STANDARDS AND GUIDELINES FOR COMMUNICATION SITES CLAMP-ON OHMMETER TESTING PROCEDURE<br />

Neutral bonding inside meter box makes reading taken in building impossible.<br />

Reading must be taken on the power company side of this bond.<br />

Electrical Meter<br />

FIGURE D-10 CLAMP-ON OHMMETER PLACEMENT FOR MULTI-BONDED/MULTI-GROUNDING<br />

ELECTRODE SYSTEM (NEUTRAL-GROUND BOND AT METER BOX)<br />

Reading must be taken on the power company side<br />

of this bond.<br />

Electrical Meter<br />

Clamp-on Ohmmeter placed around<br />

Neutral on service feed<br />

Place Clamp-on Ohmmeter around<br />

Neutral on service feed.<br />

FIGURE D-11 CLAMP-ON OHMMETER PLACEMENT FOR MULTI-BONDED/MULTI-GROUNDING<br />

ELECTRODE SYSTEM (OVERHEAD SERVICE)<br />

68P81089E50-B 9/1/05 D-19