standards and guidelines for communication sites - Radio And ...
standards and guidelines for communication sites - Radio And ... standards and guidelines for communication sites - Radio And ...
FALL-OF-POTENTIAL METHOD TESTING PROCEDURE APPENDIX D: GROUNDING (EARTHING) ELECTRODE SYSTEM TESTING/VERIFICATION 4. Connect the Y lead to the measurement (Y) probe. 5. Determine the required placement of outer reference probe (Z) in accordance with paragraph “Testing Area Requirements” on page D-5. 6. Place the outer reference probe (Z) into the soil at the determined location. Connect the outer reference probe (Z) to meter terminal Z. 7. Note the distance of the outer reference probe (Z) from the grounding electrode system (this distance will be used in determining subsequent measurements). On the photocopy of the Fall-of- Potential Test Worksheet, write this distance in the “100%” space. 8. Place the measurement probe (Y) in the soil starting close to the area of the grounding electrode system under test. Take a measurement. 9. On the photocopy of the Fall-of-Potential Test Worksheet (page D-21), write the reading in the “0%” row of the worksheet. 10. Place the measurement probe (Y) at 5% of the distance between the grounding electrode system 'X' connection and the outer reference probe (Z). Take a measurement. Example: Assuming a “100%” distance of 131 m (430 ft.), Y probe would be placed at 6.55 m (21.5 ft.) for “5%” measurement location. NOTE: Placement of the measurement probe (Y) must be along a straight path between the grounding electrode system 'X' connection and the outer reference probe (Z). 11. On the photocopy of the Fall-of-Potential Test Worksheet, write down the reading in the appropriate row of the worksheet. 12. Place the measurement probe (Y) at 10% of the distance between the grounding electrode system 'X' connection and the outer reference probe (Z). Take a measurement. Example: Assuming a “100%” distance of 131 m (430 ft.), Y probe would be placed at 13.1 m (43 ft.) for “10%” measurement location. 13. On the photocopy of the Fall-of-Potential Test Worksheet (, write down the reading in the appropriate row of the worksheet. 14. At every 10% point, repeat steps 12 and 13 for the remaining spaces on the worksheet. 15. On the photocopy of Fall-of-Potential Test Graph Form, plot a graph of the measured resistances for all points listed on the worksheet. 16. Using Figure D-5, assess the test results as follows: • Valid Test: At approximately 62% of the total distance (“100%” distance), a plateau or “flat spot” should be noticeable in the plot, as shown in “VALID TEST GRAPH” in Figure D-5. The resistance at this plateau is the validated resistance of the system under test. • Invalid Test Graph (insufficient distance of Z-probe): If there is no plateau on the plot, shown in “INVALID TEST GRAPH (Z-Probe Spacing)” in Figure D-5, the test is considered invalid because the Z probe is not far enough from the X probe. D-10 68P81089E50-B 9/1/05
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES FALL-OF-POTENTIAL METHOD TESTING PROCEDURE • Invalid Test Graph (erroneous connection to neutral): If there is no plateau on the plot, shown in “INVALID TEST GRAPH (Connection to neutral)” in Figure D-5, the test is considered invalid because an erroneous connection of the grounding electrode system to a power company neutral , or other utility ground, remains. NOTE: If the electrical service provided by the Power Company does not contain a neutral wire that is bonded to an extensive power company grounding system, such as a 3-phase delta service, the fall-of-potential test can be performed on the grounding electrode system without disconnecting it from the power company. This is because the neutral wire is locally derived at the transformer and is not part of the extensive Power Company grounding system. All other utility connections must still be removed, such as the telephone company ground connection and ground through water/gas metallic pipes. NOTE: If sufficient access area exists, the entire procedure above should be repeated in different directions facing away from the center of the grounding electrode system. Repeating the procedure is recommended in case metal pipes or similar conductive objects are buried in a given test area. The presence of metal pipes or similar conductive objects may result in an inaccurate reading. Grounding Electrode Under Test TESTER X Xv Y Z X Y Z Outer Probe Measurement Probe Site Boundary FIGURE D-4 TYPICAL GROUND RESISTANCE TESTER CONNECTION 68P81089E50-B 9/1/05 D-11
- Page 429 and 430: STANDARDS AND GUIDELINES FOR COMMUN
- Page 431 and 432: STANDARDS AND GUIDELINES FOR COMMUN
- Page 433 and 434: APPENDIX B SOIL RESISTIVITY MEASURE
- Page 435 and 436: STANDARDS AND GUIDELINES FOR COMMUN
- Page 437 and 438: STANDARDS AND GUIDELINES FOR COMMUN
- Page 439 and 440: STANDARDS AND GUIDELINES FOR COMMUN
- Page 441 and 442: STANDARDS AND GUIDELINES FOR COMMUN
- Page 443 and 444: STANDARDS AND GUIDELINES FOR COMMUN
- Page 445 and 446: STANDARDS AND GUIDELINES FOR COMMUN
- Page 447 and 448: STANDARDS AND GUIDELINES FOR COMMUN
- Page 449 and 450: STANDARDS AND GUIDELINES FOR COMMUN
- Page 451 and 452: STANDARDS AND GUIDELINES FOR COMMUN
- Page 453 and 454: STANDARDS AND GUIDELINES FOR COMMUN
- Page 455 and 456: STANDARDS AND GUIDELINES FOR COMMUN
- Page 457 and 458: STANDARDS AND GUIDELINES FOR COMMUN
- Page 459 and 460: STANDARDS AND GUIDELINES FOR COMMUN
- Page 461 and 462: STANDARDS AND GUIDELINES FOR COMMUN
- Page 463 and 464: STANDARDS AND GUIDELINES FOR COMMUN
- Page 465 and 466: STANDARDS AND GUIDELINES FOR COMMUN
- Page 467 and 468: APPENDIX C PROTECTING AGAINST ELECT
- Page 469 and 470: STANDARDS AND GUIDELINES FOR COMMUN
- Page 471 and 472: APPENDIX D GROUNDING (EARTHING) ELE
- Page 473 and 474: STANDARDS AND GUIDELINES FOR COMMUN
- Page 475 and 476: STANDARDS AND GUIDELINES FOR COMMUN
- Page 477 and 478: STANDARDS AND GUIDELINES FOR COMMUN
- Page 479: STANDARDS AND GUIDELINES FOR COMMUN
- Page 483 and 484: STANDARDS AND GUIDELINES FOR COMMUN
- Page 485 and 486: STANDARDS AND GUIDELINES FOR COMMUN
- Page 487 and 488: STANDARDS AND GUIDELINES FOR COMMUN
- Page 489 and 490: STANDARDS AND GUIDELINES FOR COMMUN
- Page 491 and 492: STANDARDS AND GUIDELINES FOR COMMUN
- Page 493 and 494: STANDARDS AND GUIDELINES FOR COMMUN
- Page 495 and 496: STANDARDS AND GUIDELINES FOR COMMUN
- Page 497 and 498: APPENDIX E GENERAL CONVERSIONS AND
- Page 499 and 500: STANDARDS AND GUIDELINES FOR COMMUN
- Page 501 and 502: STANDARDS AND GUIDELINES FOR COMMUN
- Page 503 and 504: APPENDIX F R56 COMPLIANCE CHECKLIST
- Page 505 and 506: STANDARDS AND GUIDELINES FOR COMMUN
- Page 507 and 508: STANDARDS AND GUIDELINES FOR COMMUN
- Page 509 and 510: I NDEX Index Index AC power cabling
- Page 511 and 512: STANDARDS AND GUIDELINES FOR COMMUN
- Page 513 and 514: STANDARDS AND GUIDELINES FOR COMMUN
- Page 515 and 516: STANDARDS AND GUIDELINES FOR COMMUN
- Page 517 and 518: STANDARDS AND GUIDELINES FOR COMMUN
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES FALL-OF-POTENTIAL METHOD TESTING PROCEDURE<br />
• Invalid Test Graph (erroneous connection to neutral): If there is no plateau on the plot, shown<br />
in “INVALID TEST GRAPH (Connection to neutral)” in Figure D-5, the test is considered<br />
invalid because an erroneous connection of the grounding electrode system to a power<br />
company neutral , or other utility ground, remains.<br />
NOTE: If the electrical service provided by the Power Company does not contain a neutral wire that is bonded<br />
to an extensive power company grounding system, such as a 3-phase delta service, the fall-of-potential<br />
test can be per<strong>for</strong>med on the grounding electrode system without disconnecting it from the power<br />
company. This is because the neutral wire is locally derived at the trans<strong>for</strong>mer <strong>and</strong> is not part of the<br />
extensive Power Company grounding system. All other utility connections must still be removed, such<br />
as the telephone company ground connection <strong>and</strong> ground through water/gas metallic pipes.<br />
NOTE: If sufficient access area exists, the entire procedure above should be repeated in different directions<br />
facing away from the center of the grounding electrode system. Repeating the procedure is<br />
recommended in case metal pipes or similar conductive objects are buried in a given test area. The<br />
presence of metal pipes or similar conductive objects may result in an inaccurate reading.<br />
Grounding Electrode<br />
Under Test<br />
TESTER<br />
X Xv Y Z<br />
X Y Z<br />
Outer Probe<br />
Measurement<br />
Probe<br />
Site Boundary<br />
FIGURE D-4 TYPICAL GROUND RESISTANCE TESTER CONNECTION<br />
68P81089E50-B 9/1/05 D-11