7.0 Findings<br />
1. The propane service technicians, emergency responders, <strong>and</strong> store employees did not evacuate the<br />
area as recommended by nationally accepted guidance for propane emergencies. In fact, emergency<br />
responders <strong>and</strong> the propane service technicians were observed st<strong>and</strong>ing in the propane vapor cloud.<br />
2. <strong>Propane</strong> companies, the National <strong>Propane</strong> Gas Association, <strong>and</strong> the U.S. Department of<br />
Transportation recommend evacuation to a safe distance as the first action in response to a propane<br />
release.<br />
3. The fire department captain, the propane service technicians, <strong>and</strong> the <strong>Little</strong> <strong>General</strong> <strong>Store</strong> employees<br />
were unaware of the dangerous propane accumulation inside the building.<br />
4. A defect in the existing tank’s liquid withdrawal valve caused it to malfunction <strong>and</strong> remain in an open<br />
position.<br />
5. About 25 minutes elapsed from the time the release began until the explosion.<br />
6. Both the U.S. Occupational <strong>Safety</strong> <strong>and</strong> Health Administration’s <strong>and</strong> the West Virginia Fire<br />
Commission’s propane st<strong>and</strong>ards require a distance of at least 10 feet between 500-gallon propane<br />
tanks <strong>and</strong> buildings such as the <strong>Little</strong> <strong>General</strong> <strong>Store</strong>. However, when the Southern Sun propane<br />
company installed the propane tank in 1994 it was placed directly against the <strong>Little</strong> <strong>General</strong> <strong>Store</strong>’s<br />
exterior back wall.<br />
7. Ferrellgas, which acquired Southern Sun in 1996, allowed the tank to remain against the building’s<br />
exterior wall for more than 10 years.<br />
8. The placement of the 500-gallon propane tank against the building’s exterior wall provided propane a<br />
direct pathway into the store’s interior during the release.<br />
9. Ferrellgas management’s quality review program functions as a basic safety inspection rather than a<br />
management systems audit.<br />