />
6ES7 134-4NB50-0AB0 B)<br />
■ Selection <strong>and</strong> Ordering Data<br />
Analog Output<br />
Order No.<br />
AO 2xU (1...5 V / 12 bit, ±10 V /<br />
13 bit), st<strong>and</strong>ard<br />
- Diagnostics inside module<br />
- Parameterizable connection of<br />
a default value in case of CPU<br />
stop<br />
- Short-circuit monitoring<br />
6ES7 135-4FB00-0AB0 B)<br />
AO 2xI (±20 mA, 4...20 mA) /<br />
13 bit, st<strong>and</strong>ard<br />
- Diagnostics inside module<br />
- Parameterizable connection of<br />
a default value in case of CPU<br />
stop<br />
- Wire break monitoring<br />
6ES7 135-4GB00-0AB0<br />
6ES7 135-4LB00-0AB0<br />
B)<br />
AO 2xU (1...5 V, ±10 V) / 15 bit,<br />
high resolution<br />
- Diagnostics inside module<br />
- Parameterizable connection of<br />
a default value in case of CPU<br />
stop<br />
- Short-circuit monitoring<br />
AO 2xI (±20 mA, 4...20 mA) /<br />
15 bit, high resolution<br />
- Diagnostics inside module<br />
- Parameterizable connection of<br />
a default value in case of CPU<br />
stop<br />
- Wire break monitoring<br />
6ES7 135-4MB00-0AB0<br />
B) Subject to export regulations: AL: N, ECCN: EAR99H
■ Overview<br />
Completely prewired motor starter for the switching <strong>and</strong> safeguarding<br />
of any three-phase current loads<br />
Optionally available as direct, reversing or soft starter<br />
High Feature motor starter with combination of motor circuit<br />
protector, electronic overload protection <strong>and</strong> contactor or soft<br />
starter up to 7.5 kW<br />
Failsafe motor starters based on the High Feature micro starters<br />
with integrated redundancy also offer shut-down reliability<br />
up to Category 4 (EN 954-1)<br />
With build-as-you-go 40/50 A power bus, i.e. once-only incoming<br />
supply of load voltage for a group of motor starters<br />
Hot swapping permissible<br />
Inputs <strong>and</strong> outputs for controlling <strong>and</strong> signalizing states already<br />
integrated<br />
Diagnostics-capable for active monitoring of the protection<br />
<strong>and</strong> switching function<br />
Combinable with expansion modules: Brake control module<br />
for operating electromechanical brakes in three-phase AC<br />
motors, <strong>and</strong> with two optional inputs for special functions<br />
■ Selection <strong>and</strong> Ordering Data<br />
High Feature Motor Starter<br />
With diagnostics, unfused;<br />
exp<strong>and</strong>able with brake control<br />
module<br />
DS1e-x Direct Starter<br />
Direct starter; mechanical switching;<br />
electronic UE protection<br />
Order No.<br />
up to 1.1 kW/400 V; 0.3..0.3.0 A 3RK1 301-0AB10-0AA3<br />
up to 3.0 kW/400 V; 2.4..00.8.0 A 3RK1 301-0BB10-0AA3<br />
up to 7.5 kW/400 V;<br />
2.4..00.16.0 A<br />
DSS1e-x Soft Starter<br />
Direct soft starter; electronic<br />
switching; electronic UE protection<br />
3RK1 301-0CB10-0AA3<br />
up to 1.1 kW/400 V; 0.3..0.3.0 A 3RK1 301-0AB20-0AA3<br />
up to 3.0 kW/400 V; 2.4..00.8.0 A 3RK1 301-0BB20-0AA3<br />
up to 7.5 kW/400 V;<br />
2.4..00.16.0 A<br />
RS1e-x Reversing Starter<br />
Reversing starter; mechanical<br />
switching; electronic UE protection<br />
3RK1 301-0CB20-0AA3 F)<br />
up to 1.1 kW/400 V; 0.3..0.3.0 A 3RK1 301-0AB10-1AA3<br />
up to 3.0 kW/400 V; 2.4..00.8.0 A 3RK1 301-0BB10-1AA3<br />
up to 7.5 kW/400 V;<br />
2.4..00.16.0 A<br />
3RK1 301-0CB10-1AA3<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Accessories for Motor Starter<br />
High Feature<br />
Terminal module<br />
TM-DS65-S32<br />
for DS1e-x, DSS1e-x direct starters<br />
with supply connection for<br />
power bus incl. 3 caps for terminating<br />
the power bus<br />
TM-DS65-S31<br />
for DS1e-x, DSS1e-x direct starters<br />
without supply connection<br />
for power bus<br />
TM-RS130-S32<br />
for RS1e-x reversing starter with<br />
supply connection for power<br />
bus incl. 3 caps for connecting<br />
the power bus<br />
TM-RS130-S31<br />
for RS1e-x reversing starter without<br />
supply connection for power<br />
bus<br />
Jumper Modules<br />
M15-PEN<br />
15 mm wide, for jumpering a<br />
15-mm module<br />
M30-PEN<br />
30 mm wide, for jumpering a<br />
30-mm module<br />
M15-L123<br />
15 mm wide, for jumpering a<br />
15-mm module<br />
M30-L123<br />
30 mm wide, for jumpering a<br />
30-mm module<br />
2DI 24 V DC control module<br />
Digital input module with two<br />
inputs for local motor starter functions<br />
for mounting on the front of<br />
the motor starter<br />
M65-PEN-F Feeder Block<br />
65 mm wide, incl. two caps,<br />
in combination with TM-DS65-<br />
32/TM-RS130-S32<br />
M65-PEN-S Connection Module<br />
65 mm wide, in combination with<br />
TM-DS65-31/TM-RS130-S31<br />
Brake Control Expansion Module<br />
For motors with mechanical brake<br />
xB1<br />
24 V DC / 4 A<br />
xB2<br />
500V DC / 0.7A<br />
xB3<br />
24 V DC / 4 A, DI 2 x 24 V DC local<br />
control<br />
xB4<br />
500 V DC/ 0.7 A, DI 2 x 24 V DC<br />
local control<br />
Terminal Modules for Brake<br />
Control Expansion Module<br />
TM-xB15 S24-01<br />
for xB1 or xB2<br />
TM-xB215 S24-01<br />
for xB1 ... 4<br />
Process I/O<br />
ET 200S distributed I/O<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Motor starters<br />
3RK1 903-0AK00 F)<br />
3RK1 903-0AK10 F)<br />
3RK1 903-0AL00 F)<br />
3RK1 903-0AL10 F)<br />
3RK1 903-0AH00<br />
3RK1 903-0AJ00<br />
3RK1 903-0AE00<br />
3RK1 903-0AF00<br />
3RK1 903-0CH10<br />
3RK1 903-2AC00<br />
3RK1 903-2AC10<br />
3RK1 903-0CB00 F)<br />
3RK1 903-0CC00 F)<br />
3RK1 903-0CE00 F)<br />
3RK1 903-0CF00 F)<br />
3RK1 903-0AG00<br />
3RK1 903-0AG01 F)<br />
11/31<br />
11
11<br />
Process I/O<br />
ET 200S distributed I/O<br />
Motor starters<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Motor Starter Failsafe<br />
Unfused; exp<strong>and</strong>able with brake<br />
control module; High Feature;<br />
for PM-D F PROFIsafe power<br />
module<br />
F-DS1e-x Failsafe Direct Starter<br />
up to 1.1 kW/400 V; 0.3..0.3.0 A 3RK1 301-0AB13-0AA2<br />
up to 3.0 kW/400 V; 2.4..00.8.0 A 3RK1 301-0BB13-0AA2<br />
up to 7.5 kW/400 V;<br />
3RK1 301-0CB13-0AA2<br />
2.4..00.16.0 A<br />
F-RS1e-x Failsafe Reversing<br />
Starter<br />
up to 1.1 kW/400 V; 0.3..0.3.0 A 3RK1 301-0AB13-1AA2<br />
up to 3.0 kW/400 V; 2.4..00.8.0 A 3RK1 301-0BB13-1AA2<br />
up to 7.5 kW/400 V;<br />
3RK1 301-0CB13-1AA2<br />
2.4..00.16.0 A<br />
Brake Control Module<br />
For motors with mechanical brake<br />
xB3<br />
24 V DC / 4 A, DI 2 x 24 V DC local<br />
control<br />
xB4<br />
500 V DC/ 0.7 A, DI 2 x 24 V DC<br />
local control<br />
11/32<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
3RK1 903-0CE00 F)<br />
3RK1 903-0CF00 F)<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Accessories for Motorstarter<br />
Failsafe<br />
Terminal module<br />
PM-D F PROFIsafe 3RK1 903-3AA00 F)<br />
PM-D F X1, incoming supply<br />
on left<br />
PM-D F X1, incoming supply in<br />
center<br />
3RK1 903-3AE00 F)<br />
3RK1 903-3AE10 F)<br />
For contact multipliers 3RK1 903-3AB10<br />
For F-DS1e-x, with supply connection<br />
For F-DS1e-x, without supply<br />
connection<br />
For F-RS1e-x, with supply connection<br />
For F-RS1e-x, without supply<br />
connection<br />
M65-PEN-F Feeder Block<br />
65 mm wide, incl. two caps,<br />
in combination with TM-DS65-<br />
32/TM-RS130-S32<br />
M65-PEN-S Connection Module<br />
65 mm wide, in combination with<br />
TM-DS65-31/TM-RS130-S31<br />
3RK1 903-3AC00 F)<br />
3RK1 903-3AC10 F)<br />
3RK1 903-3AD00 F)<br />
3RK1 903-3AD10 F)<br />
3RK1 903-2AC00<br />
3RK1 903-2AC10<br />
F) Subject to export regulations: AL: N, ECCN: EAR99
■ Overview<br />
The SIGUARD safety system is based on special terminal <strong>and</strong><br />
power modules that can be combined with the ET 200S motor<br />
starters <strong>and</strong> a failsafe kit to achieve the highest safety category<br />
4 (according to EN 954-1). It enables the evaluation of emergency<br />
stop circuits, the monitoring of protective doors or the implementation<br />
of time-delayed shut-downs. The costs involved in<br />
the configuration <strong>and</strong> wiring of conventional safety systems are<br />
no longer incurred. All st<strong>and</strong>ard safety applications can be covered<br />
with SIGUARD (see the ET 200S manual for examples of<br />
applications).<br />
■ Design<br />
Terminal modules for SIGUARD power modules<br />
The terminal modules integrate the SIGUARD power modules.<br />
Using different terminal modules it is possible to separate various<br />
safety circuits by function or cascade them. Each group of<br />
this type has to be terminated with a SIGUARD PM-X connection<br />
module.<br />
The TM-PF30 S47-B1 terminal module always st<strong>and</strong>s at the<br />
beginning of a safety segment <strong>and</strong> integrates either the PM-<br />
DF1 power module for emergency stop applications or the<br />
PM-DF2 power module for protective door monitoring. The 2channel<br />
connection of the safety sensor (e.g. emergency stop<br />
sensor) as well as the 24-V supplies for the electronics (U1 )<br />
<strong>and</strong> the contactors (U2 ) of the motor starters have to be connected<br />
to this terminal module. Connections for the ON button<br />
(enable) <strong>and</strong> the safe output of the power module are also<br />
available.<br />
The TM-PF30 S47-B0 terminal module is used for the cascading<br />
of subordinate safety segments <strong>and</strong> integrates either the<br />
PM-D F1 power module for emergency stop applications or<br />
the PM-D F2 power module for protective door monitoring. No<br />
additional auxiliary voltage has to be connected to this terminal<br />
module. The supply is fed through the terminal module<br />
voltage buses from the preceding PM-D F1 or PM-D F2 power<br />
module. Switching off the voltage of the preceding power<br />
module means that the terminal module has no voltage either.<br />
The TM-PF30 S47-C1 terminal module always st<strong>and</strong>s at the<br />
beginning of an expansion of a safety segment in a new station,<br />
e.g. in an interlaced configuration. It integrates the PM-D<br />
F3 power module for time-delayed shut-down or the PM-D F4<br />
power module for direct shut-down in physically separated<br />
ET 200S stations. The 24 V supplies for the electronics (U1)<br />
<strong>and</strong> for the contactors (U2) are fed in anew. The shut-down<br />
comm<strong>and</strong> of a preceding ET 200S station is integrated<br />
through a safe input. Separate terminals are available for connecting<br />
the feedback circuit to the upstream ET 200S station.<br />
It is not possible to connect safety sensors to this terminal<br />
module.<br />
The TM-PF30 S47-C0 terminal module is used for the cascading<br />
of subordinate safety segments <strong>and</strong> integrates either the<br />
PM-D F3 power module for time-delayed shut-down or the PM-<br />
D F4 power module. Only the U2 supply voltage has to be connected<br />
to this terminal module. The U1 supply is fed through<br />
the terminal module voltage buses of the preceding power<br />
module (voltage group section). It is not possible to connect<br />
safety sensors to this terminal module.<br />
The TM-PF30 S47-D0 terminal module is used to integrated<br />
the PM-D F5 power module. At this terminal module it is possible<br />
to forward safe signals to external systems through four<br />
groups, each with two safety relay contacts in redundant configuration.<br />
The terminal module must always be positioned between<br />
one of the afore-mentioned terminal modules <strong>and</strong> a terminal<br />
module for the TM-X connection module. It is not<br />
possible to connect safety sensors to this terminal module<br />
Process I/O<br />
ET 200S distributed I/O<br />
SIGUARD safety engineering<br />
TM-X terminal module for SIGUARD connection module<br />
For connecting an external incoming supply contactor (second<br />
shut-down option) in category 3 <strong>and</strong> 4. The SIGUARD connection<br />
module is inserted to the right of the last motor starter in a<br />
safety segment. The terminals for connecting the positively<br />
driven NC contact of the contactor are located along side the terminals<br />
for connecting the contactor coil likewise on the TM-X terminal<br />
module. If no redundant contactor is required in<br />
category 2 (EN 954-1), for example, the feedback circuit has to<br />
be closed at these terminals with a jumper. This arrangement is<br />
also used instead of SIGUARD power module as an interface to<br />
the external safety relay when external safety relays are used.<br />
SIGUARD PM-D F1/F2/F3/F4/F5 power modules<br />
Following SIGUARD PM-D power modules are available for selection:<br />
PM-D F1 for evaluating emergency stop circuits with the function<br />
"monitored start“<br />
PM-D F2 for monitoring protective doors with the function "automatic<br />
start"<br />
PM-D F3 as PM-D F1/F2 expansion for time-delayed shutdown<br />
PM-D F4 for exp<strong>and</strong>ing safety circuits with other ET 200S motor<br />
starters, e.g. in another row<br />
PM-D F5 for transmitting the status of PM-D F1...4 over four<br />
floating release circuits to external safety devices (contact<br />
multipliers)<br />
No additional PM-S power module is required when using the SI-<br />
GUARD power modules. SIGUARD PM-D F1/F2/F3/F4 power<br />
modules monitor auxiliary voltages <strong>and</strong> contain the complete<br />
functionality of a safety relay. The PM-D F1 <strong>and</strong> PM-D F2 modules<br />
can be combined with the PM-D F3 or PM-D F4 modules. A<br />
PM-D F5 can be arranged in any position between PM-D F1...4<br />
<strong>and</strong> a PM-X.<br />
Every safety circuit, starting with a PM-D F1 ... 4, has to be terminated<br />
with a PM-X.<br />
Failsafe kit<br />
Every st<strong>and</strong>ard motor starter in a safety segment has to be supplemented<br />
with the failsafe kit (F-kit) in order to monitor the<br />
switching function. F-kit 1 supplements the DS1-x direct starter,<br />
F-kit 2 supplements the RS1-x reversing starter.<br />
The F-kits comprise<br />
Contact carriers for the terminal modules,<br />
one or two auxiliary switch blocks for the contactor / contactors<br />
of the motor starter, <strong>and</strong><br />
connecting cables.<br />
High Feature motor starters <strong>and</strong> their terminal modules come<br />
equipped with the F-kit functions.<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
11/33<br />
11
11<br />
Process I/O<br />
ET 200S distributed I/O<br />
SIGUARD safety engineering<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
SIGUARD Terminal Modules<br />
PM-PF30 S47 B1<br />
Terminal Module<br />
For PM-D F1/2 power modules<br />
with U1/U2 incoming supply <strong>and</strong><br />
sensor connection<br />
PM-PF30 S47 B0<br />
Terminal Module<br />
For PM-D F1/2 power modules<br />
with sensor connection<br />
PM-PF30 S47 C1<br />
Terminal Module<br />
For PM-D F3/4 power modules<br />
with U1/U2 incoming supply <strong>and</strong><br />
IN+/IN- control input<br />
PM-PF30 S47 C0<br />
Terminal Module<br />
For PM-D F3/4 power modules<br />
with U2 incoming supply<br />
PM-PF30 S47 D0<br />
Terminal Module<br />
For PM-D F5 power modules<br />
PM-X15 S27 01<br />
Terminal Module<br />
For SIGUARD connection module<br />
SIGUARD Power Modules<br />
PM-D F1 SIGUARD<br />
Power Module<br />
EMERGENCY STOP; monitored<br />
start; 2-channel<br />
PM-D F2 SIGUARD<br />
Power Module<br />
Protective door; autostart;<br />
2-channel<br />
PM-D F3 SIGUARD<br />
Power Module<br />
Expansion to F1/2 for an additional<br />
voltage group; timedelayed<br />
PM-D F4 SIGUARD<br />
Power Module<br />
Expansion to F1/2 for an additional<br />
voltage group<br />
PM-D F5 SIGUARD<br />
Power Module<br />
Expansion to PM-D F1 up to<br />
PM-D F4, contact multiplier<br />
11/34<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
3RK1 903-1AA00 F)<br />
3RK1 903-1AA10 F)<br />
3RK1 903-1AC00 F)<br />
3RK1 903-1AC10<br />
3RK1 903-1AD10<br />
3RK1 903-1AB00 F)<br />
3RK1 903-1BA00<br />
3RK1 903-1BB00<br />
3RK1 903-1BD00<br />
3RK1 903-1BC00<br />
3RK1 903-1BE00<br />
■ Selection <strong>and</strong> Ordering Data<br />
Accessories<br />
Order No.<br />
PM-X SIGUARD<br />
Connection module for incomingfeeder<br />
contactor; external safety<br />
circuits<br />
3RK1 903-1CB00 F)<br />
Failsafe kit 1<br />
Failsafe kit for DS1-x st<strong>and</strong>ard<br />
motor starter (not necessary for<br />
High Feature motor starter)<br />
3RK1 903-1CA00 F)<br />
Failsafe kit 2<br />
Failsafe kit for RS1-x st<strong>and</strong>ard<br />
motor starter (not necessary for<br />
High Feature motor starter)<br />
3RK1 903-1CA01 F)<br />
F) Subject to export regulations: AL: N, ECCN: EAR99
Migration to<br />
SIMATIC PCS 7<br />
12/2 Migration TELEPERM M<br />
12/2 Introduction<br />
12/4 OS Migration from TELEPERM M<br />
12/8 AS Migration from TELEPERM M<br />
12/10 Migration APACS+<br />
12/10 Introduction<br />
12/11 PCS 7/APACS+ ES Software<br />
12/12 PCS 7/APACS+ OS Software<br />
12/13 Migration SIMATIC PCS/TISTAR<br />
12/13 Migration of SIMATIC PCS / TISTAR<br />
systems with 505 controllers<br />
12/14 PCS 7/505 ES Software<br />
12/15 PCS 7/505 OS Software<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
12<br />
Migration to SIMATIC PCS 7<br />
Migration TELEPERM M<br />
Introduction<br />
■ Overview<br />
The TELEPERM ® M process control system from <strong>Siemens</strong> has<br />
proven itself worldwide in many different industry sectors in the<br />
past 20 years. More than 15,000 installed systems have proven<br />
their performance, reliability <strong>and</strong> user-friendliness in many years<br />
of service, even under extreme operating conditions.<br />
Many users are faced with the need to adapt their production operations<br />
to market requirements, which means having to exp<strong>and</strong><br />
or modernize their plants.<br />
SIMATIC PCS 7, the succesor generation for the process control<br />
system, was introduced by <strong>Siemens</strong> in 1997 for new plants <strong>and</strong><br />
plant expansions, <strong>and</strong> offers an open platform for modern, forward-looking<br />
<strong>and</strong> economical automation solutions in all industries.<br />
The installed platform of the old process control system represents<br />
an immense investment in hardware <strong>and</strong> application software<br />
as well as a wealth of valuable <strong>and</strong> complex know-how accumulated<br />
by operating <strong>and</strong> maintenance personnel.<br />
The objective of the migration is to modernize the existing platform<br />
step-by-step without changing the system, <strong>and</strong> at the same<br />
time to guarantee past investments for as long as possible. For<br />
this purpose, <strong>Siemens</strong> has been offering optimized migration solutions<br />
for the transition from TELEPERM M to SIMATIC PCS 7<br />
since 1996. The range of migration products covers hardware<br />
<strong>and</strong> software components as well as services for converting application<br />
software, on-site conversions, <strong>and</strong> the migration of<br />
complete systems.<br />
2/2<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
At the beginning, the main migration of customers was the stepby-step<br />
modernization <strong>and</strong> functional expansion of individual<br />
components of the existing TELEPERM M systems:<br />
Replacement of existing automation systems by future-compatible<br />
automation systems under the premise of importing<br />
existing application software <strong>and</strong> TELEPERM M I/O.<br />
Replacement of operation <strong>and</strong> monitoring systems by operator<br />
systems on the basis of SIMATIC PCS 7<br />
Integration of the distributed SIMATIC process I/Os<br />
Customers are increasingly choosing a more direct migration of<br />
TELEPERM M to SIMATIC PCS 7. They are selecting the full<br />
range of SIMATIC system components, which have been proven<br />
worldwide. They therefore benefit from the characteristics of a<br />
modern process control system <strong>and</strong> the synergies of TIA, <strong>and</strong><br />
are able at the same time to continue using their existing<br />
TELEPERM M I/Os. <strong>Siemens</strong> supports this trend by means of<br />
new migration products as well as optimized services <strong>and</strong> inhouse<br />
tools for hardware <strong>and</strong> software conversion.<br />
With the modern, pioneering SIMATIC PCS 7 process control<br />
system, innovative migration solutions <strong>and</strong> services, many years<br />
of know-how in process control engineering <strong>and</strong> migration, as<br />
well as worldwide servicing, <strong>Siemens</strong> demonstrates its expertise<br />
in the process control engineering field <strong>and</strong> offers the security of<br />
a reliable partner.
■ Options<br />
Migration Services<br />
For a migration project to succeed it is not enough just to have a<br />
technical solution that is optimally adapted to the customer ’s<br />
needs <strong>and</strong> the individual conditions of the plant in question.<br />
Equally important is the fast <strong>and</strong> punctual implementation of this<br />
solution at a high level of quality.<br />
We thus offer you not only services for single phases of the migration<br />
process, e.g. AS conversion with retention of the<br />
TELEPERM M I/Os or substitution of the operator systems incl.<br />
conversion of your user software, but also for the complete migration<br />
of your plant - all from one source.<br />
Our migration specialists are familiar with the systems technology<br />
behind TELEPERM M <strong>and</strong> SIMATIC PCS 7 <strong>and</strong> have many<br />
years of experience in engineering, commissioning <strong>and</strong> service.<br />
They will inform you about the migration options available, analyze<br />
your plant, provide you with individual consulting <strong>and</strong>, finally,<br />
draw up a detailed quotation for your migration project.<br />
Short stoppage times call for exact planning, which is why our<br />
migration specialists join you in organizing <strong>and</strong> coordinating the<br />
smooth performance of all the activities itemized in the quotation.<br />
The user software is the know-how medium <strong>and</strong> embodies a<br />
large part of the overall investment volume. Hence the quality of<br />
its conversion into the new system world is a key criterion for a<br />
migration’s economic efficiency. The modern conversion tools<br />
that we developed ourselves enable the conversion work to proceed<br />
quickly <strong>and</strong> reliably, <strong>and</strong> guarantee software of constant<br />
quality, reliability <strong>and</strong> verifiability. All the conversion steps performed<br />
are documented, as are the manual reconfigurations required<br />
in special cases.<br />
Finally, we will draw up detailed documentation of your plant as<br />
soon as the re-start is completed. We even see to the proper disposal<br />
of any replaced system components.<br />
Contact address for information, consulting, analysis <strong>and</strong> quotations:<br />
<strong>Siemens</strong> AG<br />
Uwe Skoeries<br />
Tel.: +49 721 595-8789<br />
Fax: +49 721 595-5121<br />
E-mail: uwe.skoeries@siemens.com<br />
Migration to SIMATIC PCS 7<br />
Migration TELEPERM M<br />
■ More information<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Introduction<br />
You can find further information, order data <strong>and</strong> technical data<br />
on the various migration products for TELEPERM M in the following<br />
sections "OS Migration from TELEPERM M" <strong>and</strong> "AS Migration<br />
from TELEPERM M" as well as in the catalog PLT 112 or<br />
CA 01 under "Process Control <strong>System</strong> TELEPERM M".<br />
More migration products can also be found in the catalog ST<br />
PCS 7.A (Add Ons for the SIMATIC PCS 7 Process Control <strong>System</strong>).<br />
Additional information is available in the Internet under:<br />
http://www.siemens.com/teleperm<br />
2/3<br />
12
12<br />
Migration to SIMATIC PCS 7<br />
Migration TELEPERM M<br />
OS Migration TELEPERM M<br />
■ Overview<br />
The PCS7/TM-OS operator systems offered here can be used for<br />
the migration of older TELEPERM M operator systems. This is<br />
simply done by replacing the OS 252, OS 26x or OS 52x operator<br />
systems already installed in existing TELEPERM M<br />
plants/plant units with the SIMATIC PCS 7 operator systems,<br />
which are designed for connection to the TELEPERM M plant<br />
bus CS 275.<br />
As explained in the previous section, The PCS 7/TM OS operator<br />
system with double channel functionality, which is designed to<br />
be operated simultaneously on the TELEPERM M plant bus<br />
CS 275 <strong>and</strong> the PCS 7 plant bus, can be used in combination<br />
with the GT104CS gateway (SIMATIC PCS 7 add-on product,<br />
see the ST PCS 7.A catalog). The effective connection of existing<br />
TELEPERM M plant units with SIMATIC PCS 7 plant units is<br />
thus possible. The cross-bus communication load can be skilfully<br />
shared using this combination. While the PCS 7/TM-OS operator<br />
system with double channel functionality sees to AS-OS<br />
communication with the automation systems on the two plant<br />
buses CS 275 <strong>and</strong> Industrial Ethernet <strong>and</strong> to time synchronization<br />
for the TELEPERM M subplant, the cross-bus AS-AS communication<br />
takes place through the GT104CS gateway.<br />
The PCS7/TM-OS operator systems can be used as display <strong>and</strong><br />
control components for TELEPERM M automation systems<br />
AS 215,<br />
AS 220 S, AS 220 K, AS 220 H,<br />
AS 230, AS 230 K,<br />
AS 235, AS 235 K, AS 235 H,<br />
AS 388/TM <strong>and</strong> AS 488/TM as well as<br />
SIMATIC S5-150U/S5-155U on the CS 275 plant bus.<br />
This basic hardware available as single station systems, servers<br />
<strong>and</strong> clients for PCS 7/TM-OS may be exp<strong>and</strong>ed with the following<br />
options, depending on their use <strong>and</strong> the defined scope of<br />
supply:<br />
PCS 7 OS Software,<br />
components for connecting to the TELEPERM M plant bus<br />
CS 275 (interface module, local bus connecting cable <strong>and</strong><br />
PCS 7/TM-OS coupling package),<br />
signal module <strong>and</strong><br />
PCS 7/TM-OCX (NORA) program package.<br />
Also relevant for the configuration of PCS 7/TM-OS are the additional/expansion<br />
components, multi-VGA graphics cards, monitors<br />
<strong>and</strong> chipcard readers available for St<strong>and</strong>ard PCS 7 OS (see<br />
the sections "ES/OS/Batch/IT basic devices" <strong>and</strong> "Administration"<br />
in the chapter "<strong>System</strong> Neutral Components"). OS options<br />
such as redundancy <strong>and</strong> signal output (see the section "OS<br />
hardware" in the chapter "Operator <strong>System</strong>") are also useful.<br />
2/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Function<br />
Coupling packages for PCS 7/TM-OS V3.0<br />
With the coupling packages for PCS 7/TM-OS it is possible for<br />
the self-configured operator systems to exchange information<br />
with automation systems on the CS 275 plant bus. They contain<br />
a bus-specific channel DLL <strong>and</strong> a TM Manager. The channel<br />
DLL adapts the TELEPERM M frames to the OS-specific data<br />
structures <strong>and</strong> procedures by converting the protocol. The TM<br />
Manager is a configuration assistant that supports the following<br />
configuration functions:<br />
ORPA Import<br />
The ORPA Import function creates (in the operator system) for<br />
TELEPERM M st<strong>and</strong>ard <strong>and</strong> user blocks structured variables<br />
in accordance with the AS data defined in the PROGRAF AS+<br />
configuration tool. The selection of parameters to be imported<br />
can be modified using filters <strong>and</strong> a dialog box.<br />
Block Import<br />
The Block Import function creates (in the operator system) for<br />
TELEPERM M st<strong>and</strong>ard <strong>and</strong> user block instances of the block<br />
types defined in PROGRAF AS+. The selection of parameters<br />
to be imported can be modified using filters <strong>and</strong> a dialog box.<br />
Connection Import<br />
The Connection Import function generates connections in the<br />
TELEPERM M channel CS 275. Flags can be set for transmitting<br />
status signals or plain-text messages, <strong>and</strong> for loading<br />
onto the corresponding automation system.<br />
Signal Generator<br />
The Signal Generator function determines the block instances<br />
which were imported into the operator system <strong>and</strong> generates<br />
signals for said instances in the AlarmLogging. The message<br />
texts can be parameterized. Signal class <strong>and</strong> signal type can<br />
be bit-specifically defined for MKS blocks.<br />
Batch Import<br />
The Batch Import function merges the SIMATIC BATCH-specific<br />
configuration in the SIMATIC Manager <strong>and</strong> in<br />
TELEPERM M <strong>and</strong> prepares the data for the SIMATIC BATCH<br />
data household.<br />
The coupling packages for PCS 7/TM-OS are available in<br />
3 different versions depending on the lower-level TELEPERM M<br />
automation systems:<br />
AS23x/ASx88<br />
for the systems AS 215, AS 230, AS 230 K, AS 235, AS 235 K,<br />
AS 235 H, AS 388/TM, AS 488/TM, <strong>and</strong> for SIMATIC S5-<br />
150U/S5-155U<br />
AS220<br />
for the systems AS 220 S, AS 220 K, AS 220 H<br />
AS220/AS23x/ASx88<br />
for all the previously listed systems<br />
Coupling package upgrade to PCS 7/TM-OS V3.0<br />
An upgrade package that also includes the PCS 7/TM-OCX program<br />
package is available to upgrade existing WinCC/TM V1.0x<br />
or PCS 7/TM-OS V2.x coupling packages. One upgrade package<br />
is required for each PCS 7/TM-OS single station system, operator<br />
terminal or server. The order number of the upgrade must<br />
be selected according to the installed platform (type of PCS<br />
7/TM-OS coupling package <strong>and</strong>/or PCS 7/TM-OCX (NORA) program<br />
package).
PCS 7/TM-OCX (NORA) Program Package V3.0<br />
Faceplate (here for the RN block) in the TELEPERM M NORA display (left)<br />
<strong>and</strong> the PCS 7 layout (right)<br />
The PCS 7/TM-OCX (NORA) program package comprises:<br />
Faceplates for the st<strong>and</strong>ardized display of operable<br />
TELEPERM M AS function blocks in various hierarchy levels<br />
(symbol display/group display/loop display)<br />
Faceplates for the visualization of PCS 7 driver blocks of the<br />
TELEPERM M I/Os<br />
The faceplates for the AS st<strong>and</strong>ard function blocks are comparable<br />
with the st<strong>and</strong>ardized displays of the TELEPERM M operator<br />
system OS 525 or with the layout of PCS 7 process displays.<br />
They are of multi-lingual design, i.e. the user can choose between<br />
the languages German, English <strong>and</strong> French. The related<br />
electronic documentation is supplied on CD in German <strong>and</strong> English.<br />
Process connection takes place by linking the faceplate to the<br />
AS st<strong>and</strong>ard function block. The Object Control ActiveX (OCX)<br />
interactive graphics element performs the logic operation with<br />
the process variables.<br />
As a result, the PCS7/TM-OCX (NORA) program package not<br />
only makes the configuration of pictures easier, it also does<br />
much to simplify <strong>and</strong> speed up the entire OS configuration process.<br />
For some AS st<strong>and</strong>ard function blocks the PCS 7/TM-OCX<br />
(NORA) program package offers not only faceplates in the<br />
PCS 7 layout but also faceplates in the TELEPERM M NORA presentation.<br />
Both faceplate types can be used simultaneously on<br />
the same computer. However, you can use the displays of only<br />
one block type for the function "Select display using measuring<br />
point".<br />
Migration to SIMATIC PCS 7<br />
Migration TELEPERM M<br />
OS Migration TELEPERM M<br />
OS <strong>Engineering</strong> Bundle for TM Migration<br />
The PCS 7/TM-OS coupling package for AS 23x/488 <strong>and</strong> the<br />
PCS 7 <strong>Engineering</strong> Software OS for 2,000 POs/RC 64K are available<br />
as economical preferred versions in the bundle<br />
"OS <strong>Engineering</strong> for TELEPERM M Migration". The benefits are<br />
felt above all by customers who are using a PCS 7/TM-OS operator<br />
system for the first time <strong>and</strong> need to create the necessary<br />
engineering conditions to do so.<br />
The number of configurable process objects <strong>and</strong> variables can<br />
be increased further by means of add-on PCS 7 <strong>Engineering</strong><br />
Power Packs if required.<br />
The bundle "OS <strong>Engineering</strong> for TELEPERM M Migration“<br />
can also be used together with the SIMATIC PCS 7/TM-<br />
OS Server IL 40 S V2 BCE <strong>and</strong> the PROGRAF AS+/NT program<br />
package listed in the "Selection <strong>and</strong> ordering data" to configure<br />
an AS/OS <strong>Engineering</strong> Station for subsystems networked by the<br />
CS 275 plant bus. In case of direction migration to SIMATIC<br />
PCS 7, during which existing TELEPERM M automation systems<br />
are replaced by PCS 7 automation systems upon receiving the<br />
TELEPERM M I/Os, the engineering station can be extended in<br />
addition with PCS 7 <strong>Engineering</strong> Software AS. The bus interface<br />
for the PCS 7 Industrial Ethernet plant bus, which is required for<br />
ES-AS communication, is already included in the SIMATIC<br />
PCS 7/TM-OS Server IL 40 S V2 BCE.<br />
■ Integration<br />
Connecting systems with TELEPERM M basic functions to<br />
SIMATIC BATCH V6.0<br />
Using the coupling packages for PCS 7/TM-OS it is possible to<br />
connect AS 23x or AS 488/TM automation systems, whose functional<br />
process areas are automated with GF blocks of the basic<br />
functions program package in version V1.3 <strong>and</strong> lower<br />
(6DS5305-8AA; released for delivery in 08/89), to SIMATIC<br />
BATCH V6.0. Connection takes place through the UNIB, TR1B<br />
<strong>and</strong> EM1B interface blocks, which are inserted in the AS structure.<br />
The interface blocks enable SIMATIC BATCH to dock on in<br />
order to forward modes of operation, setpoint values <strong>and</strong> phase<br />
change comm<strong>and</strong>s to the basic function, <strong>and</strong> to read its status.<br />
Each interface block on the AS side is assigned an equivalent<br />
SIMATIC BATCH inteface block in the CFC, which is visible in the<br />
variable household of PCS 7 operator systems.<br />
The double channel functionality also supports connection to SI-<br />
MATIC BATCH, i.e. plant units can be used by different systems<br />
within a recipe. It is irrelevant for the recipe whether a plant unit<br />
is on a SIMATIC PCS 7 automation system or on a TELEPERM M<br />
automation system.<br />
Converting existing user software<br />
The user software is the know-how medium <strong>and</strong> embodies a<br />
large part of the overall investment volume. We provide you,<br />
therefore, with the fast <strong>and</strong> reliable conversion of your user software<br />
for use on the new system platform. In doing so we make<br />
allowance for sector-specific properties as well as special plant<br />
solutions. Using tools that we developed ourselves we guarantee<br />
software of constant quality, reliablity <strong>and</strong> verifiability. All the<br />
conversion steps performed are documented, as are the manual<br />
reconfigurations required in special cases.<br />
Contact address for quotations <strong>and</strong> more information:<br />
<strong>Siemens</strong> AG<br />
Uwe Skoeries<br />
Tel.: +49 721 595-8789<br />
Fax: +49 721 595-5121<br />
E-mail: uwe.skoeries@siemens.com<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/5<br />
12
12<br />
Migration to SIMATIC PCS 7<br />
Migration TELEPERM M<br />
OS Migration TELEPERM M<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Single station<br />
Complies with St<strong>and</strong>ard PCS 7 Single Station, see the chapter<br />
"ES/OS/BATCH/IT basic devices"<br />
PCS 7 ES/OS IL 40 S V2 BCE<br />
with SIMATIC PC in rack of<br />
19" design, Pentium 4 with<br />
2.8 GHz <strong>and</strong> more, 1 Gbyte RAM<br />
(2 x 512 Mbyte), sound, EIDE-<br />
RAID 1 with 2 hard disks of<br />
120 Gbyte, graphics controller on<br />
board with Dynamic Video Memory,<br />
DVD±RW IDE, optical mouse,<br />
2x FastEthernet RJ45 (on board<br />
for connection to OS-LAN/terminal<br />
bus + PCI card for double<br />
channel mode),<br />
without monitor, keyboard <strong>and</strong><br />
printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish)<br />
PCS 7 OS Software Single Station<br />
preinstalled <strong>and</strong> on restore DVD,<br />
but without authorization<br />
Other items required:<br />
interface module for CS 275 incl.<br />
local bus connecting cable,<br />
PCS 7 OS Software Single Station<br />
(for authorization),<br />
PCS 7/TM-OS coupling package,<br />
optional: signal module,<br />
PCS 7/TM-OCX (NORA)<br />
Note:<br />
the coupling package for<br />
PCS 7/TM-OS <strong>and</strong> PCS 7/TM-<br />
OCX (NORA) are not preinstalled<br />
(unlike on the OS Server)<br />
6ES7 650-0GC06-0YX0 D)<br />
2/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Selection <strong>and</strong> Ordering Data<br />
Server<br />
SIMATIC PCS 7/TM-OS Server<br />
IL40 S V2 BCE<br />
SIMATIC PC in rack of 19" design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
1 Gbyte RAM (2 x 512 Mbyte),<br />
sound, EIDE-RAID 1 with 2 hard<br />
disks of 120 Gbyte, graphics controller<br />
on board with Dynamic<br />
Video Memory, DVD-ROM IDE,<br />
2 x Fast Ethernet RJ45 (on board<br />
for connection to OS-LAN/terminal<br />
bus + PCI card for double<br />
channel operation), interface<br />
module for CS 275, optical<br />
mouse, without monitor, keyboard<br />
<strong>and</strong> printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish)<br />
PCS 7 OS Software Server,preinstalled<br />
<strong>and</strong> on restore DVD but<br />
without authorization<br />
Coupling package for PCS 7/TM-<br />
OS <strong>and</strong> PCS 7/TM-OCX (NORA)<br />
preinstalled but without authorization<br />
Descriptions of coupling<br />
package for PCS 7/TM-OS <strong>and</strong><br />
PCS 7/TM-OCX (NORA) preinstalled<br />
as PDF file (German <strong>and</strong><br />
English)<br />
Instruction manual of the interface<br />
module for CS 275 is provided as<br />
a PDF file on CD (German <strong>and</strong><br />
English)<br />
Order No.<br />
Without signal module 6DL2 207-1CA D)<br />
With signal module<br />
Other items required:<br />
local bus connecting cable,<br />
PCS 7 OS Software Server <strong>and</strong><br />
coupling package for PCS 7/TM-<br />
OS (each for authorization);<br />
optional when there is a process<br />
visualization module on the server:<br />
PCS 7/TM-OCX (NORA)<br />
Client<br />
6DL2 207-1DA D)<br />
Complies with St<strong>and</strong>ard PCS 7 Client, see the chapter "ES/OS/BATCH/IT<br />
basic devices"<br />
PCS 7 OS Client IL 40 S V2<br />
SIMATIC PC in rack of 19“ design,<br />
Pentium 4 with 2.8 GHz <strong>and</strong> more,<br />
512 Mbyte RAM (2 x 256 Mbyte),<br />
EIDE hard disk of 80 Gbyte,<br />
graphics controller on board with<br />
Dynamic Video Memory, DVD-<br />
ROM IDE, optical mouse,Fast Ethernet<br />
RJ45 on board for connection<br />
to OS-LAN, without monitor,<br />
keyboard <strong>and</strong> printer,<br />
Windows 2000 Professional MUI<br />
(German, English, French, Italian,<br />
Spanish)<br />
PCS 7 OS Software Client preinstalled<br />
<strong>and</strong> on restore DVD, but<br />
without authorization<br />
Other items required:<br />
PCS 7 OS Software Client (for<br />
authorization),<br />
optional: signal module,<br />
PCS 7/TM-OCX (NORA)<br />
Note:<br />
PCS 7/TM-OCX (NORA) is not<br />
preinstalled (unlike on the<br />
OS Server)<br />
6ES7 650-0GD06-0YX0 D)
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Additional <strong>and</strong> expansion components<br />
Hardware Coupling Package for<br />
CS 275<br />
Comprising an interface module<br />
for CS 275, 2.5-m local bus connecting<br />
cable, documentation<br />
(German or English)<br />
Coupling packages for<br />
PCS 7/TM-OS V3.0<br />
On request<br />
PCS 7/TM-OS Coupling Package<br />
for AS 23x/AS x88<br />
bilingual (German, English)<br />
Type of delivery: Certificate of license<br />
<strong>and</strong> authorization diskette;<br />
software <strong>and</strong> electronic<br />
documentation on CD<br />
6DS5 140-1AX A)<br />
PCS 7/TM-OS Coupling Package<br />
for AS 220<br />
bilingual (German, English)<br />
Type of delivery: Certificate of license<br />
<strong>and</strong> authorization diskette;<br />
software <strong>and</strong> electronic<br />
documentation on CD<br />
6DS5 140-1BX A)<br />
PCS 7/TM-OS Coupling Package<br />
for AS 220/AS 23x/AS x88<br />
bilingual (German, English)<br />
Type of delivery: Certificate of license<br />
<strong>and</strong> authorization diskette;<br />
software <strong>and</strong> electronic<br />
documentation on CD<br />
6DS5 140-1CX A)<br />
PCS 7/TM-OCX (NORA) Program<br />
Package V3.0<br />
St<strong>and</strong>ardized displays for operable<br />
TELEPERM M AS function<br />
blocks <strong>and</strong> for PCS 7 driver<br />
blocks of the TELEPERM M I/Os,<br />
trilingual (German, English,<br />
French)<br />
type of delivery: Certificate of<br />
license <strong>and</strong> authorization diskette;<br />
electronic documentation<br />
(German, English) <strong>and</strong> software<br />
on CD<br />
Note:<br />
When the PCS 7/TM-OCX (NORA)<br />
is used, a 6DS5 034-1AX program<br />
package has to be ordered<br />
for each single-user system (OS<br />
Single Station) <strong>and</strong> for each operator<br />
terminal (OS Client) of a<br />
multi-user system. A program<br />
package is also required for the<br />
process visualization module if it<br />
is used on the server.<br />
6DS5 034-1AX A)<br />
Migration to SIMATIC PCS 7<br />
Migration TELEPERM M<br />
OS Migration TELEPERM M<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
OS <strong>Engineering</strong> Bundle for<br />
TM Migration<br />
Comprising:<br />
PCS 7/TM-OS coupling package<br />
for AS 23x/488, order No.<br />
6DS5 140-1AX, <strong>and</strong><br />
PCS 7 <strong>Engineering</strong> Software OS<br />
for 2,000 POs/RC 64K, order<br />
No. 6ES7 658-2DB06-0YA0<br />
6DL5 200-1AX00-0XA0 C)<br />
Coupling package upgrade to<br />
PCS 7/TM-OS V3.0<br />
Comprising software CD <strong>and</strong>:<br />
without authorization for process<br />
coupling <strong>and</strong> PCS 7/TM-OCX<br />
Authorization for PCS 7/TM-OS<br />
AS23x/ASx88 coupling package<br />
Authorization for PCS 7/TM-OS<br />
AS220 coupling package<br />
Authorization for PCS 7/TM-OS<br />
AS220/AS23x/ASx88 coupling<br />
package<br />
A) Subject to export regulations: AL: N, ECCN: 5D992B2<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
D) Subject to export regulations: AL: N, ECCN: 5D992B1<br />
Other additional/expansion components such as utility software, power<br />
cables, signal modules, multi-VGA graphics cards, OS redundancy components,<br />
chipcard readers, memory expansions, keyboards or monitors<br />
can be found in the sections "ES/OS/BATCH/IT basic devices" <strong>and</strong> "Administration"<br />
in the chapter "<strong>System</strong> Neutral Components", in the chapter<br />
"ES/OS/BATCH/IT basic devices" or in the section "OS hardware" in the<br />
chapter "Operator <strong>System</strong>". The PCS 7 OS software required for use as a<br />
single station, server or client can be found in the section "OS software".<br />
■ More information<br />
6DS5 128-1XX00-2XX4 A)<br />
6DS5 128-1XX40-2XX4 A)<br />
6DS5 128-1XX50-2XX4 A)<br />
6DS5 128-1XX60-2XX4 A)<br />
Authorization for PCS 7/TM-OCX 6DS5 128-1XX02-2XX4 A)<br />
Authorization for PCS 7/TM-OS<br />
AS23x/ASx88 coupling package<br />
<strong>and</strong> PCS 7/TM-OCX<br />
6DS5 128-1XX42-2XX4 A)<br />
Authorization for PCS 7/TM-OS<br />
AS220 coupling package <strong>and</strong><br />
PCS 7/TM-OCX<br />
6DS5 128-1XX52-2XX4 A)<br />
Authorization for PCS 7/TM-OS<br />
AS220/AS23x/ASx88 coupling<br />
package <strong>and</strong> PCS 7/TM-OCX<br />
6DS5 128-1XX62-2XX4 A)<br />
Customized special configurations for TELEPERM M operator<br />
systems PCS 7/TM-OS<br />
On request:<br />
<strong>Siemens</strong> Karlsruhe<br />
Tel.: +49 721 595-4272 or -3776<br />
Fax: +49 721 595-6525<br />
E-mail:<br />
gerhard.kuhn@siemens.com<br />
helmut.heib@siemens.com<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/7<br />
12
12<br />
Migration to SIMATIC PCS 7<br />
Migration TELEPERM M<br />
AS Migration from TELEPERM M<br />
■ Overview<br />
The process I/Os of existing plants with their extensive wiring<br />
<strong>and</strong> routing, large stock of I/O modules, power supply units,<br />
cabinets <strong>and</strong> sometimes Ex isolating devices represent, together<br />
with the plant’s documentation <strong>and</strong> the maintenance personnel’s<br />
know-how, a highly valuable asset. Plant managers are<br />
often concerned, therefore, to preserve <strong>and</strong> use these resources<br />
for as long as possible.<br />
They are supported in this endeavor in excellent manner by the<br />
PCS 7/TM I/O migration package <strong>and</strong> by the services which are<br />
offered in this connection for the on-site conversion of the AS as<br />
well as implementation of the user’s TELEPERM M automation<br />
system structure in a SIMATIC PCS 7 structure.<br />
The PCS 7/TM I/O migration package unites a SIMATIC PCS 7<br />
automation system with the components required for connecting<br />
the TELEPERM I/Os in a MIG II migration rack. This migration<br />
rack provides in addition 5 slots for TELEPERM I/O modules <strong>and</strong><br />
replaces the module rack with CPU in the TELEPERM M basic<br />
cabinet of the automation system that is undergoing the migration.<br />
The SIMATIC PCS 7 automation system needs suitable driver<br />
blocks in order to address the TELEPERM I/O modules. A library<br />
with these driver blocks <strong>and</strong> an S7 object manager for the hardware<br />
configuration in HW Config are supplied with the PCS 7/TM<br />
I/O migration package.<br />
The different versions of the PCS 7/TM I/O migration package<br />
are referred to below as AS 414-3 TM I/O, AS 416-2 TM I/O <strong>and</strong><br />
AS 416-3 TM I/O depending on the type of automation system.<br />
2/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Integration<br />
Migratable TELEPERM I/O modules<br />
The spectrum of TELEPERM I/O modules that can be operated<br />
on SIMATIC PCS 7 automation systems covers all module types<br />
that have been released for the TELEPERM M automation system<br />
AS 488/TM. An overview is available as a configuration list<br />
on the Internet pages of TELEPERM M under Support -> Info<br />
Material -> Configuration of I/Os.<br />
Additional information is available in the Internet under:<br />
http://www.siemens.com/teleperm<br />
AS migration with retention of the TELEPERM I/Os / conversion<br />
of existing user software<br />
Our migration specialists will join you in drawing up an optimum<br />
migration solution for your requirements <strong>and</strong> the technical conditions<br />
of your plant. We provide services for single phases of<br />
the migration process, e.g. AS conversion with retention of the<br />
TELEPERM M I/Os, in addition to the complete migration of your<br />
plant - all from one source.<br />
And we can also provide you with the fast <strong>and</strong> reliable conversion<br />
of your user software for use on the new system platform. In<br />
doing so we make allowance for sector-specific properties as<br />
well as special plant solutions. Using tools that we developed<br />
ourselves we guarantee software of constant quality, reliablity<br />
<strong>and</strong> verifiability. All the conversion steps performed are documented,<br />
as are the manual reconfigurations required in special<br />
cases.<br />
Contact address for quotations <strong>and</strong> more information:<br />
<strong>Siemens</strong> AG<br />
Uwe Skoeries<br />
Tel.: +49 721 595-8789<br />
Fax: +49 721 595-5121<br />
E-mail: uwe.skoeries@siemens.com
■ Selection <strong>and</strong> Ordering Data Order No.<br />
Ordering units for automation systems (preferred configurations)<br />
AS 414-3 TM I/O automation<br />
system<br />
Comprising:<br />
MIG II migration rack with slots for<br />
5 TELEPERM M I/O modules,<br />
CPU 414-3 with 3 interfaces<br />
(MPI/DP, DP <strong>and</strong> slot for<br />
IF module),<br />
1.4 Mbyte main memory<br />
(0.7 Mbyte each for program <strong>and</strong><br />
data) <strong>and</strong> 2 Mbyte RAM memory<br />
card, 2 backup batteries,<br />
CP 443-1 communications module<br />
for connection to Industrial<br />
Ethernet plant bus,<br />
FM 456-4 function module with<br />
8 MByte memory expansion <strong>and</strong><br />
5V Flash-EPROM 8 Mbyte memory<br />
card,<br />
TPM 478-2 interface module for<br />
TELEPERM M I/O bus A <strong>and</strong> B,<br />
software CD with PCS 7 driver<br />
block library for TELEPERM M I/O<br />
modules, operating software for<br />
FM 456-4, S7 object manager,<br />
M7-SYS Realtime V4.0 <strong>and</strong> documentation<br />
for PCS 7/TM I/O in<br />
PDF format (German, English)<br />
PS 405 power supply; 20 A, for<br />
24 V DC<br />
6DL2 100-1AJ30 A)<br />
PS 405 power supply; 10 A for<br />
24 V DC<br />
AS 416-2 TM I/O automation<br />
system<br />
Comprising:<br />
MIG II migration rack with slots for<br />
5 TELEPERM M I/O modules,<br />
CPU 416-2 with 2 interfaces<br />
(MPI/DP <strong>and</strong> DP),<br />
2.8 Mbyte main memory<br />
(1.4 Mbyte each for program <strong>and</strong><br />
data) <strong>and</strong> 4 Mbyte RAM memory<br />
card, 2 backup batteries,<br />
CP 443-1 communications module<br />
for connection to Industrial<br />
Ethernet plant bus,<br />
FM 456-4 function module with<br />
8 MByte memory expansion <strong>and</strong><br />
5V Flash-EPROM 8 Mbyte memory<br />
card,<br />
TPM 478-2 interface module for<br />
TELEPERM M I/O bus A <strong>and</strong> B,<br />
software CD with PCS 7 driver<br />
block library for TELEPERM M I/O<br />
modules, operating software for<br />
FM 456-4, S7 object manager,<br />
M7-SYS Realtime V4.0 <strong>and</strong> documentation<br />
for PCS 7/TM I/O in<br />
PDF format (German, English)<br />
6DL2 100-1BJ30 A)<br />
PS 405 power supply; 20 A, for<br />
24 V DC<br />
6DL2 100-1AK30 A)<br />
PS 405 power supply; 10 A for<br />
24 V DC<br />
6DL2 100-1BK30 A)<br />
Migration to SIMATIC PCS 7<br />
Migration TELEPERM M<br />
AS Migration from TELEPERM M<br />
■ Selection <strong>and</strong> Ordering Data<br />
AS 416-3 TM I/O automation<br />
system<br />
Comprising:<br />
MIG II migration rack with slots for<br />
5 TELEPERM M I/O modules,<br />
CPU 416-3 with 3 interfaces<br />
(MPI/DP, DP <strong>and</strong> slot for<br />
IF module),<br />
5.6 Mbyte main memory<br />
(2.8 Mbyte each for program <strong>and</strong><br />
data) <strong>and</strong> 8 Mbyte RAM memory<br />
card, 2 backup batteries,<br />
CP 443-1 communications module<br />
for connection to Industrial<br />
Ethernet plant bus,<br />
FM 456-4 function module with<br />
8 MByte memory expansion <strong>and</strong><br />
5V Flash-EPROM 8 Mbyte memory<br />
card,<br />
TPM 478-2 interface module for<br />
TELEPERM M I/O bus A <strong>and</strong> B,<br />
software CD with PCS 7 driver<br />
block library for TELEPERM M I/O<br />
modules, operating software for<br />
FM 456-4, S7 object manager,<br />
M7-SYS Realtime V4.0 <strong>and</strong> documentation<br />
for PCS 7/TM I/O in<br />
PDF format (German, English)<br />
Order No.<br />
PS 405 power supply; 20 A, for<br />
24 V DC<br />
6DL2 100-1AL30 A)<br />
PS 405 power supply; 10 A for<br />
24 V DC<br />
6DL2 100-1BL30 A)<br />
Individual components for automation systems<br />
See ordering data for accessories<br />
for st<strong>and</strong>ard automation systems<br />
in the section "<strong>Automation</strong> <strong>System</strong>s"<br />
In addition for AS 414-3 TM I/O,<br />
AS 416-2 TM I/O <strong>and</strong><br />
AS 416-3 TM I/O:<br />
PCS 7/TM I/O coupling package<br />
Comprising:<br />
TPM 478-2 interface module<br />
Software CD with PCS 7 driver<br />
block library for TELEPERM M<br />
I/O modules, operating software<br />
for FM 456-4, S7 object manager<br />
<strong>and</strong> M7-SYS Realtime V4.0<br />
Documentation for 7/TM I/O in<br />
PDF format (German, English)<br />
Product information<br />
IF 961-DI0 Interface Module<br />
Digital I/O for controlling the cabinet<br />
lamp<br />
Still available for TELEPERM M<br />
migration, order no. 6ES7 961-<br />
1AA00-0AC0<br />
6ES7 478-2DA10-0AC0<br />
A) Subject to export regulations: AL: N, ECCN: 5D992B2<br />
Note :<br />
The PCS 7/TM-OCX (NORA) program package provides suitable faceplates<br />
for visualization of the PCS 7/TM I/O driver blocks (see the section<br />
"Operator <strong>System</strong> - OS Migration“).<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/9<br />
12
12<br />
Migration to SIMATIC PCS 7<br />
Migration APACS+<br />
Introduction<br />
■ Overview<br />
The APACS+ process control system has been used successfully<br />
world-wide for over 10 years. Its functionality, reliability <strong>and</strong><br />
user-friendliness have been demonstrated in more than<br />
10,000 installed systems. In the meantime industry regulations<br />
have become more stringent <strong>and</strong> the dem<strong>and</strong>s of industrial production<br />
more exacting.<br />
A study of APACS+ systems used in the manufacturing sector indicated<br />
that the dem<strong>and</strong>s made of the HMI level (operator system)<br />
have gone up by a disproportionate amount compared to<br />
the controller <strong>and</strong> I/O level. As the result, an operator system<br />
(OS) installed four years ago is no longer able to satisfy today’s<br />
st<strong>and</strong>ards <strong>and</strong> has to be brought up to the current state of the art<br />
using modern technology. <strong>Automation</strong> systems (AS) have a far<br />
longer useful life by comparison.<br />
An installed APACS+ system represents an immense investment<br />
in hardware <strong>and</strong> application software as well as a wealth of valuable<br />
know-how accumulated by operating <strong>and</strong> maintenance<br />
personnel; selective migration through modernization of the operator<br />
system <strong>and</strong> engineering systems without changing the existing<br />
controller <strong>and</strong> I/O level system thus offers a welcome opportunity<br />
to protect a great deal of your past investment for as<br />
long as possible.<br />
A suitable open system platform for this purpose is available<br />
from <strong>Siemens</strong> in the form of its modern, pioneering SIMATIC<br />
PCS 7 process control system.<br />
Migration to SIMATIC PCS 7 technology can increase the functionality<br />
<strong>and</strong> performance of an APACS+ process control system<br />
by a significant amount. And APACS+ customers benefit in addition<br />
from continuous further development <strong>and</strong> long-term global<br />
service for the installed APACS+ base as well as from the advantages<br />
to be gained from TIA (Totally Integrated <strong>Automation</strong>) <strong>and</strong><br />
SIMATIC IT. This shortens the time to market, protects existing investments<br />
<strong>and</strong> increases plant productivity.<br />
2/10<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Design<br />
Different migration products are available for migration of<br />
APACS+ <strong>System</strong>s:<br />
PCS 7/APACS+ OS <strong>Engineering</strong> Pack<br />
for <strong>Engineering</strong> of the OS <strong>and</strong> for OS connection to APACS+<br />
<strong>and</strong>/or QUADLOG Controllers<br />
PCS 7/APACS+ ES Libraries option package<br />
for <strong>Engineering</strong> of the PCS 7 ES <strong>and</strong> OS using APACS+ style<br />
process automation templates (function blocks, symbols <strong>and</strong><br />
faceplates) for connection to SIMATIC S7 Controllers<br />
PCS 7/APACS+ OS software packages<br />
for Operation <strong>and</strong> Monitoring of APACS+ <strong>and</strong>/or QUADLOG<br />
Controllers using PCS 7 OS (single stations or client/server<br />
systems)<br />
PCS 7/APACS+ SIMATIC BATCH products for ES <strong>and</strong> OS<br />
for engineering, operation <strong>and</strong> control of Batch processes using<br />
SIMATIC BATCH connected to APACS+ Controllers
■ Design<br />
The following ES software products are available for migration to<br />
SIMATIC PCS 7 technology <strong>and</strong> can be applied to either Batch<br />
or Continuous applications:<br />
Required<br />
Software Products<br />
PCS 7/APACS+ OS<br />
<strong>Engineering</strong> Pack<br />
V6.0<br />
PCS 7/APACS+ ES<br />
Libraries V6.0<br />
PCS 7/APACS+<br />
SIMATIC BATCH DBA<br />
<strong>Engineering</strong> V6.0<br />
Batch Application Continuous Application<br />
APACS+ /QUADLOG<br />
Controller<br />
X X<br />
X<br />
AS 41x<br />
(S7-400<br />
Controller)<br />
X<br />
Migration to SIMATIC PCS 7<br />
Migration APACS+<br />
PCS 7/APACS+ ES Software<br />
PCS 7/APACS+ SIMATIC BATCH DBA <strong>Engineering</strong> V6.0 option<br />
package<br />
for <strong>Engineering</strong> of PCS 7 OS <strong>and</strong> SIMATIC BATCH to connect<br />
with APACS+ Controllers<br />
This optional package extends the PCS 7/APACS+ OS DBA software<br />
application so that it can populate the OS database with<br />
batch interface information <strong>and</strong> create the file that contains the<br />
process model information used by SIMATIC BATCH.<br />
Migration to SIMATIC BATCH enables you to take advantage of<br />
advanced features like:<br />
one time configuration of equipment information,<br />
easy graphical recipe creation,<br />
ability to define when to start <strong>and</strong> stop batch related continuous<br />
data collection, <strong>and</strong><br />
to define the execution order of batches by chaining the<br />
batches.<br />
PowerPacks <strong>and</strong> additional engineering software can be selected<br />
from the Section "ES software" of Chapter "<strong>Engineering</strong> ■ Selection <strong>and</strong> Ordering Data Order No.<br />
system".<br />
PCS 7/APACS+ OS <strong>Engineering</strong> 6EQ2 000-2EB06-3BA0 C)<br />
PCS 7/APACS+ OS <strong>Engineering</strong> Pack V6.0<br />
Pack V6.0<br />
RC 64K process variables, incl.<br />
for OS connection to APACS+ <strong>and</strong>/or QUADLOG Controllers 512 archive variables<br />
The software package consists of:<br />
Single license for 1 installation,<br />
English<br />
PCS 7 <strong>Engineering</strong> Software (64K variables, incl. 512 archive Electronic documentation on the<br />
variables)<br />
CD "PCS 7/APACS+ Options<br />
PCS 7/APACS+ OS DBA software application<br />
Version 6.0" <strong>and</strong> the PCS 7<br />
Toolset CDs<br />
Channel DLL for communication with APACS+/QUADLOG<br />
controllers<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> autho-<br />
The core component of PCS 7/APACS+ OS engineering is the rization diskette<br />
PCS 7/APACS+ OS DBA (Database <strong>Automation</strong>) software appli- PCS 7 Toolset CDs <strong>and</strong> additioncation.<br />
It automatically generates the OS database with the real CDs with Service Pack for Miquired<br />
variables, display hierarchies, specific block symbols<br />
<strong>and</strong> faceplates directly from the APACS+/QUADLOG controller.<br />
The display hierarchies are used to automatically create a navigation<br />
system for movement between process graphics within<br />
the operator station. PCS 7/APACS+ OS DBA automatically positions<br />
the type-specific block symbols, e.g. controllers or anacrosoft<br />
Windows 2000 (5<br />
languages), Microsoft Internet<br />
Explorer, Microsoft SQL Server<br />
2000 <strong>and</strong> PC Anywhere<br />
CD "PCS 7/APACS+ Options<br />
Version 6.0"<br />
log inputs (AI), in the generated process displays. These sym- PCS 7/APACS+ ES Libraries 6EQ2 000-1AX06-2BC0 C)<br />
bols are linked to the corresponding function blocks <strong>and</strong><br />
faceplates via the database. The manual configuration activities<br />
are basically limited to the design <strong>and</strong> positioning of static<br />
graphic elements, e.g. pipes or tanks.<br />
V6.0<br />
Single license for 1 installation,<br />
English<br />
Electronic documentation on the<br />
CD "PCS 7/APACS+ Options<br />
PCS 7/APACS+ ES Libraries V6.0 option package<br />
Version 6.0"<br />
for <strong>Engineering</strong> of the PCS 7 ES <strong>and</strong> OS using APACS+ style pro-<br />
Type of delivery:<br />
cess automation templates (function blocks, symbols <strong>and</strong> face- Certificate of license<br />
plates) for use in SIMATIC S7-400 Controllers (AS 41x)<br />
CD "PCS 7/APACS+ Options<br />
This option package for the PCS 7 engineering software includes:<br />
an ES library with preconfigured PID, motor <strong>and</strong> valve controllers<br />
for SIMATIC S7-400 controllers as well as<br />
Version 6.0"<br />
PCS 7/APACS+ SIMATIC BATCH<br />
DBA <strong>Engineering</strong> V6.0<br />
Single license for 1 installation,<br />
English<br />
6EQ2 000-5XX06-2BD0 C)<br />
corresponding block symbols <strong>and</strong> faceplates for the PCS 7 Type of delivery:<br />
operator system.<br />
Certificate of license <strong>and</strong> autho-<br />
This library is designed to copy the functionality of the APACS+<br />
rization diskette<br />
Basic Application Library allowing it to be used in AS 41x automation<br />
systems. Thus AS 41x automation systems can be operated<br />
<strong>and</strong> displayed as well as APACS+/QUADLOG controllers.<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/11<br />
12
12<br />
Migration to SIMATIC PCS 7<br />
Migration APACS+<br />
PCS 7/APACS+ OS Software<br />
■ Overview<br />
The PCS 7/APACS+ operator system is based on SIMATIC<br />
PCS 7 st<strong>and</strong>ard components: OS clients, OS servers,<br />
OS redundant servers, OS single stations <strong>and</strong> archive servers.<br />
The OS migration packages PCS 7/APACS+ OS are adapted to<br />
these system components <strong>and</strong> include not only the PCS 7 OS<br />
software for one OS single station, one OS server or two redundant<br />
servers but also the corresponding software for OS communication<br />
with the APACS+ automation systems through the<br />
MBI/MNET communication module.<br />
Similarly, in a batch application, the architecture will be augmented<br />
with batch clients, <strong>and</strong> batch servers. Batch clients may<br />
be on the same SIMATIC PCS 7 basic units as the OS clients or<br />
may be on separate basic units. Except for all-in-one systems,<br />
batch servers are usually on basic units separate from OS servers.<br />
SIMATIC BATCH servers always communicate to APACS+ controllers<br />
through PCS 7/APACS+ OS Servers. The PCS 7/APACS+<br />
SIMATIC BATCH Runtime license enables SIMATIC BATCH to<br />
exchange runtime information with an APACS+ controller<br />
through an OS server or OS single station via the<br />
APACS+/QUADLOG Communication Channel DLL. One license<br />
is needed for each OS server or OS single station that is used to<br />
exchange data with SIMATIC BATCH. For this reason, the<br />
PCS 7/APACS+ SIMATIC BATCH Runtime license is loaded on<br />
each OS server <strong>and</strong> OS single station. For architectures utilizing<br />
a OS single station, SIMATIC BATCH <strong>and</strong> PCS 7 OS must be executing<br />
on the same basic unit (all-in-one).<br />
2/12<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Design<br />
The following OS software packages are required depending<br />
on the configuration of a SIMATIC PCS 7 basic unit as a<br />
PCS 7/APACS+ OS Single Station, PCS 7/APACS+ OS Server<br />
(single or redundant) or PCS 7/APACS+ OS Client. The PCS<br />
7/APACS+ OS software packages for OS Servers <strong>and</strong> OS Single<br />
Stations include the channel dll for communicating with the<br />
APACS+ controllers (APACS <strong>and</strong> QUADLOG) through the<br />
MBI/MNET communications module. If SIMATIC BATCH is used,<br />
the PCS 7/APACS+ SIMATIC BATCH Runtime V6.0 option will<br />
also be needed on each PCS 7/APACS+ OS Server <strong>and</strong> PCS<br />
7/APACS+ OS Single Station that contains batch data.<br />
Required Software<br />
Packages<br />
Architecture<br />
PCS 7/ PCS 7/APACS+ PCS 7/<br />
APACS+ OS Server<br />
APACS+<br />
OS Single<br />
Station<br />
single redundant<br />
OS Client<br />
PCS 7/APACS+ OS<br />
Single Station Pack<br />
V6.0 (PO 2000/RT<br />
64K)<br />
1<br />
PCS 7/APACS+ OS<br />
Server Pack V6.0<br />
(PO 2000/RT 64K)<br />
PCS 7/APACS+ OS<br />
Redundant Server<br />
Pack V6.0 (PO<br />
2000/RT 64K)<br />
PCS 7 OS Client<br />
(see Section "OS<br />
software" in chapter<br />
"Operator system")<br />
Required for use<br />
with SIMATIC<br />
BATCH:<br />
PCS 7/APACS+<br />
SIMATIC BATCH<br />
Runtime license<br />
V6.0<br />
Power Packs <strong>and</strong> additional software for SIMATIC PCS 7 operator<br />
systems can be selected from the Section "OS software" of<br />
Chapter "Operator system".<br />
1<br />
1 1 2<br />
1<br />
1
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PCS 7/APACS+ OS Server Pack<br />
V6.0<br />
2000 PO/RT 64K process variables,<br />
incl. 512 archive variables<br />
Single license for 1 installation,<br />
English<br />
Electronic documentation on the<br />
CD "PCS 7/APACS+ Options<br />
Version 6.0" <strong>and</strong> the PCS 7<br />
Toolset CDs<br />
Type of delivery:<br />
Certificate of license <strong>and</strong> authorization<br />
diskette<br />
PCS 7 Toolset CDs <strong>and</strong> additional<br />
CDs with Service Pack for<br />
Microsoft Windows 2000<br />
(5 languages), Microsoft Internet<br />
Explorer, Microsoft SQL<br />
Server 2000 <strong>and</strong> PC Anywhere<br />
CD "PCS 7/APACS+ Options<br />
Version 6.0"<br />
6EQ2 000-2BB06-3BA0 C)<br />
PCS 7/APACS+ OS Redundant<br />
Server Pack V6.0<br />
2000 PO/RT 64K process variables,<br />
incl. 512 archive variables<br />
Single license for 2 installations,<br />
English, incl. WinCC/Redundancy<br />
<strong>and</strong> RS 232 connecting<br />
cable, 10 m<br />
Electronic documentation on the<br />
CD "PCS 7/APACS+ Options<br />
Version 6.0" <strong>and</strong> the PCS 7<br />
Toolset CDs<br />
Type of delivery:<br />
2 certificates of license <strong>and</strong><br />
2 authorization diskettes<br />
PCS 7 Toolset CDs <strong>and</strong> additional<br />
CDs with Service Pack for<br />
Microsoft Windows 2000 (5 languages),<br />
Microsoft Internet Explorer,<br />
Microsoft SQL Server<br />
2000 <strong>and</strong> PC Anywhere;<br />
WinCC/Redundancy incl. RS<br />
232 connecting cable, 10 m<br />
CD "PCS 7/APACS+ Options<br />
Version 6.0"<br />
6EQ2 000-2DB06-3BA0 C)<br />
Migration to SIMATIC PCS 7<br />
Migration APACS+<br />
PCS 7/APACS+ OS Software<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PCS 7/APACS+ OS Single Station<br />
Pack V6.0<br />
2000 PO/RT 64K process variables,<br />
incl. 512 archive variables<br />
Single license for 1 installation,<br />
English<br />
Electronic documentation on the<br />
CD "PCS 7/APACS+ Options<br />
Version 6.0" <strong>and</strong> the PCS 7<br />
Toolset CDs<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette<br />
PCS 7 Toolset CDs <strong>and</strong> additional<br />
CDs with Service Pack for<br />
Microsoft Windows 2000 (5 languages),<br />
Microsoft Internet Explorer,<br />
Microsoft SQL Server<br />
2000 <strong>and</strong> PC Anywhere<br />
CD "PCS 7/APACS+ Options<br />
Version 6.0"<br />
6EQ2 000-2AB06-3BA0 C)<br />
PCS 7/APACS+ SIMATIC BATCH<br />
Runtime license V6.0<br />
Single License for 1 installation,<br />
English<br />
Type of delivery:<br />
Certificate of license, authorization<br />
diskette<br />
6EQ2 000-6XX06-2BD0 C)<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/13<br />
12
12<br />
Migration to SIMATIC PCS 7<br />
Migration SIMATIC PCS/TISTAR<br />
Migration of SIMATIC PCS / TISTAR systems with<br />
505 controllers<br />
■ Overview<br />
Very many SIMATIC PCS / TISTAR systems are installed worldwide.<br />
These systems represent a wealth of hardware, user software<br />
<strong>and</strong> know-how accumulated by operating <strong>and</strong> maintenance<br />
personnel. To preserve the installed PCS/TISTAR<br />
platforms <strong>and</strong> add to their value, <strong>Siemens</strong> developed a migration<br />
strategy which aims to modernize existing operator <strong>and</strong> engineering<br />
systems whilst retaining the 505 controllers <strong>and</strong> the<br />
lower-lying I/O level. With this strategy the customer can migrate<br />
his existing system efficiently <strong>and</strong> economically without having<br />
to replace any controllers, I/O devices or their wiring, <strong>and</strong> without<br />
rendering the associated know-how useless.<br />
2/14<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
<strong>Siemens</strong> supplies the system platform for this migration strategy<br />
in the form of its innovative SIMATIC PCS 7 process control system.<br />
Through migration with SIMATIC PCS 7 <strong>Engineering</strong> <strong>and</strong> Operator<br />
<strong>System</strong>s it is possible to significantly increase the functionality<br />
<strong>and</strong> efficiency of process control systems based on<br />
505 controllers. And customers benefit in addition from continuous<br />
further development, long-term global support <strong>and</strong> the manifold<br />
advantages to be gained from TIA (Totally Integrated <strong>Automation</strong>)<br />
<strong>and</strong> SIMATIC IT. This protects existing investments,<br />
provides security for the future <strong>and</strong> increases plant productivity.
■ Overview<br />
A SIMATIC PCS 7 <strong>Engineering</strong> Station provided for the<br />
PCS 7/505 OS <strong>Engineering</strong> requires the following engineering<br />
software:<br />
Required software PCS 7/505 OS<br />
<strong>Engineering</strong> Station<br />
PCS 7/505 OS DBA x<br />
PCS 7/505 OS Server x<br />
PCS 7 <strong>Engineering</strong> Software OS<br />
x<br />
(see the chapter "ES Software" in the section<br />
"<strong>Engineering</strong> <strong>System</strong>")<br />
Additional engineering software for the installation on this <strong>Engineering</strong><br />
Station can be selected from the chapter "ES Software"<br />
in the section "<strong>Engineering</strong> <strong>System</strong>".<br />
A core component for the PCS 7/505 OS <strong>Engineering</strong> is the software<br />
application PCS 7/505 OS DBA (Database <strong>Automation</strong>).<br />
PCS 7/505 OS DBA automatically generates the OS database<br />
with the required variables, image hierarchies, specific block<br />
symbols <strong>and</strong> faceplates. The image hierarchy enables navigation<br />
between the process displays. PCS 7/505 OS DBA automatically<br />
places the type-specific block symbols, e.g. controller or<br />
analog input(AI), in the generated process displays. These symbols<br />
are linked to the corresponding function blocks <strong>and</strong> faceplates<br />
through the database. The manual configuration actions<br />
are mainly limited to the design <strong>and</strong> positioning of the of the<br />
static graphic elements, e.g. tubes or tanks.<br />
Migration to SIMATIC PCS 7<br />
Migration SIMATIC PCS/TISTAR<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S<br />
PCS 7/505 ES Software<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PCS 7/505 OS DBA V6.0<br />
Single license for 1 installation,<br />
English<br />
Electronic documentation on the<br />
CD "PCS 7/505 Options<br />
Version 6.0"<br />
Scope of delivery:<br />
License certificate <strong>and</strong> authorization<br />
diskette<br />
CD "PCS 7/505 Options<br />
Version 6.0"<br />
6EQ2 000-3EX06-2BC0 C)<br />
PCS 7/505 OS Server V6.0<br />
Single license for 1 installation,<br />
English<br />
Electronic documentation on the<br />
CD "PCS 7/505 Options<br />
Version 6.0"<br />
Scope of delivery:<br />
License certificate <strong>and</strong> authorization<br />
diskette<br />
CD "PCS 7/505 Options<br />
Version 6.0"<br />
6EQ2 000-3BX06-2BC0 C)<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
2/15<br />
12
12<br />
Migration to SIMATIC PCS 7<br />
Migration SIMATIC PCS/TISTAR<br />
PCS 7/505 OS Software<br />
■ Overview<br />
The PCS 7/505 operator system can be configured as a singleuser<br />
system (Single Station) or multi-user system with client/server<br />
architecture. SIMATIC PCS 7 support multi-user systems<br />
with up to 12 servers/redundant pairs of servers <strong>and</strong> up to<br />
32 clients.<br />
■ Design<br />
Depending on whether a SIMATIC PCS 7 basic device is configured<br />
as a PCS 7/505 OS Single Station, PCS 7/505 OS Server<br />
(single or redundant) or PCS 7/505 Client, the following OS software<br />
will be needed:<br />
Required software Architecture<br />
PCS 7/505 OS Single<br />
Station<br />
PCS 7 OS Single Station<br />
(see the chapter "OS<br />
Software" in the section<br />
"Operator <strong>System</strong>")<br />
The software components "PCS 7/505 OS Single Station”<br />
<strong>and</strong> “PCS 7/505 OS Server” are tailored for the respective<br />
system architecture <strong>and</strong> supply not only special block<br />
symbols <strong>and</strong> faceplates but also the functionality for communicating<br />
with the 505 controllers.<br />
2/16<br />
PCS 7/505<br />
OS<br />
Single<br />
Station<br />
1<br />
1<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
PCS 7/505 OS Server PCS 7/505<br />
Client<br />
single redundant<br />
PCS 7/505 OS Server 1 2<br />
PCS 7 OS Server<br />
(see the chapter "OS<br />
Software" in the section<br />
"Operator <strong>System</strong>")<br />
1<br />
PCS 7 OS Redundant<br />
Server<br />
(see the chapter "OS<br />
Redundance" in the<br />
section "Operator<br />
<strong>System</strong>")<br />
1<br />
PCS 7 OS Client<br />
(see the chapter "OS<br />
Software" in the section<br />
"Operator <strong>System</strong>")<br />
1<br />
■ Selection <strong>and</strong> Ordering Data Order No.<br />
PCS 7/505 OS Server V6.0<br />
Single license for 1 installation,<br />
English<br />
Electronic documentation on the<br />
CD "PCS 7/505 Options Version<br />
6.0"<br />
Scope of delivery:<br />
License certificate <strong>and</strong> authorization<br />
diskette<br />
CD "PCS 7/505 Options Version<br />
6.0"<br />
6EQ2 000-3BX06-2BC0 C)<br />
PCS 7/505 OS Single Station<br />
V6.0<br />
Single license for 1 installation,<br />
English<br />
Electronic documentation on the<br />
CD "PCS 7/505 Options Version<br />
6.0"<br />
Scope of delivery:<br />
License certificate <strong>and</strong> authorization<br />
diskette<br />
CD "PCS 7/505 Options Version<br />
6.0"<br />
6EQ2 000-3AX06-2BC0 C)<br />
C) Subject to export regulations: AL: N, ECCN: EAR99S
Appendix<br />
13/2 Training<br />
13/3 <strong>Siemens</strong> contacts worldwide<br />
13/4 Service & Support<br />
13/5 Customer Support<br />
13/7 <strong>Siemens</strong> <strong>Automation</strong><br />
Solution Provider<br />
13/8 Software Licenses<br />
13/9 Index<br />
13/10 Order no. index<br />
13/14 Conditions of sale <strong>and</strong> delivery<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
13<br />
Training<br />
13/2<br />
Appendix<br />
■ Training is decisive for your success<br />
SITRAIN ® Wide variety<br />
With a total of approx. 300 local attendance courses, we train the<br />
- the <strong>Siemens</strong> Training for <strong>Automation</strong> <strong>and</strong> Industrial complete range of A&D products <strong>and</strong> a large portion of the sys-<br />
Solutions - provides you with comprehensive support when solvtem solutions from I&S. Telecourses, teach-yourself software <strong>and</strong><br />
ing your tasks.<br />
seminars presented on the Web supplement our classical range<br />
Training by the market leader in automation, plant installation of courses.<br />
<strong>and</strong> support permits you to make your decisions with certainty Close to our customers<br />
<strong>and</strong> full comm<strong>and</strong>. Especially where the optimum <strong>and</strong> efficient<br />
use of products <strong>and</strong> plants are concerned. You can eliminate de- The distance is short. You can find us approx. 60 times in Gerficiencies<br />
in existing plants, <strong>and</strong> exclude expensive faulty planmany, <strong>and</strong> worldwide in 62 countries. You wish to have individual<br />
ning right from the beginning.<br />
training instead of one of our 300 courses? No problem: we will<br />
provide a program tailored exactly to your personal require-<br />
All in all, this represent an enormous gain for your company: ments. Training can be carried out in our Training Centers or at<br />
shortened startup times, optimized plant components, your company.<br />
faster troubleshooting, reduced down times. In other words,<br />
increased profits <strong>and</strong> lower costs.<br />
■ The right mixture: blended learning<br />
Blended learning is understood to be the combination of various<br />
training media <strong>and</strong> sequences. For example, a local attendance<br />
course in a Training Center can be optimally supplemented by a<br />
teach-yourself program as preparation or follow-up. Furthermore,<br />
SITRAIN utilizes supported online training for live instruction<br />
on the Internet at agreed times.<br />
The right mixture is the solution. Therefore blended learning<br />
can convey complex topics well, <strong>and</strong> train networked thinking.<br />
Additional effect: reduced travelling costs <strong>and</strong> periods<br />
of absence through training sequences independent of location<br />
<strong>and</strong> time.<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ The international training portal<br />
www.siemens.com/sitrain<br />
All training facilities at a glance: search in the worldwide range<br />
of courses at leisure, call up all course dates online, utilize the<br />
daily updated display of vacant course spaces - <strong>and</strong> register directly.<br />
Top trainers<br />
■ Customer comments on Sitrain<br />
" ... the good course documents, competence <strong>and</strong> flexibility convinced<br />
me."<br />
[Manfred Riek from Festo <strong>System</strong>technik, responsible for plan-<br />
Our trainers know their topics in practice, <strong>and</strong> possess comprening the basic <strong>and</strong> further training of project engineers]<br />
hensive didactic experience. Course developers have a direct<br />
wire to product development, <strong>and</strong> directly pass on their knowledge<br />
to the trainers.<br />
" ... represents effective training, constructive dialogs, <strong>and</strong> solutions<br />
which provide great help."<br />
[Günter Niedermaier, electrical design manager at AMT, Aalen]<br />
Practical experience<br />
The practical experience of our trainers makes it possible for ■ Contact<br />
them to pass on theoretical matter in a plausible manner. But<br />
since it is known that all theory is drab, we attach great importance<br />
to practical exercises which can comprise up to half of the<br />
Visit us on the Internet at:<br />
www.siemens.com/sitrain<br />
course time. You can therefore immediately implement your new<br />
knowledge in practice. We train you on state-of-the-art methodically/didactically<br />
designed training equipment. You feel abso-<br />
or let us advise you personally. You can request our latest training<br />
catalog from:<br />
lutely certain when trained in this manner.<br />
Course office, Infoline Germany:<br />
Tel.: 01805 / 23 56 11 (0.12 €/Min)<br />
Fax: 01805 / 23 56 12
At<br />
www.siemens.com/automation/partner<br />
Appendix<br />
<strong>Siemens</strong> contacts worldwide<br />
you can find details of <strong>Siemens</strong> contact partners worldwide responsible<br />
for particular technologies.<br />
You can obtain in most cases a contact partner for<br />
Technical Support,<br />
Spare parts/repairs,<br />
Service,<br />
Training,<br />
Sales or<br />
Consultation/engineering.<br />
You start by selecting a<br />
Country,<br />
Product or<br />
Sector.<br />
By further specifying the remaining criteria you will find exactly<br />
the right contact partner with his/her respective expertise.<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
13/3<br />
13
13<br />
Appendix<br />
Service & Support<br />
Information <strong>and</strong> Ordering<br />
in the Internet <strong>and</strong> on CD-ROM<br />
■ A&D in the WWW<br />
■ Product Selection Using the Interactive Catalog<br />
■ Easy Shopping with the A&D Mall<br />
13/4<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
A detailed knowledge of the range of products <strong>and</strong> services<br />
available is essential when planning <strong>and</strong> configuring automation<br />
systems. It goes without saying that this information must always<br />
be fully up-to-date.<br />
The <strong>Siemens</strong> <strong>Automation</strong> <strong>and</strong> <strong>Drives</strong> <strong>Group</strong> (A&D) has therefore<br />
built up a comprehensive range of information in the World Wide<br />
Web, which offers quick <strong>and</strong> easy access to all data required.<br />
Under the address<br />
http://www.siemens.com/automation<br />
you will find everything you need to know about products, systems<br />
<strong>and</strong> services.<br />
Detailed information together with convenient interactive functions:<br />
The interactive catalog CA 01 covers more than 80,000 products<br />
<strong>and</strong> thus provides a full summary of the <strong>Siemens</strong> <strong>Automation</strong><br />
<strong>and</strong> <strong>Drives</strong> product base.<br />
Here you will find everything that you need to solve tasks in the<br />
fields of automation, switchgear, installation <strong>and</strong> drives.<br />
All information is linked into a user interface which is easy to<br />
work with <strong>and</strong> intuitive.<br />
After selecting the product of your choice you can order at the<br />
press of a button, by fax or by online link.<br />
Information on the interactive catalog can be found in the Internet<br />
under<br />
http://www.siemens.com/automation/ca01<br />
or on CD-ROM:<br />
<strong>Automation</strong> & <strong>Drives</strong> CA 01,<br />
Order No.: E86060-D4001-A110-C2-7600<br />
The A&D Mall is the virtual department store of <strong>Siemens</strong> AG in<br />
the Internet. Here you have access to a huge range of products<br />
presented in electronic catalogs in an informative <strong>and</strong> attractive<br />
way.<br />
Data transfer via EDIFACT allows the whole procedure from selection<br />
through ordering to tracking of the order to be carried out<br />
online via the Internet.<br />
Numerous functions are available to support you.<br />
For example, powerful search functions make it easy to find the<br />
required products, which can be immediately checked for availability.<br />
Customer-specific discounts <strong>and</strong> preparation of quotes<br />
can be carried out online as well as order tracking <strong>and</strong> tracing.<br />
Please visit the A&D Mall on the Internet under:<br />
http://www.siemens.com/automation/mall
.I<br />
In the face of harsh competition you need optimum conditions to<br />
keep ahead all the time:<br />
A strong starting position. A sophisticated strategy <strong>and</strong> team for<br />
the necessary support - in every phase.<br />
Service & Support from <strong>Siemens</strong> provides this support with a<br />
complete range of different services for automation <strong>and</strong> drives.<br />
In every phase: from planning <strong>and</strong> startup to maintenance <strong>and</strong><br />
upgrading.<br />
Our specialists know when <strong>and</strong> where to act to keep the productivity<br />
<strong>and</strong> cost-effectiveness of your system running in top form.<br />
■ Online Support<br />
■ Technical Support<br />
■ Technical Consulting<br />
The comprehensive information<br />
system available round the<br />
clock via Internet ranging from<br />
Product Support <strong>and</strong> Service &<br />
Support services to Support<br />
Tools in the Shop.<br />
http://www.siemens.com/<br />
automation/service&support<br />
Competent consulting in technical<br />
questions covering a wide<br />
range of customer-oriented services<br />
for all our products <strong>and</strong><br />
systems.<br />
Tel.: +49 (0)180 50 50 222<br />
Fax: +49 (0)180 50 50 223<br />
E-Mail:<br />
adsupport@siemens.com<br />
Support in the planning <strong>and</strong> designing<br />
of your project from detailed<br />
actual-state analysis,<br />
target definition <strong>and</strong> consulting<br />
on product <strong>and</strong> system questions<br />
right to the creation of the<br />
automation solution. 1 )<br />
Appendix<br />
Customer Support<br />
Our Services for Every Phase of Your Project<br />
■ Configuration <strong>and</strong> Software <strong>Engineering</strong><br />
Support in configuring <strong>and</strong> developing<br />
with customer-oriented<br />
services from actual configuration<br />
to implementation of the automation<br />
project. 1 )<br />
■ Service On Site<br />
■ Repairs <strong>and</strong> Spare Parts<br />
■ Optimization <strong>and</strong> Upgrading<br />
With Service On Site we offer<br />
services for startup <strong>and</strong> maintenance,<br />
essential for ensuring<br />
system availability.<br />
In Germany<br />
0180 50 50 444 1 )<br />
In the operating phase of a machine<br />
or automation system we<br />
provide a comprehensive repair<br />
<strong>and</strong> spare parts service ensuring<br />
the highest degree of operating<br />
safety <strong>and</strong> reliability.<br />
In Germany<br />
0180 50 50 448 1 )<br />
To enhance productivity <strong>and</strong><br />
save costs in your project we offer<br />
high-quality services in optimization<br />
<strong>and</strong> upgrading. 1 )<br />
1) For country-specific telephone numbers go to our Internet site at:<br />
http://www.siemens.com/automation/service&support<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
13/5<br />
13
13<br />
Appendix<br />
Customer Support<br />
■ Knowledge Base on CD-ROM<br />
For locations without online connections<br />
to the Internet there are<br />
excerpts of the free part of the<br />
information sources available on<br />
CD-ROM (Service & Support<br />
Knowledge Base). This CD-<br />
ROM contains all the latest<br />
product information at the time<br />
of production (FAQs, Downloads,<br />
Tips <strong>and</strong> Tricks, Updates)<br />
as well as general information<br />
on Service <strong>and</strong> Technical Support.<br />
■ <strong>Automation</strong> Value Card<br />
Small card - great support<br />
The <strong>Automation</strong> Value Card is an integral component of the comprehensive<br />
service concept with which <strong>Siemens</strong> <strong>Automation</strong> <strong>and</strong><br />
<strong>Drives</strong> will accompany you in each phase of your automation<br />
project.<br />
It doesn't matter whether you want just specific services from our<br />
Technical Support or want to purchase high-quality Support<br />
Tools in our Online Shop, you can always pay with your <strong>Automation</strong><br />
Value Card. No invoicing, transparent <strong>and</strong> safe. With your<br />
personal card number <strong>and</strong> associated PIN you can view the<br />
state of your account <strong>and</strong> all transactions at any time.<br />
Services on card. This is how it's done.<br />
Card number <strong>and</strong> PIN are on the back of the <strong>Automation</strong> Value<br />
Card. When delivered, the PIN is covered by a scratch field,<br />
guaranteeing that the full credit is on the card.<br />
13/6<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
The CD-ROM also includes a full-text search <strong>and</strong> our Knowledge<br />
Manager for targeted searches for solutions. The CD-ROM will<br />
be updated every 4 months.<br />
Just the same as our online offer in the Internet, the Service &<br />
Support Knowledge Base on CD comes complete in 5 languages<br />
(German, English, French, Italian, Spanish).<br />
You can order the Service & Support Knowledge Base CD<br />
from your <strong>Siemens</strong> contact.<br />
Order no. 6ZB5310-0EP30-0BA2<br />
Orders via the Internet<br />
(with <strong>Automation</strong> Value Card or credit card) at:<br />
http://www.siemens.com/automation/service&support<br />
in the Shop domain.<br />
By entering the card number <strong>and</strong> PIN you have full access to the<br />
Service & Support services being offered. The charge for the<br />
services procured is debited from the credits on your <strong>Automation</strong><br />
Value Card.<br />
All the services offered are marked in currency-neutral credits,<br />
so you can use the <strong>Automation</strong> Value Card worldwide.<br />
<strong>Automation</strong> Value Card order numbers<br />
Credits Order no.<br />
200 6ES7 997-0BA00-0XA0<br />
500 6ES7 997-0BB00-0XA0<br />
1000 6ES7 997-0BC00-0XA0<br />
10000 6ES7 997-0BG00-0XA0<br />
Detailed information on the services offered is available on our<br />
Internet site at:<br />
http://www.siemens.com/automation/service&support<br />
Service & Support à la Card: Examples<br />
Technical Support<br />
”Priority“ Priority processing for urgent cases<br />
”24 h“ Availability round the clock<br />
„Extended“ Technical consulting for complex questions<br />
Support Tools in the Support Shop<br />
”<strong>System</strong> Utili- Tools that can be used directly for configuration, analties“ysis<br />
<strong>and</strong> testing<br />
”Applications“ Complete topic solutions including ready-tested software<br />
”Functions & Adaptable blocks for accelerating your developments<br />
Samples“
■ <strong>Siemens</strong> <strong>Automation</strong> Solution Provider<br />
<strong>Automation</strong> solutions are becoming increasingly complex, <strong>and</strong><br />
dem<strong>and</strong>s are permanently growing. We can help you find competent<br />
partners for an excellent, reliable solution. Partners who<br />
have competence <strong>and</strong> experience in the required sector linked<br />
with comprehensive know-how for automation solutions.<br />
Our partner programs set new st<strong>and</strong>ards with respect to the specific<br />
competence of the companies involved <strong>and</strong> the global network<br />
of partners. As a result of the careful selection <strong>and</strong> permanent<br />
training of our solution providers, you will always be able to<br />
find a competent partner close at h<strong>and</strong> who is always working<br />
with state-of-the-art technology.<br />
The program<br />
You are searching for automation solutions for a particular task?<br />
Or you require professional consulting <strong>and</strong> support? You wish to<br />
contact specialists in your sector? You wish to secure market advantages?<br />
Then our <strong>Siemens</strong> automation solution providers are<br />
the right partners for you!<br />
Our partner companies possess the know-how for developing<br />
reliable, economic <strong>and</strong> future-oriented solutions – for all sectors<br />
<strong>and</strong> all automation components: covering all SIMATIC components,<br />
visualization systems, communi-cations networks using<br />
SIMATIC PCS 7, microsystems <strong>and</strong> motion control systems up to<br />
products for vertical integration of industrial automation <strong>and</strong> office<br />
environments.<br />
Appendix<br />
<strong>Siemens</strong> <strong>Automation</strong> Solution Provider<br />
Your benefits<br />
Customized, economic <strong>and</strong> future-oriented solutions<br />
Significant advantages with respect to speed, efficiency <strong>and</strong><br />
locality<br />
Solution provider has special knowledge of sector<br />
Guaranteed state-of-the-art technology <strong>and</strong> knowledge of latest<br />
developments<br />
Certification<br />
The solution providers are continuously being trained in order to<br />
remain completely up-to-date. They are subjected to a special<br />
certification program where they have to prove their high competence<br />
using <strong>Siemens</strong>’ automation tools. We can therefore<br />
guarantee a special st<strong>and</strong>ard of quality which is successively<br />
achieved by training on new components <strong>and</strong> during special solution<br />
provider workshops.<br />
Internet:<br />
www.siemens.com/automation/solution-provider<br />
E-Mail:<br />
SSPinfo@nbgm.siemens.de<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
13/7<br />
13
13<br />
Appendix<br />
Software Licenses<br />
■ Overview<br />
Software types<br />
Software requiring a license is categorized into types.<br />
The following software types have been defined:<br />
<strong>Engineering</strong> software<br />
Runtime software<br />
<strong>Engineering</strong> software<br />
This includes all software products for creating (engineering)<br />
user software, e.g. for configuring, programming, parameterizing,<br />
testing, commissioning or servicing.<br />
Data generated with engineering software <strong>and</strong> executable<br />
programs can be duplicated for your own use or for use by thirdparties<br />
free-of-charge.<br />
Runtime software<br />
This includes all software products required for plant/machine<br />
operation, e.g. operating system, basic system, system expansions,<br />
drivers, etc.<br />
The duplication of the runtime software <strong>and</strong> executable programs<br />
created with the runtime software for your own use or for<br />
use by third-parties is subject to a charge.<br />
You can find information about license fees according to use in<br />
the ordering data (e.g. in the catalog). Examples of categories of<br />
use include per CPU, per installation, per channel, per instance,<br />
per axis, per control loop, per variable, etc.<br />
Information about extended rights of use for parameterization/configuration<br />
tools supplied as integral components of the<br />
scope of delivery can be found in the readme file supplied with<br />
the relevant product(s).<br />
License types<br />
<strong>Siemens</strong> <strong>Automation</strong> & <strong>Drives</strong> offers various types of software<br />
license:<br />
Floating license<br />
Single license<br />
Rental license<br />
Trial license<br />
Floating license<br />
The software may be installed for internal use on any number of<br />
devices by the licensee. Only the concurrent user is licensed.<br />
The concurrent user is the person using the program. Use begins<br />
when the software is started.<br />
A license is required for each concurrent user.<br />
Single license<br />
Unlike the floating license, a single license permits only one<br />
installation of the software.<br />
The type of use licensed is specified in the ordering data <strong>and</strong><br />
in the Certificate of License (CoL). Types of use include for<br />
example per device, per axis, per channel, etc.<br />
One single license is required for each type of use defined.<br />
Rental license<br />
A rental license supports the "sporadic use" of engineering<br />
software. Once the license key has been installed, the software<br />
can be used for a specific number of hours (the operating hours<br />
do not have to be consecutive).<br />
One license is required for each installation of the software.<br />
Trial license<br />
A trial license supports "short-term use" of the software in a nonproductive<br />
context, e.g. for testing <strong>and</strong> evaluation purposes.<br />
It can be transferred to another license.<br />
13/8<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Certificate of license<br />
The Certificate of License (CoL) is the licensee's proof that the<br />
use of the software has been licensed by <strong>Siemens</strong>. A CoL is<br />
required for every type of use <strong>and</strong> must be kept in a safe place.<br />
Downgrading<br />
The licensee is permitted to use the software or an earlier version/release<br />
of the software, provided that the licensee owns<br />
such a version/release <strong>and</strong> its use is technically feasible.<br />
Delivery versions<br />
Software is constantly being updated.<br />
The following delivery versions<br />
PowerPack<br />
Upgrade<br />
can be used to access updates.<br />
Existing bug fixes are supplied with the ServicePack version.<br />
PowerPack<br />
PowerPacks can be used to upgrade to more powerful software.<br />
The licensee receives a new license agreement <strong>and</strong> CoL<br />
(Certificate of License) with the PowerPack. This CoL, together<br />
with the CoL for the original product, proves that the new software<br />
is licensed.<br />
A separate PowerPack must be purchased for each original<br />
license of the software to be replaced.<br />
Upgrade<br />
An upgrade permits the use of a new version of the software on<br />
the condition that a license for a previous version of the product<br />
is already held.<br />
The licensee receives a new license agreement <strong>and</strong> CoL with<br />
the upgrade. This CoL, together with the CoL for the previous<br />
product, proves that the new version is licensed.<br />
A separate upgrade must be purchased for each original license<br />
of the software to be upgraded.<br />
ServicePack<br />
ServicePacks are used to debug existing products.<br />
ServicePacks may be duplicated for use as prescribed according<br />
to the number of existing original licenses.<br />
License key<br />
<strong>Siemens</strong> <strong>Automation</strong> & <strong>Drives</strong> supplies software products with<br />
<strong>and</strong> without license keys.<br />
The license key serves as an electronic license stamp <strong>and</strong><br />
is also the "switch" for activating the software (floating license,<br />
rental license, etc.).<br />
The complete installation of software products requiring license<br />
keys includes the program to be licensed (the software) <strong>and</strong> the<br />
license key (which represents the license).<br />
Detailed explanations concerning license conditions can be<br />
found in the “Terms <strong>and</strong> Conditions of <strong>Siemens</strong> AG” or under<br />
http://www.siemens.com/automation/mall<br />
(A&D Mall Online-Help <strong>System</strong>)
■<br />
@<br />
@PCS 7 .............................................................8/3<br />
A<br />
Administration ...................................................2/3<br />
Alarms...............................................................5/9<br />
APACS+ ........................................................12/10<br />
Archive server..........................................5/4, 5/11<br />
AS-Interface ....................................................9/19<br />
AS migration from TELEPERM M ....................12/8<br />
<strong>Automation</strong> systems........................................10/2<br />
B<br />
Basic hardware ..........................................2/6, 4/3<br />
Batch Control Center ........................................6/6<br />
Batch Planning..................................................6/8<br />
Batch automation..............................................6/2<br />
Branch & Merge................................................4/6<br />
C<br />
Central I/O modules........................................11/3<br />
CFC...................................................................4/6<br />
Chip card reader...............................................2/3<br />
Client/server architecture..................................5/4<br />
Communications module ..................................9/8<br />
Connectivity Pack ...........................................5/14<br />
Contacts..........................................................13/3<br />
Controller modules........................................11/19<br />
Controller optimization ....................................4/20<br />
Counter modules ..........................................11/20<br />
Coupling package PCS 7/TM-OS ...................12/4<br />
CP 1612 ............................................................9/8<br />
CP 1613 ............................................................9/8<br />
CP 341 ............................................................9/21<br />
CP 443-1 ................................................10/5, 10/8<br />
CP 443-5 .......................................9/13, 10/5, 10/8<br />
Customer Support...........................................13/6<br />
D<br />
DOCPRO...........................................................4/6<br />
Documentation..................................................2/2<br />
DP/PA Coupler ................................................9/16<br />
E<br />
EDD.................................................................4/16<br />
EIB instabus....................................................9/20<br />
Electrical Switch Module...................................9/5<br />
Electronic signature ..........................................2/3<br />
Electronic modules .......................................11/29<br />
<strong>Engineering</strong> <strong>System</strong>..........................................4/2<br />
ES software .......................................................4/4<br />
ET 200iS........................................................11/21<br />
ET 200M..........................................................11/5<br />
ET 200S.........................................................11/24<br />
Ex zone ................................................11/2, 11/15<br />
Expansion devices..........................................11/4<br />
F<br />
F modules .....................................................11/17<br />
F systems........................................................10/9<br />
Faceplate Designer ..........................................4/6<br />
Failsafe automation systems...........................10/9<br />
Fast Ethernet.....................................................9/4<br />
FastConnect.............................................9/7, 9/18<br />
Fault-tolerant automation systems ..................10/6<br />
Fiber optic cable.............................................9/11<br />
G<br />
Graphics Designer ........................................... 4/6<br />
H<br />
H systems................................................ 4/8, 10/6<br />
HART ............................................................ 11/16<br />
Hierarchical Recipe.......................................... 6/9<br />
Horizontal integration ....................................... 1/8<br />
Hot swapping ................................................. 9/16<br />
I<br />
Image & Partition Creator................................. 2/8<br />
Import/export assistant..................................... 4/9<br />
Industrial Ethernet ............................................ 9/3<br />
L<br />
Libraries ........................................................... 4/5<br />
M<br />
Measuring point ............................................... 5/3<br />
Messages......................................................... 5/9<br />
Modbus .......................................................... 9/21<br />
Motor starter ................................................. 11/31<br />
Multi-client ........................................................ 5/4<br />
Multi-VGA graphics card................................ 2/10<br />
N<br />
NORA ............................................................. 12/5<br />
O<br />
Operator <strong>System</strong> .............................................. 5/2<br />
Optical Switch Module ..................................... 9/4<br />
OS Variable ...................................................... 5/3<br />
OS migration from TELEPERM M ................... 12/4<br />
OS redundancy .............................................. 5/15<br />
OS software...................................................... 5/8<br />
P<br />
PCS 7/505 .................................................... 12/14<br />
PCS 7/TM-OS ................................................. 12/4<br />
PID Tuner........................................................ 4/20<br />
Plant Hierarchy................................................. 4/5<br />
Plant view ......................................................... 4/5<br />
PO .................................................................... 5/3<br />
Process monitor.............................................. 2/11<br />
Process objekt (PO) ......................................... 5/3<br />
Process objekt view.......................................... 4/5<br />
PROFIBUS........................................................ 9/9<br />
R<br />
Recipe <strong>System</strong> ................................................. 6/7<br />
Redundancy................................................... 5/15<br />
ROP Library...................................................... 6/9<br />
Route Control ................................................. 4/14<br />
RS485-iS.............................................. 9/10, 11/23<br />
Appendix<br />
<strong>Siemens</strong> ST PCS 7 · November 2004<br />
Index<br />
S<br />
S7 F <strong>System</strong>s ..................................................4/11<br />
S7-300 modules...........................................11/9 ff<br />
S7-400 modules..............................................11/3<br />
S7-PLCSIM .....................................................4/20<br />
Safety Matrix ...................................................4/12<br />
Safety Matrix Viewer .......................................5/13<br />
SFC ...................................................................4/6<br />
SFC visualization ............................................5/13<br />
Signal module...................................................5/7<br />
Sign-of-life monitoring.......................................5/9<br />
SIGUARD......................................................11/33<br />
SIMATIC BATCH ...............................................6/2<br />
SIMATIC IT ........................................................8/2<br />
SIMATIC Logon.................................................2/3<br />
SIMATIC Manager.............................................4/5<br />
SIMATIC NET ....................................................9/2<br />
SIMATIC PCS ................................................12/14<br />
SIMATIC PCS 7 BOX.........................................3/2<br />
SIMATIC PDM .................................................4/15<br />
SIMATIC Route Control ............................4/14, 7/2<br />
SIMATIC Safety Matrix ...........................4/12, 5/13<br />
Simulation .......................................................4/20<br />
Solution Provider.............................................13/7<br />
SpliTConnect ..................................................9/18<br />
StoragePlus ....................................................5/12<br />
<strong>System</strong> architecture ..........................................1/8<br />
T<br />
TELEPERM M..................................................12/2<br />
TELEPERM M Manual Collection......................2/2<br />
Terminal modules..........................................11/26<br />
Time synchronization........................................5/9<br />
TISTAR ..........................................................12/14<br />
Totally Integrated <strong>Automation</strong> (TIA) ...........1/4, 1/8<br />
Training ...........................................................13/2<br />
V<br />
Version Cross Checker .....................................4/8<br />
Vertical integration ............................................1/8<br />
Y<br />
Y-link ...............................................................9/14<br />
13/9<br />
13
13<br />
Appendix<br />
Order no. index<br />
■<br />
3RK1 301-0AB10-.... ............................... 11/31<br />
3RK1 301-0AB13-.... ............................... 11/32<br />
3RK1 301-0AB20-.... ............................... 11/31<br />
3RK1 301-0BB10-.... ............................... 11/31<br />
3RK1 301-0BB13-.... ............................... 11/32<br />
3RK1 301-0BB20-.... ............................... 11/31<br />
3RK1 301-0CB10-................................... 11/31<br />
3RK1 301-0CB13-................................... 11/32<br />
3RK1 301-0CB20-................................... 11/31<br />
3RK1 903-0A........................................... 11/31<br />
3RK1 903-0B........................................... 11/28<br />
3RK1 903-0CB.. ...................................... 11/31<br />
3RK1 903-0CC........................................ 11/31<br />
3RK1 903-0CE.. ........................... 11/31, 11/32<br />
3RK1 903-0CF.............................. 11/31, 11/32<br />
3RK1 903-0CH........................................ 11/31<br />
3RK1 903-1.... ......................................... 11/34<br />
3RK1 903-2.... .............................. 11/31, 11/32<br />
3RK1 903-3A........................................... 11/32<br />
3RK1 903-3B........................................... 11/28<br />
3RK1 903-3C... ....................................... 11/28<br />
3RK1 903-3D... ....................................... 11/28<br />
6AG1 321-1............................................... 11/9<br />
6AG1 321-7............................................. 11/10<br />
6AG1 322-1............................................. 11/11<br />
6AG1 322-8............................................. 11/12<br />
6AG1 323-1.................................... 11/9, 11/11<br />
6AG1 331-7............................................. 11/13<br />
6AG1 332-5............................................. 11/14<br />
6AV3 617-1JC20-0AX1 ........................... 11/20<br />
6AV6 371-1C............................................. 5/16<br />
6AV6 371-1D............................................. 5/14<br />
6AV6 371-1E... .......................................... 5/14<br />
6AV6 392-1D............................................. 5/16<br />
6AV8 101-..... ............................................ 2/11<br />
6DL2 100-..... ............................................ 12/9<br />
6DL2 207-... .............................................. 12/6<br />
6DL2 804-..... .......................................... 11/21<br />
6DL5 200-..... ............................................ 12/7<br />
6DL5 900-..... .............................................. 2/2<br />
6DS1 916-... ................................................ 5/7<br />
6DS5 ... ..................................................... 12/7<br />
6EP1 ... ....................................................... 3/4<br />
6EQ2 000-1A... ....................................... 12/11<br />
6EQ2 000-2A... ....................................... 12/13<br />
6EQ2 000-2B... ....................................... 12/13<br />
6EQ2 000-2D... ....................................... 12/13<br />
6EQ2 000-2E........................................... 12/11<br />
6EQ2 000-3A... ....................................... 12/16<br />
6EQ2 000-3B... ............................ 12/15, 12/16<br />
6EQ2 000-3E........................................... 12/15<br />
6EQ2 000-5X........................................... 12/11<br />
6EQ2 000-6X........................................... 12/13<br />
6ES7 131-4.... ......................................... 11/29<br />
6ES7 131-5.... ......................................... 11/22<br />
6ES7 132-4.... ......................................... 11/29<br />
6ES7 132-5.... ......................................... 11/22<br />
6ES7 134-4.... ......................................... 11/30<br />
6ES7 134-5.... ......................................... 11/22<br />
6ES7 135-4.... ......................................... 11/30<br />
6ES7 135-5.... ......................................... 11/22<br />
6ES7 138-4C........................................... 11/28<br />
6ES7 138-4F............................................ 11/29<br />
6ES7 138-5E... ........................................ 11/23<br />
6ES7 151-1.... ......................................... 11/28<br />
6ES7 151-2.... ......................................... 11/23<br />
6ES7 153-2A... .......................................... 11/8<br />
6ES7 153-2B... .......................................... 11/6<br />
6ES7 157-0.... ........................................... 9/17<br />
13/10<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
6ES7 193-4CA......................................... 11/27<br />
6ES7 193-4CB......................................... 11/27<br />
6ES7 193-4CC......................................... 11/26<br />
6ES7 193-4CD......................................... 11/26<br />
6ES7 193-4CE.. ....................................... 11/26<br />
6ES7 193-4CF.......................................... 11/27<br />
6ES7 193-4CG.. ...................................... 11/27<br />
6ES7 193-4CK......................................... 11/26<br />
6ES7 193-4CL.. ....................................... 11/27<br />
6ES7 193-5C... ........................................ 11/22<br />
6ES7 193-5D... ........................................ 11/23<br />
6ES7 195-1B... .......................................... 9/12<br />
6ES7 195-1G... ................................. 9/17, 11/7<br />
6ES7 195-1J... ........................................... 11/7<br />
6ES7 195-1K... .......................................... 11/7<br />
6ES7 195-7HA........................................... 11/7<br />
6ES7 195-7HB........................................... 11/7<br />
6ES7 195-7HC........................................... 11/7<br />
6ES7 195-7HD10-.... ................................. 11/7<br />
6ES7 195-7HD80-.... ................................. 9/17<br />
6ES7 195-7HF80-.... .................................. 9/17<br />
6ES7 195-7HG00-.... ............................... 11/17<br />
6ES7 195-7KF00-.... ................................ 11/17<br />
6ES7 197-......................................... 9/14, 10/8<br />
6ES7 305-................................ 9/14, 9/17, 11/6<br />
6ES7 307-................................ 9/14, 9/17, 11/6<br />
6ES7 321-1................................................ 11/9<br />
6ES7 321-7B... ........................................ 11/10<br />
6ES7 321-7R... ........................................ 11/15<br />
6ES7 321-7T... ......................................... 11/10<br />
6ES7 322-1.............................................. 11/11<br />
6ES7 322-5F... ......................................... 11/12<br />
6ES7 322-5G... ........................................ 11/12<br />
6ES7 322-5H... ........................................ 11/12<br />
6ES7 322-5R... ........................................ 11/15<br />
6ES7 322-5S............................................ 11/15<br />
6ES7 322-8B... ........................................ 11/12<br />
6ES7 326-................................................ 11/17<br />
6ES7 331-1K... ........................................ 11/13<br />
6ES7 331-7K... ........................................ 11/13<br />
6ES7 331-7N... ........................................ 11/13<br />
6ES7 331-7P... ......................................... 11/13<br />
6ES7 331-7R... ........................................ 11/15<br />
6ES7 331-7S............................................ 11/15<br />
6ES7 331-7T... ......................................... 11/16<br />
6ES7 332-5H... ........................................ 11/14<br />
6ES7 332-5R... ........................................ 11/15<br />
6ES7 332-5T... ......................................... 11/16<br />
6ES7 332-7N... ........................................ 11/14<br />
6ES7 336-1H... ........................................ 11/17<br />
6ES7 341-.................................................. 9/21<br />
6ES7 350-................................................ 11/20<br />
6ES7 355-................................................ 11/20<br />
6ES7 390-.................................................. 9/17<br />
6ES7 392-1AJ00-.... ......................... 9/19, 11/7<br />
6ES7 392-1AJ20-.... .................................. 11/7<br />
6ES7 392-1AM.. ........................................ 11/7<br />
6ES7 392-1B... .......................................... 11/7<br />
6ES7 393-4A... .......................................... 11/7<br />
6ES7 400-1.............................. 10/5, 10/8, 11/4<br />
6ES7 400-2................................................ 10/8<br />
6ES7 405-0KA.. ................................ 10/5, 10/8<br />
6ES7 405-0KR.. ......................................... 10/5<br />
6ES7 405-0RA.. ......................................... 10/5<br />
6ES7 407-0KA.. ......................................... 10/5<br />
6ES7 407-0KR.. ................................ 10/5, 10/8<br />
6ES7 407-0RA.. ......................................... 10/5<br />
6ES7 414-3................................................ 10/5<br />
6ES7 414-4................................................ 10/8<br />
6ES7 416-.................................................. 10/5<br />
6ES7 417-4H... .......................................... 10/8<br />
6ES7 417-4X.............................................. 10/5<br />
6ES7 421-..... .............................................11/3<br />
6ES7 422-..... .............................................11/3<br />
6ES7 431-..... .............................................11/3<br />
6ES7 432-..... .............................................11/3<br />
6ES7 460-..... .............................................11/4<br />
6ES7 461-..... .............................................11/4<br />
6ES7 468-..... .............................................11/4<br />
6ES7 478-..... .............................................12/9<br />
6ES7 492-..... .............................................11/3<br />
6ES7 648-0C.............2/9, 3/4, 4/3, 5/6, 6/4, 7/4<br />
6ES7 648-2A....................2/9, 4/3, 5/6, 6/4, 7/4<br />
6ES7 648-6A....................2/9, 4/3, 5/6, 6/4, 7/4<br />
6ES7 650-0GC06-....2/9, 4/3, 5/5, 6/4, 7/3, 12/6<br />
6ES7 650-0GC16-............2/9, 4/3, 5/5, 6/4, 7/3<br />
6ES7 650-0GD06-..........2/9, 5/6, 6/4 ,7/4, 12/6<br />
6ES7 650-0GE06-.... ...............2/9, 5/5, 6/4, 7/4<br />
6ES7 650-0GE16-.... ......................2/9, 5/5, 7/4<br />
6ES7 650-0XX06-0..........................11/8, 11/16<br />
6ES7 650-0XX06-8.......................................2/2<br />
6ES7 650-2H................................................3/4<br />
6ES7 652-0XC.. .........................................5/12<br />
6ES7 652-0XD.. .........................................5/13<br />
6ES7 652-0XX01-.........................................2/3<br />
6ES7 652-0XX03-...........2/10, 4/3, 5/6, 6/4, 7/4<br />
6ES7 652-0XX05-.........................................2/3<br />
6ES7 652-3.... ............................................5/16<br />
6ES7 653-0.... ............................................4/20<br />
6ES7 653-1.... ..............................................2/2<br />
6ES7 653-2.... ...................................10/5, 10/8<br />
6ES7 654-0.... ............................................11/8<br />
6ES7 654-1.... ............................................10/4<br />
6ES7 654-2.... ............................................10/7<br />
6ES7 654-3.... ............................................10/4<br />
6ES7 654-4.... ............................................10/4<br />
6ES7 654-5.... ............................................10/7<br />
6ES7 654-6.... ............................................10/4<br />
6ES7 657-0A................................................6/7<br />
6ES7 657-0B................................................6/8<br />
6ES7 657-0F.................................................6/9<br />
6ES7 657-0G... ............................................6/9<br />
6ES7 657-0H..............................................6/10<br />
6ES7 657-0L... .............................................6/6<br />
6ES7 657-0M... ..........................................6/10<br />
6ES7 657-0S.... ............................................6/5<br />
6ES7 657-0XB..............................................6/5<br />
6ES7 657-0XC.. ...........................................6/5<br />
6ES7 657-0XD.. ...........................................6/5<br />
6ES7 657-0XE..............................................6/5<br />
6ES7 657-0XX............................................6/10<br />
6ES7 658-0.... ..............................................8/4<br />
6ES7 658-1A................................................4/7<br />
6ES7 658-1C................................................4/8<br />
6ES7 658-1D................................................4/9<br />
6ES7 658-2AA.. .........................................5/10<br />
6ES7 658-2AB06-0YA0..............................5/10<br />
6ES7 658-2AB06-0YD0 ......................3/4, 5/10<br />
6ES7 658-2AB06-0YE0..............................5/10<br />
6ES7 658-2AC.. .........................................5/10<br />
6ES7 658-2AD.. .........................................5/10<br />
6ES7 658-2BA.. ................................5/10, 5/11<br />
6ES7 658-2BB.. .........................................5/10<br />
6ES7 658-2BC.. .........................................5/10<br />
6ES7 658-2BD.. .........................................5/10<br />
6ES7 658-2BE............................................5/10<br />
6ES7 658-2CX.. .........................................5/10
■<br />
6ES7 658-2D............................................... 4/7<br />
6ES7 658-2E... .......................................... 5/11<br />
6ES7 658-3AX05-0YC0............................. 4/19<br />
6ES7 658-3AX05-0YC3.................... 4/17, 4/19<br />
6ES7 658-3BX00-2XD0............................. 4/19<br />
6ES7 658-3CX00-2XD0............................. 4/19<br />
6ES7 658-3EX00-2XD0 .................... 4/17, 4/19<br />
6ES7 658-3GX05-0YC8 ................... 4/17, 4/19<br />
6ES7 658-3PX05-0YC0 ...................... 3/4, 4/17<br />
6ES7 658-3XA00-2XD0............................. 4/19<br />
6ES7 658-3XB00-2XD0............................. 4/19<br />
6ES7 658-3XB05-2XD5.................... 4/17, 4/19<br />
6ES7 658-3XC00-2XD0............................. 4/19<br />
6ES7 658-3XC05-2XD5.................... 4/17, 4/19<br />
6ES7 658-3XD00-2XD0............................. 4/19<br />
6ES7 658-3XD05-2XD5.................... 4/17, 4/19<br />
6ES7 658-3XH.................................. 4/17, 4/19<br />
6ES7 658-4XX.. ........................................... 2/4<br />
6ES7 658-5AA............................................. 4/7<br />
6ES7 658-5AB06-0YA0 ............................... 4/7<br />
6ES7 658-5AB06-0YD0........................ 3/4, 4/7<br />
6ES7 658-5AC.. .......................................... 4/7<br />
6ES7 658-5AD.. .......................................... 4/7<br />
6ES7 658-5AE............................................. 4/7<br />
6ES7 658-7AX21-2YB5 ............................... 2/3<br />
6ES7 658-7BX21-2YA0 ............................... 2/3<br />
6ES7 658-7CX21-2YB0............................... 2/3<br />
6ES7 658-7DX06-0YA0 ...................... 4/14, 7/6<br />
6ES7 658-7EX06-0YB0 ............................... 7/6<br />
6ES7 658-7F................................................ 7/6<br />
6ES7 833-1CC00-0YX0.................. 4/11, 10/10<br />
6ES7 833-1CC00-6YX0........................... 10/10<br />
6ES7 833-1SM00-0YA5............................. 4/13<br />
6ES7 833-1SM40-0YA5............................. 4/13<br />
6ES7 833-1SM60-0YA5.................... 4/13, 5/13<br />
6ES7 833-2AC01-0YB0........... 4/8, 10/8, 10/10<br />
6ES7 841-0C............................................. 4/20<br />
6ES7 870-1.... ........................................... 9/21<br />
6ES7 900-..... ......................... 2/9, 5/6, 6/4, 7/4<br />
6ES7 902-1AB00-0AA0............................. 9/21<br />
6ES7 902-1AC00-0AA0 ............ 5/16, 6/4, 9/21<br />
6ES7 902-1AD00-0AA0 ............................ 9/21<br />
6ES7 902-2.... ........................................... 9/21<br />
6ES7 902-3.... ........................................... 9/21<br />
6ES7 952-1AK00-0AA0............................. 10/8<br />
6ES7 952-1AL00-0AA0 .................... 10/5, 10/8<br />
6ES7 952-1AM00-0AA0 ................... 10/5, 10/8<br />
6ES7 952-1AP00-0AA0.................... 10/5, 10/8<br />
6ES7 952-1AS00-0AA0.................... 10/5, 10/8<br />
6ES7 952-1KM00-0AA0 ................... 10/5, 10/8<br />
6ES7 955-2.... ........................................... 10/8<br />
6ES7 960-1.... ........................................... 10/8<br />
6ES7 964-2AA01-0AB0............................. 9/13<br />
6ES7 964-2AA04-0AB0............................. 10/5<br />
6ES7 971-0BA00.............................. 10/5, 10/8<br />
6ES7 972-0AA01-0XA0............................. 9/10<br />
6ES7 972-0AB01-0XA0............................. 9/10<br />
6ES7 972-0AC80-0XA0.................. 9/10, 11/23<br />
6ES7 972-0BA30-0XA0........................... 11/23<br />
6ES7 972-0BA50-0XA0............................. 9/10<br />
6ES7 972-0BB50-0XA0............................. 9/10<br />
6ES7 972-0DA00-0AA0 ............................ 9/10<br />
6ES7 972-0DA30-0XA0........................... 11/23<br />
6ES7 972-0DA30-0XA0............................. 9/10<br />
6ES7 998-8XC01-8YE0 ............................... 2/2<br />
6ES7 998-8XC01-8YE2 ............................... 2/2<br />
6GF6 100-1BA........................................... 2/11<br />
6GF6 100-1PC........................................... 2/11<br />
6GF6 180-1AH .......................................... 2/11<br />
6GF6 710-1AA.......... 2/9, 3/4, 4/3, 5/6, 6/4, 7/4<br />
6GF6 710-1BA.......... 2/9, 3/4, 4/3, 5/6, 6/4, 7/4<br />
6GK1 100-..... .............................................. 9/5<br />
6GK1 105-..... .............................................. 9/5<br />
6GK1 151-..... .............................................. 3/4<br />
6GK1 161-2A............................................... 9/8<br />
6GK1 161-3A............................... 5/6, 5/16, 9/8<br />
6GK1 415-0A............................................. 9/20<br />
6GK1 415-2A............................................. 9/19<br />
6GK1 500-0FC00 ...................................... 9/10<br />
6GK1 500-3AA00 ...................................... 9/12<br />
6GK1 502-3CB10 ...................................... 9/11<br />
6GK1 704-1.... ............................................. 9/8<br />
6GK1 716-0.... .................................... 5/16, 9/8<br />
6GK1 716-1.... ...................................... 5/6, 9/8<br />
6GK1 901-0CA00-0AA0 .............................. 9/6<br />
6GK1 901-0CA01-0AA0 .............................. 9/6<br />
6GK1 901-0DA20-0AA0 ..................... 9/6, 9/11<br />
6GK1 901-0FB00-0AA0............................. 9/12<br />
6GK1 901-1B............................................... 9/7<br />
6GK1 901-1G... ........................................... 9/7<br />
6GK1 905-0.... ........................................... 9/18<br />
6GK1 905-6A.................................... 9/10, 9/18<br />
6GK1 905-6P... .......................................... 9/12<br />
6GK1 970-..... .............................................. 9/7<br />
6GK1 971-2.... ........................................... 9/19<br />
6GK1 971-3.... ........................................... 9/20<br />
6GK7 343-..... ............................................ 9/19<br />
6GK7 443-1EX11-0XE0 ............. 9/8, 10/5, 10/8<br />
6GK7 443-5DX03-0XE0........... 9/13, 10/5, 10/8<br />
6XV1 820-........................................... 9/6, 9/11<br />
6XV1 821-.................................................. 9/12<br />
6XV1 830-0................................................ 9/10<br />
6XV1 830-5................................................ 9/18<br />
6XV1 840-2.................................................. 9/7<br />
6XV1 850-0.................................................. 9/6<br />
6XV2 175-.................................................... 5/7<br />
MSO:... ...................................................... 2/12<br />
Appendix<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
Order no. index<br />
13/11<br />
13
13<br />
■<br />
13/12<br />
Appendix<br />
<strong>Siemens</strong> ST PCS 7 · October 2004
■<br />
Appendix<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
13/13<br />
13
13<br />
Appendix<br />
Conditions of sale <strong>and</strong> delivery<br />
■ Terms <strong>and</strong> Conditions of Sale <strong>and</strong> Delivery<br />
By using this catalog you can acquire hardware <strong>and</strong> software<br />
products described therein from the <strong>Siemens</strong> AG subject to the<br />
following terms. Please note! The scope, the quality <strong>and</strong> the conditions<br />
for supplies <strong>and</strong> services, including software products,<br />
by any <strong>Siemens</strong> entity having a registered office outside of Germany,<br />
shall be subject exclusively to the General Terms <strong>and</strong><br />
Conditions of the respective <strong>Siemens</strong> entity.<br />
for customers with a seat or registered office in the<br />
Federal Republic of Germany<br />
The General Terms of Payment as well as the General Conditions<br />
for the Supply of Products <strong>and</strong> Services of the Electrical <strong>and</strong><br />
Electronics Industry shall apply.<br />
For software products, the General License Conditions for Software<br />
Products for <strong>Automation</strong> <strong>and</strong> <strong>Drives</strong> for Customers with<br />
Seat or registered Office in Germany shall apply.<br />
for customers with a seat or registered office outside of<br />
Germany<br />
The General Terms of Payment as well as the General Conditions<br />
for Supplies of <strong>Siemens</strong>, <strong>Automation</strong> <strong>and</strong> <strong>Drives</strong> for Customers<br />
with a Seat or registered Office outside of Germany shall apply.<br />
For software products, the General License Conditions for Software<br />
Products for <strong>Automation</strong> <strong>and</strong> <strong>Drives</strong> for Customers with<br />
Seat or registered Office outside of Germany shall apply.<br />
General<br />
The prices are in € (Euro) ex works, exclusive packaging.<br />
The sales tax (value added tax) is not included in the prices.<br />
It shall be debited separately at the respective rate according to<br />
the applicable legal regulations.<br />
In addition to the prices of products which include silver <strong>and</strong>/or<br />
copper, surcharges may be calculated if the respective limits of<br />
the notes are exceeded.<br />
Prices are subject to change without prior notice. We will debit<br />
the prices valid at the time of delivery.<br />
The dimensions are in mm. Illustrations are not binding.<br />
Insofar as there are no remarks on the corresponding pages,<br />
- especially with regard to data, dimensions <strong>and</strong> weights given -<br />
these are subject to change without prior notice.<br />
Comprehensive Terms <strong>and</strong> Conditions of Sale <strong>and</strong> Delivery are<br />
available free of charge from your local <strong>Siemens</strong> business office<br />
under the following Order Nos.:<br />
6ZB5310-0KR30-0BA0<br />
(for customers based in the Federal Republic of Germany)<br />
6ZB5310-0KS53-0BA0<br />
(for customers based outside of theFederal Republic of<br />
Germany)<br />
or download them from the Internet:<br />
www.siemens.com/automation/mall<br />
(Germany: A&D Mall Online-Help <strong>System</strong>)<br />
Published by <strong>Siemens</strong> AG<br />
<strong>Automation</strong> <strong>and</strong> <strong>Drives</strong><br />
Industrial <strong>Automation</strong> <strong>System</strong>s<br />
Postfach 48 48,<br />
90327 NÜRNBERG<br />
FEDERAL REPUBLIC OF GERMANY<br />
13/14<br />
<strong>Siemens</strong> ST PCS 7 · October 2004<br />
■ Export regulations<br />
The products listed in this catalog / price list may be subject to<br />
European / German <strong>and</strong>/or US export regulations.<br />
Therefore, any export requiring a license is subject to approval<br />
by the competent authorities.<br />
According to current provisions, the following export regulations<br />
must be observed with respect to the products featured in this<br />
catalog / price list:<br />
AL Number of the German Export List.<br />
Products marked other than “N“ require an export<br />
license.<br />
In the case of software products, the export designations<br />
of the relevant data medium must also<br />
be generally adhered to.<br />
Goods labeled with an “AL not equal to N“ are<br />
subject to a European or German export authorization<br />
when being exported out of the EU.<br />
ECCN Export Control Classification Number.<br />
Products marked other than “N“ are subject to a<br />
reexport license to specific countries.<br />
In the case of software products, the export<br />
designations of the relevant data medium must<br />
also be generally adhered to.<br />
Goods labeled with an “ECCN not equal to N“ are<br />
subject to a US re-export authorization.<br />
Even without a label or with an “AL: N“ or “ECCN: N“, authorization<br />
may be required due to the final destination <strong>and</strong> purpose for<br />
which the goods are to be used.<br />
The deciding factors are the AL or ECCN export authorization<br />
indicated on order confirmations, delivery notes <strong>and</strong> invoices.<br />
Errors excepted <strong>and</strong> subject to change without prior notice.<br />
Online-Edition, Order No.<br />
E86060-W4678-A111-A8-7600<br />
KG K 1004 x.x x 178 En/ 415172 / IWI: TSTP<br />
Printed in the Federal Republic of Germany<br />
A&D/VuL/En 14.11.03
<strong>Automation</strong> <strong>and</strong> <strong>Drives</strong><br />
Interactive catalog on CD-ROM<br />
Catalog<br />
The Offline Mall of <strong>Automation</strong> <strong>and</strong> <strong>Drives</strong> CA 01<br />
<strong>Automation</strong> <strong>System</strong>s for Machine Tools<br />
SINUMERIK & SIMODRIVE NC 60<br />
Drive <strong>System</strong>s<br />
Variable-Speed <strong>Drives</strong><br />
SINAMICS G130 Drive Converter Chassis Units<br />
SINAMICS G150 Drive Converter Cabinet Units<br />
D11<br />
SINAMICS G110 Inverter Chassis Units D11.1<br />
SINAMICS S120 Servo Control Drive <strong>System</strong> D21.2<br />
SINAMICS S150 Drive Converter Cabinet Units D21.3<br />
DC Motors DA 12<br />
SIMOREG DC MASTER 6RA70 Digital Chassis<br />
Converters<br />
DA 21.1<br />
SIMOREG K 6RA22 Analog Chassis Converters DA 21.2<br />
SIMOREG DC MASTER 6RM70 Digital Converter<br />
Cabinet Units<br />
DA 22<br />
SIMOVERT PM Modular Converter <strong>System</strong>s DA 45<br />
SIEMOSYN Motors DA 48<br />
MICROMASTER 410/420/430/440 Inverters DA 51.2<br />
MICROMASTER 411/COMBIMASTER 411 DA 51.3<br />
SIMOVERT MV Medium-Voltage <strong>Drives</strong> DA 63<br />
SIMOVERT MASTERDRIVES Vector Control DA 65.10<br />
SIMOVERT MASTERDRIVES Motion Control DA 65.11<br />
Synchronous <strong>and</strong> asynchronous servomotors for<br />
SIMOVERT MASTERDRIVES<br />
DA 65.3<br />
SIMODRIVE 611 universal <strong>and</strong> POSMO<br />
Low-Voltage Three-Phase-Motors<br />
DA 65.4<br />
Squirrel-Cage Motors, Totally Enclosed, Fan-Cooled M 11<br />
<strong>Automation</strong> <strong>System</strong>s for Machine Tools SIMODRIVE<br />
Main Spindle Motors<br />
Feed Motors<br />
Converter <strong>System</strong>s SIMODRIVE 611/POSMO<br />
NC 60<br />
Drive <strong>and</strong> Control Components for Hoisting Equipment HE 1<br />
Electrical Installation Technology<br />
PDF: ALPHA Small Distribution Boards <strong>and</strong><br />
Distribution Boards<br />
ET A1<br />
PDF: ALPHA Side-by-Side Switchgear Cabinets ET A3<br />
PDF: ALPHA FIX Terminal Blocks ET A5<br />
PDF: BETA Modular Installation Devices ET B1<br />
PDF: DELTA Switches <strong>and</strong> Outlets ET D1<br />
PDF: GAMMA Building Management <strong>System</strong>s ET G1<br />
Factory <strong>Automation</strong> Sensors FS 10<br />
Human Machine Interface <strong>System</strong>s SIMATIC HMI ST 80<br />
Industrial Communication for<br />
<strong>Automation</strong> <strong>and</strong> <strong>Drives</strong><br />
PDF: These catalogs are only available as pdf files.<br />
IK PI<br />
Catalogs of the<br />
<strong>Automation</strong> <strong>and</strong> <strong>Drives</strong> <strong>Group</strong> (A&D)<br />
Further information can be obtained from our<br />
branch offices listed in the appendix of this catalog<br />
Low-Voltage Controls <strong>and</strong> Distribution Catalog<br />
Low-Voltage Switchgear – Controlgear for Industry LV 10<br />
Power Distribution – Products <strong>and</strong> <strong>System</strong>s<br />
for Low-Voltage Power Distribution<br />
LV 30<br />
SIDAC-D reactors <strong>and</strong> SIDAC-F filters LV 63<br />
SIVACON 8PS Busbar Trunking <strong>System</strong>s<br />
CD, BD01, BD2 up to 1250 A<br />
LV 70<br />
Busbar trunking systems LDA/LDC LV 71<br />
Busbar trunking systems LXA/LXC LV 72<br />
SENTRON WL NS WL<br />
Motion Control <strong>System</strong> SIMOTION PM 10<br />
Process Instrumentation <strong>and</strong> Analytics<br />
Field Instruments for Process <strong>Automation</strong><br />
Measuring Instruments for Pressure,<br />
Differential Pressure, Flow, Level <strong>and</strong> Temperature,<br />
Positioners <strong>and</strong> Liquid Meters<br />
FI 01<br />
PDF: Indicators for panel mounting MP 12<br />
SIREC Recorders <strong>and</strong> Accessories MP 20<br />
SIPART, Controllers <strong>and</strong> Software MP 31<br />
SIWAREX Weighing <strong>System</strong>s WT 01<br />
Continuous Weighing <strong>and</strong> Process Protection WT 02<br />
Gas Analysis Equipment for the Process Industry PA 10<br />
PDF: Process Analytics,<br />
Components for the <strong>System</strong> Integration<br />
PA 11<br />
SIPAN Liquid Analysis PA 20<br />
SIMATIC Industrial <strong>Automation</strong> <strong>System</strong>s<br />
SIMATIC PCS Process Control <strong>System</strong> ST 45<br />
PDF: SIMATIC S5/505 <strong>Automation</strong> <strong>System</strong>s ST 50<br />
Components for Totally Integrated <strong>Automation</strong> <strong>and</strong><br />
Micro <strong>Automation</strong><br />
ST 70<br />
SIMATIC PCS 7 Process Control <strong>System</strong> ST PCS 7<br />
PDF: Add-ons for the SIMATIC PCS 7<br />
Process Control <strong>System</strong><br />
ST PCS 7.A<br />
SIMATIC Control <strong>System</strong>s ST DA<br />
SIPOS Electric Actuators<br />
Electric Rotary, Linear <strong>and</strong> Part-turn Actuators MP 35<br />
Electric Rotary Actuators for Nuclear Plants MP 35.1/.2<br />
<strong>System</strong>s <strong>Engineering</strong><br />
Power supplies SITOP power KT 10.1<br />
<strong>System</strong> cabling SIMATIC TOP connect KT 10.2<br />
<strong>System</strong> Solutions<br />
Applications <strong>and</strong> Products for Industry are part of the<br />
interactive catalog CA 01<br />
TELEPERM M Process Control <strong>System</strong><br />
AS 235, AS 235H <strong>and</strong> AS 235K automation systems PLT 111<br />
PDF: AS 488/TM automation systems PLT 112<br />
Operating <strong>and</strong> monitoring with WinCC/TM PLT 123<br />
CS 275 bus system PLT 130<br />
A&D/3U/En 28.09.04
The information provided in this catalog contains descriptions<br />
or characteristics of performance which in case of actual use<br />
do not always apply as described or which may change as a<br />
result of further development of the products. An obligation<br />
to provide the respective characteristics shall only exist if<br />
expressly agreed in the terms of contract. Availability <strong>and</strong><br />
technical specifications are subject to change without notice.<br />
<strong>Siemens</strong> AG<br />
<strong>Automation</strong> <strong>and</strong> <strong>Drives</strong><br />
Industrial <strong>Automation</strong> <strong>System</strong>s<br />
FEDERAL REPUBLIC OF GERMANY<br />
www.siemens.com/simatic-pcs7 Order No. E86060-W4678-A111-A8-7600