24.12.2012 Views

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

standards and guidelines for communication sites - Radio And ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

FALL-OF-POTENTIAL METHOD TESTING PROCEDURE APPENDIX D: GROUNDING (EARTHING) ELECTRODE SYSTEM TESTING/VERIFICATION<br />

4. Connect the Y lead to the measurement (Y) probe.<br />

5. Determine the required placement of outer reference probe (Z) in accordance with paragraph<br />

“Testing Area Requirements” on page D-5.<br />

6. Place the outer reference probe (Z) into the soil at the determined location. Connect the outer<br />

reference probe (Z) to meter terminal Z.<br />

7. Note the distance of the outer reference probe (Z) from the grounding electrode system (this<br />

distance will be used in determining subsequent measurements). On the photocopy of the Fall-of-<br />

Potential Test Worksheet, write this distance in the “100%” space.<br />

8. Place the measurement probe (Y) in the soil starting close to the area of the grounding electrode<br />

system under test. Take a measurement.<br />

9. On the photocopy of the Fall-of-Potential Test Worksheet (page D-21), write the reading in the<br />

“0%” row of the worksheet.<br />

10. Place the measurement probe (Y) at 5% of the distance between the grounding electrode system 'X'<br />

connection <strong>and</strong> the outer reference probe (Z). Take a measurement.<br />

Example: Assuming a “100%” distance of 131 m (430 ft.), Y probe would be placed at 6.55 m (21.5 ft.)<br />

<strong>for</strong> “5%” measurement location.<br />

NOTE: Placement of the measurement probe (Y) must be along a straight path between the grounding electrode<br />

system 'X' connection <strong>and</strong> the outer reference probe (Z).<br />

11. On the photocopy of the Fall-of-Potential Test Worksheet, write down the reading in the<br />

appropriate row of the worksheet.<br />

12. Place the measurement probe (Y) at 10% of the distance between the grounding electrode system<br />

'X' connection <strong>and</strong> the outer reference probe (Z). Take a measurement.<br />

Example: Assuming a “100%” distance of 131 m (430 ft.), Y probe would be placed at 13.1 m (43 ft.)<br />

<strong>for</strong> “10%” measurement location.<br />

13. On the photocopy of the Fall-of-Potential Test Worksheet (, write down the reading in the<br />

appropriate row of the worksheet.<br />

14. At every 10% point, repeat steps 12 <strong>and</strong> 13 <strong>for</strong> the remaining spaces on the worksheet.<br />

15. On the photocopy of Fall-of-Potential Test Graph Form, plot a graph of the measured resistances<br />

<strong>for</strong> all points listed on the worksheet.<br />

16. Using Figure D-5, assess the test results as follows:<br />

• Valid Test: At approximately 62% of the total distance (“100%” distance), a plateau or “flat<br />

spot” should be noticeable in the plot, as shown in “VALID TEST GRAPH” in Figure D-5.<br />

The resistance at this plateau is the validated resistance of the system under test.<br />

• Invalid Test Graph (insufficient distance of Z-probe): If there is no plateau on the plot, shown<br />

in “INVALID TEST GRAPH (Z-Probe Spacing)” in Figure D-5, the test is considered invalid<br />

because the Z probe is not far enough from the X probe.<br />

D-10 68P81089E50-B 9/1/05

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!