STANDARDS AND GUIDELINES FOR COMMUNICATION SITES FLOOR LOADING<br />

• Design of foundation shall consider any special precipitation conditions unique to the installation<br />

locality. These considerations include, but are not limited to, elevated (pier type) plat<strong>for</strong>ms used in<br />

low-lying areas prone to regular flooding <strong>and</strong> elevated foundations to prevent burial of site due to<br />

snowfall. Special foundation designs include:<br />

• Footings<br />

• Piers<br />

• Columns<br />

FIGURE 3-6 TYPICAL SHELTER MOUNTED ON ELEVATED PIERS<br />

3.5 FLOOR LOADING<br />

When determining equipment placement in an existing structure or when developing building<br />

specifications <strong>for</strong> an equipment shelter, attention shall be given to the Structural Live Load capacity of<br />

the building. St<strong>and</strong>ard commercial construction specifications will, in most cases, provide substantial<br />

floor loading capacity. However, stacking <strong>and</strong>/or back-to-back placement of some equipment may<br />

exceed structural load limits. The weight <strong>and</strong> footprint dimensions of each piece of equipment to be<br />

installed shall be used to calculate floor loading.<br />

The minimum floor loading st<strong>and</strong>ard <strong>for</strong> current Motorola manufactured equipment is 635 kPa<br />

(300 lb/ft2 (PSF)). Calculations of the weight of the proposed equipment in PSF shall be compared to<br />

the rated load carrying capacity of the structure.<br />

Battery configurations can sometimes be specified with feet, rails, or specialized load spreading devices<br />

that can facilitate deployments in high-rise structures. It is often necessary to specify a battery's location<br />

within a pre-fabricated shelter, such that if the building is staged (fully equipped <strong>and</strong> optimized) be<strong>for</strong>e<br />

shipment, the building has enough structural strength to be lifted <strong>and</strong> transported fully loaded.<br />

Battery configurations with weight exceeding 300 lb/ft 2 shall utilize a specialized load spreading device<br />

<strong>for</strong> the battery rack. Remember to plan <strong>for</strong> expansion when calculating floor loading.<br />

The civil engineering firm, contractor, or architect responsible <strong>for</strong> designing <strong>and</strong>/or constructing the site<br />