EXTERNAL GROUNDING (EARTHING) ELECTRODE SYSTEM APPENDIX F: R56 COMPLIANCE CHECKLIST<br />

❐ When used, grounding electrode encasement materials meet specifications <strong>and</strong> installation<br />

requirements.<br />

❐ All grounding conductors meet specifications <strong>and</strong> are properly installed.<br />

❐ All grounding conductors have been routed in a continuous downward direction toward<br />

the EGB, TGB, or grounding electrode system, with no sharp bends.<br />

❐ Grounding conductors are routed as straight as possible <strong>and</strong> protected from physical<br />

damage as required.<br />

❐ Grounding conductors are securely fastened as required.<br />

❐ Grounding conductors meet or exceed the conductor size requirements.<br />

❐ Braided grounding conductors re not used anywhere in the external grounding system.<br />

❐ An External Ground Bus Bar (if required) is properly installed at transmission line entry<br />

point.<br />

❐ EGB grounding electrode conductor is properly installed.<br />

❐ A Tower ground bus bar (if required) is properly installed.<br />

❐ Soil conditions at the site have been reviewed <strong>and</strong> grounding electrode system<br />

components have been selected accordingly.<br />

❐ Galvanic corrosion has been considered <strong>and</strong> installation techniques have been employed<br />

to help prevent galvanic corrosion.<br />

❐ Approved bonding techniques are used to bond dissimilar metals.<br />

❐ Approved methods are used <strong>for</strong> conductor connection <strong>and</strong> termination.<br />

❐ Bonding surfaces <strong>for</strong> lugs <strong>and</strong> clamps are free of paint <strong>and</strong> corrosion <strong>and</strong> a conductive<br />

anti-oxidant compound has been applied.<br />

❐ Painted or galvanized bonding surfaces <strong>for</strong> exothermic welding were cleaned <strong>and</strong> painted<br />

to inhibit rusting.<br />

❐ The grounding electrode system resistance requirements are met.<br />

❐ The tower is properly grounded <strong>and</strong> bonded, with the required number of grounding<br />

conductors.<br />

❐ Guy anchor points <strong>for</strong> guyed towers are properly grounded in a manner that will minimize<br />

galvanic corrosion.<br />

❐ A grounding electrode system that is appropriated <strong>for</strong> the site (e.g., dedicated<br />

<strong>communication</strong>s building, outdoor cabinet, or Type A site) is installed.<br />

❐ Generators external to the building are properly grounded/bonded.<br />

❐ Tower mounted antenna preamplifiers are properly grounded/bonded to the tower.<br />

❐ Each transmission line outer shield is properly bonded to the tower at the top of the tower<br />

near the antenna with a weather sealed transmission line grounding kit.<br />

❐ Each transmission line outer shield is properly bonded to the tower or the TGB at the<br />

transition of the vertical line run with a weather sealed transmission line grounding kit.<br />

F-2 68P81089E50-B 9/1/05