D Chimney effect on large size vertical pipes, best: on the<br />
bottom.<br />
D Accessibility for maintenance purposes, best: at ground<br />
level.<br />
D Impact of other heat sources, sun etc, best: at cold side.<br />
For details please refer to the engineering documentation.<br />
5.3 Sensor placement: limitation device<br />
6<br />
Typically the sensor is being placed on a length of cable,<br />
that is separated from the pipe by means of insulating<br />
material,in order to create an “artificial hotspot”.<br />
The choice of the right location for the limiter sensor<br />
depends on, but is not limited to following aspects:<br />
D Flow direction of the fluid, best location: upstream.<br />
D Impact of heatsinks such as supports etc, best: away from<br />
heatsinks.<br />
D Accessability for maintenance purposes, best: at ground<br />
level.<br />
D Chimney effect on large size vertical pipes, best: at the top.<br />
D Impact of other heat sources, sun etc, best: at hot side of<br />
pipe.<br />
D It is the responsibility of the installer to ensure that these<br />
conditions are met in the most appropriate way.<br />
For details please refer to the engineering documentation.<br />
<strong>Thermal</strong> insulation <strong>and</strong> marking<br />
6.1 Pre-insulation checks<br />
D Visually inspect the heating cable <strong>and</strong> components for correct<br />
installation <strong>and</strong> possible damage. (See Section 10 if<br />
damaged.)<br />
D Insulation resistance testing (as per Section 8) is strongly<br />
recommended prior to covering the pipe with thermal insulation.<br />
18