<strong>ULTIMA</strong> <strong>COMPACT</strong> <strong>Chillers</strong><br />

Installation Data<br />

ELECTRICAL DATA<br />

General • As standard the equipment is designed for 400V, 3 phase, 3 wire 50Hz and a<br />

separate permanent 230V, 1 phase, 50Hz supply, to all relevant IEE regulations,<br />

British standards and IEC requirements.<br />

CAUTION<br />

CAUTION<br />

CAUTION<br />

Interlocks & Protection<br />

CAUTION<br />

CAUTION<br />

• Ensure correct phase rotation.<br />

• A fused and isolated electrical supply of the appropriate phase, frequency and<br />

voltage should be installed.<br />

• The control voltage to the interlocks is 24V. Always size the low voltage interlock and<br />

protection cabling for a maximum voltage drop of 2V.<br />

<strong>Chillers</strong><br />

22 Installation & Maintenance : 903-129 IM E 10/04/C<br />

• Wires should be capable of carrying the maximum load current under non-fault<br />

conditions at the stipulated voltage.<br />

• Avoid large voltage drops on cable runs, particularly low voltage wiring.<br />

• Once the connecting pipework is complete the electrical supply can be connected by<br />

routing the cable through the appropriate casing hole and connecting the cables,<br />

refer to the Wiring Diagram supplied with each unit.<br />

A separately fused, locally isolated, permanent single phase and neutral supply<br />

MUST BE FITTED for the compressor sump heater, evaporator trace heating and<br />

control circuits, FAILURE to do so could INVALIDATE WARRANTY.<br />

Always electrically interlock the operation of the chiller with the pump controls and water<br />

flow switch.<br />

These safety devices prevent the chiller operating with low water flow which can cause<br />

serious damage.<br />

Failure to install both safety devices will invalidate the chiller warranty.<br />

Do not rely solely on the BMS to protect the chiller against low flow conditions.<br />

An evaporator pump interlock and flow switch MUST be directly wired to the<br />

chiller, refer to Interconnecting Wiring diagram.