AC POWER SPD REQUIREMENTS CHAPTER 7: SURGE PROTECTIVE DEVICES<br />

TABLE 7-4 SPD SPECIFICATIONS<br />

Type<br />

Service<br />

Configura<br />

tion MCOV<br />

Required Measured Testing<br />

Safety Per<strong>for</strong>mance<br />

Surge<br />

Voltage<br />

Rating<br />

(SVR) UL<br />

1449-2nd<br />

Edition<br />

Duty<br />

Cycle<br />

Test, IEEE<br />

C62.41,<br />

200A<br />

ringwave<br />

6kV, 500A 6kV, 200A,<br />

100 kHz<br />

Duty<br />

Cycle<br />

Test,<br />

IEEE<br />

C62.41<br />

Nominal<br />

Discharge<br />

Current<br />

(In) 1<br />

6kV, 3 kA 6kV, 10 kA<br />

Maximum<br />

Discharge<br />

Current<br />

(Imax)<br />

Manual Section 7.10.3 3 7.10.3.4 7.10.3 7.10.4<br />

Type 1<br />

High lightning exposure or<br />

main utility service on the load<br />

side of the disconnect<br />

Type 2<br />

High lightning exposure<br />

Service entrance<br />

Suitable <strong>for</strong> branch service<br />

applications on load side of<br />

utility disconnect<br />

Type 3<br />

Branch circuit protection<br />

device<br />

120/240 1φ 145 330 n/a Required VPL<br />

Recorded<br />

120/208 3φ 145 330 n/a Required VPL<br />

Recorded<br />

480/277 1φ 320 800 n/a Required VPL<br />

Recorded<br />

230/380 3φ 280 n/a n/a Required VPL<br />

Recorded<br />

120/240 1φ 145 400 n/a Required VPL<br />

Recorded<br />

120/208 3φ 145 400 n/a Required VPL<br />

Recorded<br />

480/277 1φ 320 800 n/a Required VPL<br />

Recorded<br />

230/380 3φ 280 n/a n/a Required VPL<br />

Recorded<br />

120 V 145 330 Required n/a n/a n/a<br />

230-240V 280 570 Required n/a n/a n/a<br />

1. Nominal Surge Current Value (In) is a single 10 kA impulse.This single impulse shall be applied at the SPDs <strong>and</strong><br />

the Voltage Protection Level (VPL) measured <strong>and</strong> recorded.<br />

Required<br />

Required<br />

Required<br />

Required<br />

Required<br />

Required<br />

Required<br />

Required<br />

7-32 68P81089E50-B 9/1/05