WEATHERPROOFING/SEALING CHAPTER 3: COMMUNICATION SITE BUILDING DESIGN AND INSTALLATION<br />

In general, observe the following considerations <strong>for</strong> <strong>sites</strong> utilizing transmission line connections from<br />

an interior area to the exterior of a building or shelter:<br />

• The entry of antenna transmission lines into a <strong>communication</strong>s building or room requires a<br />

weatherproof, commercially made port assembly specifically designed <strong>for</strong> this purpose. These<br />

assemblies typically consist of a transmission line entry plate <strong>and</strong> boot assembly.<br />

• A boot shall be used even if the cable is run through conduit. To avoid inconvenient rework in the<br />

future, it is recommended to select a transmission line entry plate with enough ports to<br />

accommodate the number of transmission lines at the site <strong>and</strong> allow <strong>for</strong> expansion.<br />

• Entry plates should have 102 mm or 127 mm (4 or 5 in.) diameter openings. The plate is usually<br />

made of painted aluminum, with from one to 12 ports per plate. A single entry plate mounted on the<br />

outside wall or bulkhead is sufficient. See Figure 3-7.<br />

FIGURE 3-7 TYPICAL ENTRY PLATE<br />

• Cable boots corresponding to the cable diameter(s) shall be used. Cable boots are sized <strong>for</strong> the<br />

transmission line they will carry <strong>and</strong> can be round, oval or rectangular. Some cable boots allow up<br />

to three small (12.7 or 22.2 mm (0.5 or 0.875 in.)) transmission lines to enter through one boot. The<br />

boot is usually made up of a two-piece cushion jacket, cushion (sized to cable diameter), <strong>and</strong> clamp<br />

set.<br />

• To reduce heat loss from the building, two entry plates should be installed inside <strong>and</strong> outside, with<br />

rigid construction foam insulation between them. (Two sets of boots are then required.)<br />

• The entry plate shall be installed per the manufacturer's instructions.<br />

• The building/shelter <strong>and</strong> the port attachment to the building/shelter, shall be designed to prevent<br />

animals or birds from nesting in <strong>and</strong> around the entry ports.<br />

• Transmission line entry ports shall not be used to feed through tower light power, building ground,<br />

or control cables.<br />

• Boots shall be made of a material unaffected by ozone, sunlight, extreme heat, <strong>and</strong> cold.<br />

3-12 68P81089E50-B 9/1/05