Commissioning Data<br />
OPERATIONAL SEQUENCE<br />
Refrigerant Charge Check for the presence of a refrigerant charge in the condenser side.<br />
Sump Heater The mains supply to the sump (oil) heater should be switched on at least 8 hours prior to<br />
compressor starting to avoid refrigerant migration.<br />
CAUTION<br />
<strong>Chillers</strong><br />
40 Installation & Maintenance : 903-129 IM E 10/04/C<br />
A separately fused, locally isolated, permanent single phase and neutral supply<br />
MUST BE FITTED for the compressor sump heater, evaporator trace heating and<br />
control circuits, FAILURE to do so could INVALIDATE WARRANTY.<br />
Pre-Start-Up Check Before compressor start-up, make sure that an oil level is showing in the compressor<br />
sight glass, and that all refrigerant ball valves are opened.<br />
CAUTION<br />
Check phase rotation by connecting pressure gauges to the suction and<br />
discharge ports, if no differential pressure occurs, isolate immediately.<br />
Adding Refrigerant The unit is supplied with a full refrigerant charge, additional refrigerant should be added to<br />
the system via 1/4” schraeder connection on the expansion line if required.<br />
Pump Down Never pump down without the low pressure trip and high discharge temperature switches<br />
being operative.<br />
UNLOADING PROTECTION<br />
Head Pressure The microprocessor has inbuilt protection against nuisance trips. If the head pressure<br />
rises above 24barg the system will unload 1 compressor and remain unloaded until the<br />
head pressure drops below 21barg.<br />
Low Pressure If low pressure drops below the microprocessor setting, the compressor will unload to 1<br />
compressor, if low pressure persists for 1 minute, the circuit will be switched off and<br />
sound an alarm.