<strong>ULTIMA</strong> <strong>COMPACT</strong> <strong>Chillers</strong><br />
Maintenance<br />
CAUTION<br />
IMPORTANT<br />
GENERAL<br />
MAINTENANCE<br />
<strong>Chillers</strong><br />
44 Installation & Maintenance : 903-129 IM E 10/04/C<br />
ALL work MUST be carried out by Technically Trained competent personnel.<br />
The equipment contains live electrical and moving parts, ISOLATE prior to<br />
maintenance or repair work.<br />
UK MAINLAND - The Chiller Maintenance Record and supporting maintenance<br />
documents MUST be complete and available on request to validate warranty.<br />
The Chiller Maintenance Record is located within the unit control panel.<br />
The maintenance schedule indicates the time period between maintenance operations.<br />
3 MONTHS ACTION NOTES<br />
REFRIGERATION<br />
SYSTEM<br />
Check the following and compare results with<br />
commissioning records.<br />
Investigate and rectify variations.<br />
• Suction and discharge readings.<br />
Remember to re-cap the Schraeder<br />
• Head pressure control is maintained.<br />
connections!<br />
• Pressure relief indicator gauge.<br />
• Check each circuit sight glass for dryness and bubbles<br />
for indication of leaks.<br />
• Check compressor oil level and<br />
shell/sump temperature.<br />
• Visually inspect the unit for oil patches. Investigate and repair possible leaks.<br />
Check the following against the commissioning records.<br />
• Control settings.<br />
• Alarm log for unusual occurrences.<br />
• Chilled water control maintains design temperature.<br />
• Chilled water flow is within design limits of zero to<br />
plus 10%.<br />
• Concurrently ensure chilled water pump and flow switch<br />
operate efficiently, and that interlocks function correctly.<br />
• Operation of waterflow switch and pump interlock.<br />
Finally! Record operating conditions.<br />
FABRIC<br />
Visually inspect the unit for general wear and tear, treat<br />
metalwork.<br />
Investigate and adjust as necessary.<br />
Rust should be inhibited, primed and touched up<br />
with matching paint (available from <strong><strong>Air</strong>edale</strong> or<br />
your Distributor).<br />
Visually inspect pipe and pipework insulation. Repair/rectify as necessary.<br />
Clean evaporator water strainer. At first maintenance visit and then as frequently<br />
as necessary (12 months).<br />
Clean condenser coils. Do not steam clean use detergent Do not damage fins and comb out if necessary.<br />
and stiff bristled brush. For heavy dirt, use either a high<br />
pressure water or chemical hose.<br />
Visually check the following:<br />
• Pipework clamps are secure.<br />
• Tightness and condition of fan and compressor mounts.<br />
• Anti-Vibration mounts fixings (if fitted).<br />
Finally! Ensure control panel lids and access panels have been<br />
correctly replaced and securely fastened in position.<br />
Secure/tighten as necessary.