<strong>ULTIMA</strong> <strong>COMPACT</strong> <strong>Chillers</strong><br />

Installation Data<br />

WATER SYSTEM<br />

CAUTION<br />

Chilled water pipework and ancillary components must be installed in accordance with:<br />

• National and Local Water supply company standards.<br />

• The manufacturer's instructions are followed when fitting ancillary components.<br />

• The system water is treated to prevent corrosion and algae forming.<br />

• In ambients of 0°C and below, where static water can be expected, or when water<br />

supply temperatures of +5°C or below is required, the necessary concentration of<br />

Glycol or use of an electrical trace heater must be included.<br />

• The schematic is referred to as a guide to ancillary recommendations.<br />

The unit water connections are NOT designed to support external pipework,<br />

pipework should be supported during installation.<br />

The water flow commissioning valve set is not shown in the diagram, as the valve can be<br />

fitted elsewhere within the chilled water circuit.<br />

STANDARD RECOMMENDED INSTALLATION (PARTS SUPPLIED BY OTHERS)<br />

CAUTION<br />

CAUTION<br />

<strong>Chillers</strong><br />

16 Installation & Maintenance : 903-129 IM E 10/04/C<br />

T<br />

5<br />

FS<br />

1<br />

6<br />

2<br />

M<br />

1 Filter 20 Mesh<br />

2 Pump<br />

3 Filter 1/16”<br />

4 Pressure Sensor<br />

5 Flow Switch<br />

6 Flushing By Pass Leg<br />

7 Pressure Sensor<br />

Constant water flow MUST be maintained. Variable water volume is<br />

NOT recommended and may invalidate warranty.<br />

Following components are fitted within the chiller unit as standard:<br />

• Temperature Sensors<br />

• Drain Point<br />

• Auto <strong>Air</strong> Vent<br />

FLOW SCHEMES Key: 1 Water In<br />

2 Water Out<br />

Basic Supplied Water<br />

Schematic<br />

(Includes Flow Switch<br />

Optional Extra)<br />

TT F<br />

TT FS<br />

3<br />

F<br />

1<br />

2<br />

4<br />

P<br />

7<br />

P