Installation Data<br />
POINT LOADINGS, WEIGHTS & CENTRE OF GRAVITY (C OF G)<br />
SINGLE ROW FANS - /1<br />
UCC30 - UCC80 (Except UCC75)<br />
<strong>Chillers</strong><br />
10 Installation & Maintenance : 903-129 IM E 10/04/C<br />
1<br />
P1<br />
P2<br />
2 = C of G<br />
Operating C of G1 C of G2<br />
Model SQ/DQ P1 P2 P3 P4 (1) (1) Weight (mm) (mm)<br />
UCC30 SQ/DQ-1/1 kg 125 125 125 125 500 600 825<br />
UCC40 SQ/DQ-1/1 kg 150 150 140 140 580 600 800<br />
UCC50 SQ/DQ-2/1 kg 180 180 185 185 730 600 1040<br />
UCC60 SQ/DQ-2/1 kg 190 190 200 200 780 600 1040<br />
UCC70 SQ/DQ-2/1 kg 195 195 205 205 800 600 1040<br />
UCC80 SQ/DQ-2/1 kg 215 215 230 230 890 600 1040<br />
Operating C of G1 C of G2<br />
Model SSQ/DSQ P1 P2 P3 P4 (1) (1) Weight (mm) (mm)<br />
UCC30 SSQ/DSQ-1/1 kg 125 125 125 125 500 600 825<br />
UCC40 SSQ/DSQ-1/1 kg 155 155 145 145 600 600 800<br />
UCC50 SSQ/DSQ-2/1 kg 185 185 185 185 740 600 1040<br />
UCC60 SSQ/DSQ-2/1 kg 195 195 200 200 790 600 1040<br />
UCC70 SSQ/DSQ-2/1 kg 195 195 210 210 810 600 1040<br />
UCC80 SSQ/DSQ-2/1 kg 225 225 240 240 930 600 1040<br />
UCC75 - UCC150 (Except UCC80)<br />
1<br />
2<br />
P3<br />
P4<br />
P1 P3 P5<br />
P2 P4 P6<br />
= C of G<br />
Operating C of G1 C of G2<br />
Model D P1 P2 P3 P4 P5 P6 Weight (mm) (mm)<br />
UCC75D-2/1 kg 320 320 (1) (1) 160 160 960 665 845<br />
UCC100D-2/1 kg 345 345 (1) (1) 175 175 1040 665 860<br />
UCC125D-3/1 kg 315 295 140 130 190 190 1260 665 1380<br />
UCC150D-3/1 kg 330 330 155 155 205 205 1380 665 1370<br />
Operating C of G1 C of G2<br />
Model DQ P1 P2 P3 P4 P5 P6 Weight (mm) (mm)<br />
UCC75DQ-2/1 kg 330 330 (1) (1) 170 170 1000 665 845<br />
UCC100DQ-3/1 kg 285 285 135 135 175 175 1190 665 1365<br />
UCC125DQ-3/1 kg 320 300 155 145 200 200 1320 665 1385<br />
UCC150DQ-4/1 kg 340 340 195 195 250 250 1570 665 1590<br />
Operating C of G1 C of G2<br />
Model DSQ P1 P2 P3 P4 P5 P6 Weight (mm) (mm)<br />
UCC75DSQ-2/1 kg 345 345 (1) (1) 165 165 1020 665 845<br />
UCC100DSQ-3/1 kg 300 300 130 130 175 175 1210 665 1365<br />
UCC125DSQ-4/1 kg 340 320 200 190 250 240 1540 665 1575<br />
UCC150DSQ-4/1 kg 355 355 215 215 270 270 1680 665 1590<br />
(1) Have only 4 fixing and 4 point loadings.<br />
(2) Based on standard unit, for units fitted with pump, tank and expansion vessel options, please contact <strong><strong>Air</strong>edale</strong>.