<strong>ULTIMA</strong> <strong>COMPACT</strong> <strong>Chillers</strong><br />
Installation Data<br />
WATER SYSTEM<br />
CAUTION<br />
Chilled water pipework and ancillary components must be installed in accordance with:<br />
• National and Local Water supply company standards.<br />
• The manufacturer's instructions are followed when fitting ancillary components.<br />
• The system water is treated to prevent corrosion and algae forming.<br />
• In ambients of 0°C and below, where static water can be expected, or when water<br />
supply temperatures of +5°C or below is required, the necessary concentration of<br />
Glycol or use of an electrical trace heater must be included.<br />
• The schematic is referred to as a guide to ancillary recommendations.<br />
The unit water connections are NOT designed to support external pipework,<br />
pipework should be supported during installation.<br />
The water flow commissioning valve set is not shown in the diagram, as the valve can be<br />
fitted elsewhere within the chilled water circuit.<br />
STANDARD RECOMMENDED INSTALLATION (PARTS SUPPLIED BY OTHERS)<br />
CAUTION<br />
CAUTION<br />
<strong>Chillers</strong><br />
16 Installation & Maintenance : 903-129 IM E 10/04/C<br />
T<br />
5<br />
FS<br />
1<br />
6<br />
2<br />
M<br />
1 Filter 20 Mesh<br />
2 Pump<br />
3 Filter 1/16”<br />
4 Pressure Sensor<br />
5 Flow Switch<br />
6 Flushing By Pass Leg<br />
7 Pressure Sensor<br />
Constant water flow MUST be maintained. Variable water volume is<br />
NOT recommended and may invalidate warranty.<br />
Following components are fitted within the chiller unit as standard:<br />
• Temperature Sensors<br />
• Drain Point<br />
• Auto <strong>Air</strong> Vent<br />
FLOW SCHEMES Key: 1 Water In<br />
2 Water Out<br />
Basic Supplied Water<br />
Schematic<br />
(Includes Flow Switch<br />
Optional Extra)<br />
TT F<br />
TT FS<br />
3<br />
F<br />
1<br />
2<br />
4<br />
P<br />
7<br />
P