Safety Shut-Off Valves<br />

<strong>General</strong> <strong>Technical</strong> <strong>Specification</strong><br />

These shall shut-<strong>of</strong>f in case the pressure on the upstream side <strong>of</strong> the valve becomes<br />

less than preset values. The valves shall be <strong>of</strong> globe type for DN 50 and below and<br />

butterfly type for sizes above DN 50; the material shall be suitable for service conditions.<br />

The valves shall be actuated by electromagnetic or pneumatic device working in<br />

conjunction with pressure switches located on the pipelines being safeguarded and shall<br />

include all components required for its functioning.<br />

Electrical continuity<br />

Metallic electro static jumpers shall be provided at all locations on all flanged<br />

connections, in case <strong>of</strong> flammable gases and oxygen. This is to prevent accumulation <strong>of</strong><br />

static electricity in pipe sections. Piping system shall be suitably earthed at a regular<br />

length <strong>of</strong> pipeline.<br />

Measuring and control devices<br />

Instrumentation and control devices shall be provided for monitoring the fluid distribution<br />

system, regulation <strong>of</strong> pressure and flow.<br />

Flow measurement shall be provided at battery limit <strong>of</strong> all production and consuming<br />

units, inlet/ outlet piping <strong>of</strong> storage installations, on surplus gas bleeder piping to flare<br />

system etc. When orifice plates are used, proper care shall be taken in piping layout for<br />

preventing accumulation <strong>of</strong> condensate by providing suitable slope or drain system.<br />

Requirement <strong>of</strong> straight length upstream and downstream <strong>of</strong> flow sensors shall be<br />

maintained as per instrumentation requirements. Normally the straight length<br />

recommended is 10 times pipe dia before inlet and 5 times pipe dia after outlet <strong>of</strong> device.<br />

Pressure measurement shall be provided at battery limits <strong>of</strong> production and consumer<br />

units, at outlet <strong>of</strong> storage systems, inlet and outlet <strong>of</strong> pressure regulators/ controllers, etc.<br />

Pressure and Flow Control valves shall be provided at gas mixing stations, main<br />

pressure regulating stations, flare stack piping, inlet/ outlet piping <strong>of</strong> storage installations<br />

(gas holders). For low pressure gas lines, butterfly type control valves shall be used. For<br />

high pressure gases, globe valves may be used. Sizing <strong>of</strong> control valves shall be based<br />

on flow rate and pressure parameters.<br />

02.12. HOSES & HOSE BOXES<br />

<strong>General</strong> purpose oxygen and propane shall be provided with necessary isolating valves,<br />

pressure control valves, Hoses & Hose boxes at each consumer points. Nipples along<br />

with quick coupling hoses shall be provided for steam, compressed air and Nitrogen for<br />

purging and other needs.<br />

02.13. SPECIAL CONSIDERATIONS FOR OXYGEN PIPING<br />

Filters should be installed in the oxygen pipeline system at the following points:<br />

a) At the outlet <strong>of</strong> the oxygen plant.<br />

b) Upstream <strong>of</strong> components having s<strong>of</strong>t seating in contact with the oxygen stream e.g.<br />

pressure regulator and control valves.<br />

c) Upstream <strong>of</strong> components that have moving parts in contract with the oxygen stream e.g.<br />

flow measuring and limiting devices.<br />

Provision shall be made for safe and easy access for frequent cleaning and / or<br />

replacement <strong>of</strong> the filter element. The larger capacity filters like (a) above should be<br />

provided with differential pressure gauge for monitoring the condition and providing<br />

Gases & Liquid Fluids<br />