EQUIPMENT CABLING CHAPTER 9: EQUIPMENT INSTALLATION SUSPENDED CEILING CAVITY SUSPENDED CEILING CAVITY FIGURE 9-7 COMMUNICATIONS CABLES IN SUSPENDED CEILINGS 9.9.4 AC POWER CABLING WARNING Facility AC wiring within junction boxes, receptacles, and switches shall be performed by a licensed and bonded electrical contractor. Personnel safety and liability hazards can result from AC wiring performed by installation personnel other than an electrical contractor. When an open equipment rack is used, hardwiring of power is not always possible. Mounting a dedicated simplex receptacle or receptacle assembly on the rack may be the most convenient method of supplying power, especially if multiple pieces of equipment are mounted on the rack. These receptacle assemblies can be pre-manufactured and mounted to the top face of an equipment rack. Mounting can also use a fabricated power pole mounted between racks. WARNING PERMITTED NOT PERMITTED SIGNAL OR TELEPHONE CABLES SIGNAL OR TELEPHONE CABLES Under no circumstances shall consumer-grade power outlet strips be used in any installation. Extension cords of any type shall not be used for connecting line power to communications equipment. 9-16 68P81089E50-B 9/1/05
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES EQUIPMENT CABLING 9.9.5 DC POWER CABLING In telecommunications environments, common DC systems are as follows: • +12 volt systems • +24 volt systems • -24 volt systems • -48 volt systems Traditional wireline telephone offices most often use -48V, sometimes called -BATT voltage, whereas many cellular, PCS, and other radio systems use +24 to 27 V. There are also instances of -24V systems. In U. S. installations, the most common practice is to use red cabling for the sourcing, fused, ungrounded, “hot” terminal. Black cabling is used for the return, unfused, grounded, terminal. (European installation practice uses blue insulation for the “hot” lead.) Chapter 8, “Power Sources,” discusses power cabling sizing and other installation concerns. The manual for the equipment being installed will also have specifications stating the cabling size required. Careful consideration must be given to cable size and length. See Chapter 6, “Power Sources” and cabling capacity for further information. FRONT VIEW SIDE VIEW FIGURE 9-8 CABLE MANAGEMENT SYSTEM WITH INTEGRATED RACK GROUND BUS BAR 68P81089E50-B 9/1/05 9-17
- Page 337 and 338: STANDARDS AND GUIDELINES FOR COMMUN
- Page 339 and 340: STANDARDS AND GUIDELINES FOR COMMUN
- Page 341 and 342: STANDARDS AND GUIDELINES FOR COMMUN
- Page 343 and 344: STANDARDS AND GUIDELINES FOR COMMUN
- Page 345 and 346: STANDARDS AND GUIDELINES FOR COMMUN
- Page 347 and 348: STANDARDS AND GUIDELINES FOR COMMUN
- Page 349 and 350: STANDARDS AND GUIDELINES FOR COMMUN
- Page 351 and 352: STANDARDS AND GUIDELINES FOR COMMUN
- Page 353 and 354: STANDARDS AND GUIDELINES FOR COMMUN
- Page 355 and 356: STANDARDS AND GUIDELINES FOR COMMUN
- Page 357 and 358: STANDARDS AND GUIDELINES FOR COMMUN
- Page 359 and 360: STANDARDS AND GUIDELINES FOR COMMUN
- Page 361 and 362: STANDARDS AND GUIDELINES FOR COMMUN
- Page 363 and 364: CHAPTER 8 MINIMIZING SITE INTERFERE
- Page 365 and 366: STANDARDS AND GUIDELINES FOR COMMUN
- Page 367 and 368: STANDARDS AND GUIDELINES FOR COMMUN
- Page 369 and 370: STANDARDS AND GUIDELINES FOR COMMUN
- Page 371 and 372: STANDARDS AND GUIDELINES FOR COMMUN
- Page 373 and 374: CHAPTER 9 EQUIPMENT INSTALLATION 9
- Page 375 and 376: STANDARDS AND GUIDELINES FOR COMMUN
- Page 377 and 378: STANDARDS AND GUIDELINES FOR COMMUN
- Page 379 and 380: STANDARDS AND GUIDELINES FOR COMMUN
- Page 381 and 382: STANDARDS AND GUIDELINES FOR COMMUN
- Page 383 and 384: STANDARDS AND GUIDELINES FOR COMMUN
- Page 385 and 386: STANDARDS AND GUIDELINES FOR COMMUN
- Page 387: STANDARDS AND GUIDELINES FOR COMMUN
- Page 391 and 392: STANDARDS AND GUIDELINES FOR COMMUN
- Page 393 and 394: STANDARDS AND GUIDELINES FOR COMMUN
- Page 395 and 396: STANDARDS AND GUIDELINES FOR COMMUN
- Page 397 and 398: STANDARDS AND GUIDELINES FOR COMMUN
- Page 399 and 400: STANDARDS AND GUIDELINES FOR COMMUN
- Page 401 and 402: STANDARDS AND GUIDELINES FOR COMMUN
- Page 403 and 404: STANDARDS AND GUIDELINES FOR COMMUN
- Page 405 and 406: APPENDIX A ELECTROMAGNETIC ENERGY I
- Page 407 and 408: STANDARDS AND GUIDELINES FOR COMMUN
- Page 409 and 410: STANDARDS AND GUIDELINES FOR COMMUN
- Page 411 and 412: STANDARDS AND GUIDELINES FOR COMMUN
- Page 413 and 414: STANDARDS AND GUIDELINES FOR COMMUN
- Page 415 and 416: STANDARDS AND GUIDELINES FOR COMMUN
- Page 417 and 418: STANDARDS AND GUIDELINES FOR COMMUN
- Page 419 and 420: STANDARDS AND GUIDELINES FOR COMMUN
- Page 421 and 422: STANDARDS AND GUIDELINES FOR COMMUN
- Page 423 and 424: STANDARDS AND GUIDELINES FOR COMMUN
- Page 425 and 426: STANDARDS AND GUIDELINES FOR COMMUN
- Page 427 and 428: STANDARDS AND GUIDELINES FOR COMMUN
- Page 429 and 430: STANDARDS AND GUIDELINES FOR COMMUN
- Page 431 and 432: STANDARDS AND GUIDELINES FOR COMMUN
- Page 433 and 434: APPENDIX B SOIL RESISTIVITY MEASURE
- Page 435 and 436: STANDARDS AND GUIDELINES FOR COMMUN
- Page 437 and 438: STANDARDS AND GUIDELINES FOR COMMUN
STANDARDS AND GUIDELINES FOR COMMUNICATION SITES EQUIPMENT CABLING<br />
9.9.5 DC POWER CABLING<br />
In tele<strong>communication</strong>s environments, common DC systems are as follows:<br />
• +12 volt systems<br />
• +24 volt systems<br />
• -24 volt systems<br />
• -48 volt systems<br />
Traditional wireline telephone offices most often use -48V, sometimes called -BATT voltage, whereas<br />
many cellular, PCS, <strong>and</strong> other radio systems use +24 to 27 V. There are also instances of -24V systems.<br />
In U. S. installations, the most common practice is to use red cabling <strong>for</strong> the sourcing, fused,<br />
ungrounded, “hot” terminal. Black cabling is used <strong>for</strong> the return, unfused, grounded, terminal.<br />
(European installation practice uses blue insulation <strong>for</strong> the “hot” lead.) Chapter 8, “Power Sources,”<br />
discusses power cabling sizing <strong>and</strong> other installation concerns. The manual <strong>for</strong> the equipment being<br />
installed will also have specifications stating the cabling size required. Careful consideration must be<br />
given to cable size <strong>and</strong> length. See Chapter 6, “Power Sources” <strong>and</strong> cabling capacity <strong>for</strong> further<br />
in<strong>for</strong>mation.<br />
FRONT VIEW SIDE VIEW<br />
FIGURE 9-8 CABLE MANAGEMENT SYSTEM WITH INTEGRATED RACK GROUND BUS BAR<br />
68P81089E50-B 9/1/05 9-17