BLOCK DIAGRAMS FOR ROOM STATION ONLY SYSTEMS<br />

Star Wired System<br />

ROOM 1<br />

ROOM 2<br />

Power Supply<br />

Input Jack<br />

Type B<br />

ROOM 3 DOOR<br />

ROOM 4 ROOM 5<br />

Power Supply<br />

ROOM 6<br />

Note: The maximum length (in metres) of any individual wiring run = 100 divided by the number of stations on the run.<br />

i.e. The maximum length for the cable run connecting Rooms 1, 4,5 & 6, is<br />

100m ÷ 3 room stations = 33 metres in total.<br />

(Room 1 is not used in the calculation because it is the station to which the power supply is connected)<br />

Loop Wired System<br />

Plug Pack<br />

Input Jack<br />

Type B<br />

Plug Pack<br />

ROOM 1 ROOM 2 ROOM 3 DOOR<br />

Note: The maximum length (in metres) of any individual wiring run = 100 divided by the number of stations on the run.<br />

i.e. The maximum length for the cable run connecting the Door station and Rooms 1,2 & 3, is<br />

100m ÷ 3 stations = 33 metres in total.<br />

(Room 1 is not used in the calculation because it is the station to which the power supply is connected)<br />

A Load Resistor is required on Room Station Only systems. In the examples<br />

above, the Load Resistor should be fitted across the VLC and NEG terminals<br />

of Room 1 (the Room Station to which the power supply is connected).<br />

Relay<br />

Relay<br />

Lock<br />

Lock<br />

9