25.12.2012 Views

Little General Store Propane Explosion - US Chemical Safety and ...

Little General Store Propane Explosion - US Chemical Safety and ...

Little General Store Propane Explosion - US Chemical Safety and ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Little</strong> <strong>General</strong> <strong>Store</strong> September 2008<br />

Figure 10. Incident tank side facing building.<br />

During the release, witnesses described seeing billowing white clouds striking the building <strong>and</strong> roof<br />

overhang <strong>and</strong> cascading toward the ground, which is consistent with the known behavior of propane<br />

vapor following a liquid release. The peaked roof of the store overhung the exterior walls. The overhang<br />

was open to allow ventilation in the store’s attic space; restroom exhaust ducts terminated inside the<br />

overhang directly above the incident tank. The open overhang <strong>and</strong> restroom exhaust ducts provided a<br />

direct pathway for propane to enter the building. The CSB found that if the tank were placed at least 10<br />

feet from the store, propane likely would not have entered the store in large quantities.<br />

5.2.1 Southern Sun Acquisition<br />

Ferrellgas’ acquisition of Southern Sun included a pre-acquisition review of Southern Sun’s business <strong>and</strong><br />

operations, which included inspections of propane systems at select Southern Sun customer locations. In<br />

addition, Ferrellgas was allowed to identify <strong>and</strong> request correction of any deficiencies discovered in the<br />

year following the acquisition. According to Southern Sun, only two propane tanks were returned, both<br />